Technical data
● COM = 3F8H
Interrupt (IRQ) and I/O address have to correspond to the settings
carried out in BIOS.
7.2.6 XUSB Interfaces
XUSB 1 to 8 – serial interfaces for
printers, scanners, drives
The devices feature eight USB interfaces on the connector panel (XUSB).
These interfaces are compatible to USB 1.1 and USB 2.0.
The maximum power consumption of the connected devices must
not exceed 500 mA. If the load exceeds 500 mA, the internal current
monitoring is activated.
Fig.7-6: USB interfaces
Pin Function
1 USB power supply (max. 500 mA)
2 Data -
3 Data +
4 USB ground
7.2.7 Ethernet Interface XLAN
XLAN1 and XLAN2 – network con‐
nection
The control cabinet PC can be connected to an Ethernet network via the XLAN
Ethernet interface.
The LAN assignment in Windows XP to the XLAN devices at the device is preset
as follows:
Designation in Windows XP Designation at the housing
Local Area Connection XLAN2
Local Area Connection 2 XLAN1
Fig.7-7: Assignment of the LAN interfaces in the operating system to the inter‐
faces at the device
RJ45, female connector, 8-pin
Type: Ethernet 10/100/1000
Cable length: 100 m max.
Transmission rate: 10, 100 and 1000 MBit/s
40/101 Bosch Rexroth AG | Electric Drives
and Controls
Rexroth IndraControl VSB 40.3 | Project Planning Manual
PC Box