ELECTRONIC CONTROL & PROTECTION CATALOG Current and Voltage Monitors • Overload Relays • Custom Electronic Controls Intrinsically-Safe Relays • Motor and Pump Controls SymCom_catalog cover spread14.
We Are The GLOBAL EXPERTS in Electrical Safety and Productivity Global Resources for A Global Market From mining installations in Chile to semiconductor fabrication plants in Taiwan, customers trust Littelfuse electrical safety products and services to keep systems running and workers protected. Our innovation, proven technical expertise, broad portfolio of products and services and global resources enable us to provide objective, comprehensive solutions for each unique application.
TABLE OF CONTENTS Complete Motor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Overload Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (777-P2, 777-xxx-P2, 777-TS, 777-FT, 777VA-xx, 77C) Power Monitors . . . . . . . . . . . . . . . . . . . .
Overload Relays Monitoring, control, and protection are critical and necessary functions in motor and pumping applications. SymCom’s single-phase and three-phase UL listed enhanced overload relays monitor for both line-side voltage problems and load-side current faults, providing an added layer of protection over voltage monitors and other basic overload relays. All SymCom overload relays are user configurable and cover a wide range of voltages and currents, making them the most versatile in the industry.
Overload Relay Model 777 Product Line single-phase and 3-phase current & voltage monitor, on-board display, optional communications to PLC/SCADA/monitoring systems The Model 777 / 77C Features: is a fully programmable electronic overload relay designed to protect any motor drawing 2-800 full load amps (external CTs are required above 90 amps).
Overload Relay Model 777 Product Line single-phase and 3-phase current & voltage monitor, on-board display, optional communications to PLC/SCADA/monitoring systems Specifications Input Characteristics Line Voltage 777-P2, 777-LR-P2, 777-HRG-P2 . . . . . . . . . . . . . . . . . . . . . . . . . . . 777-TS, 777-LR-TS, 777-LR-HRG-P2. . . . . . . . . . . . . . . . . . . . . . . . . 777VA-02, 777VA-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77C, 77C-LR, 777-MV-P2 . . . . . .
Overload Relay Model 777 Product Line single-phase and 3-phase current & voltage monitor, on-board display, optional communications to PLC/SCADA/monitoring systems -P2 The 777-P2 protects 200-480VAC, 2-800 full load amp (FLA) motors and provides protection from overvoltage and undervoltage, overcurrent and undercurrent and unbalanced voltage or unbalanced current through adjustable setpoints.
Power Monitors Many pumping applications require advanced power monitoring and control. SymCom enhanced power monitors provide all of the protections and features included with an enhanced overload relay, but are designed specifically for applications where there is not much change in current between a load and no load condition.
Power Monitors Model 777-KW/HP-P2 Product Line 3-phase current & voltage monitor, on-board display, optional communications, underpower trip for more accurate/faster motor protection versus undercurrent trip The Model Series 777-KW/HP-P2 Features: • Low power protection High power protection • Overcurrent (overload) • High voltage • Low voltage • Current unbalance • Voltage unbalance • Ground fault detection • Modbus communication • Built-in 3-digit display for setup and diagnostics • Network communica
Power Monitors Model 777-KW/HP-P2 Product Line 3-phase current & voltage monitor, on-board display, optional communications, underpower trip for more accurate/faster motor protection versus undercurrent trip Specifications Input Characteristics Line Voltage 777-KW/HP-P2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 777-LR-KW/HP-P2, 777-MLR-KW/HP-P2 . . . . . . . . . . . . . . . . . . 777-HVR-KW/HP-P2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Monitors Model 777-AccuPower 3-phase current & voltage monitor, on-board display, calculates motor output power with optional 4-20mA communications The Model 777-AccuPower Features: is a fully-programmable 3-phase motor and pump protection relay. It allows motor hp rating, full load amps, efficiency and power factor to be entered and will accurately calculate motor output power.
Communication Modules Models RS485MS-2W / CIO-MB communication link to PLC/SCADA/monitoring systems The RS485MS-2W Features: is required to enable the Modbus communications function on Model 77x-type products. This module is required when the RM-1000, RM-2000 or other Modbus capable device is used with 77x-type products.
Communication Modules Models CIO-DN-P / CIO-777-PR communication link to PLC/SCADA/monitoring systems The CIO-DN-P / CIO-120-DN-P Features: are convenient and cost-effective Devicenet™ interfaces capable of providing discrete control and monitoring of motor starters, drives and other devices over a Devicenet™ network. • Can be used in both new and existing installations • Can be used as stand-alone or with a 777 Plus series unit • Reduced field wiring.
Communication Modules Models CIO-EN / COM 4-20mA communication link to PLC/SCADA/monitoring systems Features: The CIO-EN Module (non-POE) is a convenient and cost-effective Modbus-TCP and Modbus-RTU interface capable of providing discrete control and monitoring of an overload relay over a Modbus network. For more information see: See Appendix A, page 66, Figure 3 for dimensional drawing.
Remote Monitor Model RM-1000 remote monitoring, fault history, can read up to sixteen 777 models The RM-1000 is a motor-monitoring device to be used in conjunction with SymCom’s Model 777 family of products (excluding the P1 Series), 77C family of products and the Model 601 voltage monitors, via Modbus protocol with a communications module. The RM-1000/777 motor management system combines unsurpassed electronic motor protection and critical, user-friendly, motor monitoring.
Remote Monitor Model RM-2000 remote monitoring, real-time clock, precise fault details, kwH The RM-2000 Features: is a motor-monitoring device to be used in conjunction with SymCom’s Model 777 family of products (excluding the P1 Series), 77C family of products and the Model 601 voltage monitors, via Modbus protocol with a communications module. The RM-2000/777 motor management system combines unsurpassed electronic motor protection and critical, user-friendly, motor monitoring.
Software Solutions Software programming and monitoring of 777 models, data and fault logging Solutions is a software application that provides the ability to configure and monitor Modbus (Solutions-M) or DeviceNet™ (Solutions-D) networks. SymCom’s Solutions Software features include data logging, real-time data monitoring and fault and event monitoring.
Ground Fault Monitor Model 601-CS-D-P1 monitors a zero-sequence CT for high accuracy ground fault protection The 601-CS-D-P1 3-phase power monitor is a fully programmable electronic power monitor designed to monitor 3-phase systems. The 601-CS-D-P1 has a single relay that can be configured as a general purpose network output or to trip on ground faults. The 601-CS-D-P1 monitors ground fault current, phase currents, phase voltages, power factor and frequency.
3-Phase Voltage Monitors All SymCom voltage monitors are microcontroller based and are factory calibrated for highly accurate and precise voltage measurements to provide high sensitivity while minimizing nuisance tripping. The high accuracy and precision of these devices allows them to detect a single-phase condition or voltage unbalance even with regenerated voltages present.
3-Phase Voltage Monitor Model 80 3-phase reverse-phase protection Features: The Model 80 is designed to continuously monitor phase rotation of 3-phase systems. Critical applications include fan motors, scroll compressors, grinders, conveyor systems, elevators and escalators. A solid-state phase-sensing circuit drives an internal electromechanical relay which is energized when proper phase rotation is applied. An LED indicator illuminates when phase rotation is correct. Reset is automatic.
3-Phase Voltage Monitor Model 102A 3-phase voltage/phase monitor, high voltage option, panel mount, adjustable or manual restart delay The Model 102A Features: is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-480VAC, 50*/60Hz motors regardless of size. The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically selects between the 200V and 400V range.
3-Phase Voltage Monitor Model 201A 3-phase voltage/phase monitor, 8-pin socket mount, optional high voltage trip Features: The Model 201A is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-480VAC, 50/60Hz motors regardless of size. The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically selects between the 200V and 400V range.
a ute) ) 3-Phase Voltage Monitor Model 201A-AU 3-phase voltage/phase monitor, 8-pin socket mount, adjustable trip/restart delays & voltage unbalance percentage The Model 201A-AU is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-480VAC, 50/60Hz motors regardless of size. The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically selects between the 200V and 400V range.
3-Phase Voltage Monitor Model 201-xxx-DPDT 3-phase voltage/phase monitor, 11-pin socket mount, two isolated Form C relays The Model 201-xxx-DPDT Features: is an 11-pin octal base plug-in voltage monitor designed to protect 3-phase motors regardless of size. The 201-100-DPDT is used on 95-120VAC, 50/60Hz motors and the 201-200-DPDT is used on 190-240VAC, 50/60Hz motors to prevent damage caused by incoming voltage problems.
3-Phase Voltage Monitor Model 202 / 202-RP 3-phase voltage/phase monitor, panel mount, adjustable or manual restart delay (-RP reverse-phase protection only) The Model 202 is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-480VAC, 50*/60Hz motors regardless of size. The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically selects between the 200V and 400V range.
3-Phase Voltage Monitor Model 250A 3-phase voltage/phase monitor, panel mount, adjustable or manual restart delay, 2 Form C relay contacts The Model 250A is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-480VAC, 50*/60Hz motors regardless of size. The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically selects between the 200V and 400V range.
3-Phase Voltage Monitor Model 350 3-phase voltage/phase monitor, panel mount, optional 1 or 2 15A rated relay contacts Features: The Model 350 is a heavy-duty voltage monitor. This product should be used when high current relays or dual contacts are required, or 480V controls are used. Since the Model 350 uses heavy-duty relays, it comes in fixed voltage range models rather than a dual auto-ranging version like the Model 250. The Model 350-200 has a 15A general purpose contact.
3-Phase Voltage Monitor Model 355 3-phase voltage/phase monitor, panel mount, adjustable trip/restart delays & voltage unbalance percentage, optional 2 each 480V-rated relays The Model 355 is a 3-phase voltage monitor with adjustable trip and restart delay, adjustable voltage unbalance and multiple diagnostic lights.It is perfect for heavy-duty applications that need both protection and simple user-friendly diagnostics. Applications include pump panels, commercial HVAC, oil rigs and others.
3-Phase Voltage Monitor Model 455 3-phase voltage/phase monitor, panel mount, has add’l voltage inputs for monitoring load side of contactor for contactor failure & works with Informer-MS diagnostic tool Features: The Model 455 3-phase voltage monitor combines load and line side monitoring to alert the user of contactor failure or impending contactor failure. The line side monitoring will protect the motor from damaging line side conditions prior to the motor starting.
3-Phase Voltage Monitor Model Informer-MS wireless hand-held diagnostic tool reads Model 455 to display last 20 fault causes, real-time voltage/phase & much more The Informer-MS Features: The Informer-MS uses an infrared receiver to read valuable information transmitted from the Model 455*, which can be helpful for troubleshooting the system. A green communication status light indicates the Informer-MS is receiving data from the MotorSaver®.
3-Phase Voltage Monitor Model 460 Product Line 3-phase voltage monitor, din rail mount, adj trip/restart delays & V unbalance %, and options for 2 individual contacts, adj high/low voltage trip pts & much more The Model 460 is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-480VAC, 50/60Hz motors regardless of size. The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically selects between the 200V and 400V range.
3-Phase Voltage Monitor Model 601 3-phase voltage & frequency monitor, on-board display, adjustable trip delay, optional communications to PLC/SCADA/monitoring systems The Model 601 Features: is a fully-programmable voltage monitor designed to protect 3-phase motors. It can be used as a standalone product or networked with an RM-1000, RM-2000, PLC, computer or SCADA system.
Single-PhaseVoltage Monitors Product Selection Matrix www.symcom.com • 800-843-8848 • fax: 605-348-5685 CATALOG_SYMCOM_2014.indd 31 Single-Phase Voltage Monitors All of SymCom’s single-phase voltage monitors are micro-controller based and are factory calibrated for highly accurate and precise voltage measurements to provide high sensitivity while minimizing nuisance tripping.
Model 50R Single-Phase Voltage Monitor single-phase voltage monitor, panel mount, optional high voltage, variable restart or trip delay The Model 50R single-phase voltage monitor has a voltage-sensing circuit which constantly monitors the single-phase power for a low voltage condition. Single-phase motors on fans, compressors, air conditioners, heat pumps, well pumps, sump pumps and small conveyor motors are all applicable to the Model 50R.
Model 201-xxx-SP Single-Phase Voltage Monitor single-phase voltage/phase monitor, 8-pin socket mount The Model 201-xxx-SP is an 8-pin octal-base, plug-in voltage monitor designed to protect single-phase motors regardless of size. The 201-100-SP is used on 95-120VAC, 50/60Hz motors to prevent damage caused by low voltage. The Model 201-200-SP is used on 190240VAC, 50/60Hz motors. The 201-200-SP-T-9 is a pin-for-pin replacement for a Time Mark® #260 Series voltage monitor.
Model 201-xxx-SP-DPDT Single-Phase Voltage Monitor single-phase voltage/phase monitor, 8-pin socket mount, two isolated Form C relays The Model 201-xxx-SP-DPDT Features: is an 8-pin octal-base, plug-in voltage monitor designed to protect single-phase motors regardless of size. The 201-100-SP-DPDT is used on 95120VAC, 50/60Hz motors to prevent damage caused by low voltage. The 201-200-SP-DPDT is used on 190-240VAC, 50/60Hz motors.
Model 202-200-SP Single-Phase Voltage Monitor single-phase voltage monitor, panel mount, adjustable or manual restart delay The Model 202-200-SP voltage monitor is designed to protect singlephase motors regardless of size. It can be used with 190V-240VAC, 50/60Hz motors to prevent damage caused by incoming power problems. A unique microcontroller-based voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions.
Model 460-xxx-SP Single-Phase Voltage Monitor single-phase voltage monitor, din rail mount, adjustable restart delay The Model 460-100-SP is used on 95-120VAC, 50*/60Hz single-phase motors and the 460-200-SP is used on 190-240VAC, 50*/60Hz single-phase motors to protect them from damaging high and low voltage conditions. An adjustment knob allows the user to set a 1-500 second restart delay.
Current Monitors Current Monitors have many advantages over voltage monitors because they provide protection against both supply line and load side faults when the motor is running. They protect against single-phasing and current unbalance problems that can be caused by voltage supply problems, bad contactors, loose wiring, bad wires or damaged motors. They also provide very reliable overload and underload protection.
Current Monitor Model 520CS 3-phase current monitor, programmable motor acceleration trip delay from 0-50 seconds The Model 520CS is a fully-programmable, microcontroller-based, current-sensing device designed to monitor 3-phase pumps. Unlike the Model 520CP which is designed to work with motors that have ramp-up times of 4 seconds or less, the Model 520CS has a programmable motor acceleration time that can be set from 0-50 seconds.
Model 520CP Current Monitor 3-phase current monitor, for use with motors having ramp up times of 4 seconds or less, second relay optional on 115VAC version The Model 520CP is a fully-programmable, microcontroller-based, current-sensing device designed to monitor 3-phase pumps or systems with ramp-up times of 4 seconds or less. Applications include submersible pumps, booster pumps, reverse osmosis systems, centrifugal pumps, vertical turbine pumps, oil well pumps, chemical pumps or other similar systems.
Pump Controllers Pump Controllers are innovative products for controlling a single pump or multiple pumps. Some models can be used to detect pump seal leaks and motor overheating on submersible pumps. Other models can be used as a five-channel pump controller or five-channel switch to support all popular industry standard multi-pump configurations. ts 4.
Pump Controller Model PC-102 either a dual seal-leak detector (-DL) or seal-leak & over-temperature detector (-LT), adjustable seal-leak sensitivity The PC-102 -DL is a dual seal-leak detector. The inputs are used to sense seal failures on pumps. When water is detected, the associated output relay is energized. The input logic may be selected to be direct or inverted by using DIP switches on the side of the device. -LT is a seal-leak and over-temperature detector.
Pump Controller Model PC-105 pump controller with duplex, triplex or quadplex functionality or 5-channel relay The PC-105 is a 5-channel pump controller designed to handle multiple pump applications. Alternatively, it can operate as a 5-channel switch. The PC-105’s control functions support all of the popular industry-standard multi-pump pump-up and pump-down configurations. It can indicate low, high and out-of-sequence alarms and use alternating and non-alternating pump control.
Pump Controller Model PC-xxx-LLC-CZ / PC-xxx-LLC-GM liquid level control, 8-pin plug-in for two probe inputs with SPDT output The PC-xxx-LLC-CZ & PC-xxx-LLC-GM Features: are liquid level control relays used to control conductive liquid pumping operations in a pumpup or pump-down application. The units come in two different voltage ranges (see specs below). The units have an adjustable sensitivity knob (4.
Model 460-15-100-LLS Liquid Level Sensor single-channel liquid level sensor, din rail mount, adjustable debounce timer The Model 460-15-100-LLS is a liquid level sensor to detect the presence of conductive liquids. A probe is mounted at the desired tank level and connected to the PumpSaver®. When the probe is submersed, the PumpSaver’s output contacts will change state as soon as the debounce time expires.
n.) Seal-Leak Detector Model 460-15-100-SLD single-channel seal-leak detector, din rail mount, adjustable sensitivity setpoint The Model 460-15-100-SLD is a seal-leak detector to sense seal failures on submersible pumps. A microcontroller-based relay that monitors the shaft seal of a submersible pump motor. A resistive probe is installed in the seal cavity. If water leaks into the pump, the resistance measured by the probe decreases.
Model 201-100-SLD Seal-Leak Detector single-channel seal-leak detector, 8-pin socket mount, adjustable sensitivity point The Model 201-100-SLD is an 8-pin plug-in style seal-leak detector to sense seal failures on submersible pumps. A microcontroller-based relay that monitors the shaft seal of a submersible pump motor. A resistive probe is installed in the seal cavity. If water leaks into the pump, the resistance measured by the probe decreases.
Alternating Relay Model ALT 8-pin plug-in, single or dual float input, with or without manual switch The Model ALT alternating relays are used to alternate between two loads. The ALT is commonly used in duplex pumping applications to balance the runtime of both pumps. The Model ALT-S is used in single high-level float applications. When the float switch opens, the alternating relay changes state, forcing the other pump to run the next time the float closes.
Alternating Relay Model ALT-xxx-1-SW / ALT-xxx-3-SW 11-pin plug-in for single float input with DPDT output / 8-pin plug-in for three float input with dual load output The Model ALT-xxx-1-SW and ALT-xxx-3-SW Features: • Debounce time delay LED load indicators • Built-in switch to manually force a specific load (pump) to operate Approvals: are used to alternate between two loads and are commonly used in duplex pump-up and pumpdown applications to balance the runtime of both pumps.
Alternating Relay Model 50R-400-ALT 480VAC application, panel mount The Model 50R-400-ALT alternating relays are used to alternate between two loads, most commonly in duplex pumping and compressor applications to balance the runtime of both loads. When used in single float applications, the alternating relay changes state after the float switch opens*, forcing the other pump to run the next time the float closes.
Alarm Controller/Battery Charger Model ACBC-120 Alarm Controller and Battery Charger for pump control panels The Model ACBC-120 Features: is a dual purpose alarm controller/battery charging unit. When there is a loss of 120VAC power, the ACBC-120’s primary function as an alarm controller activates. When this power loss occurs, input power is switched to a 12VDC, lead-acid, rechargeable backup battery and a 12VDC alarm consisting of a strobe light and/or a horn is activated.
Intrinsically Safe Relays/Controllers Am le I nv p er G t 7 e Am ne ed Lo r al p gi G P c 8 Am ene urp os ra p l e G D en Pu IN rp e o r R a s Su ail M l Pu e rp rfa ou os ce n e O M tab ct l o e un al ta Ba bl O se e ut pu tS Pr ob tatu s e Li gh Pr Res ob ts is ta e nc R es e 10 is ta nc k O h e 10 ms 0k O hm s el ab ct 5 Se 5 4 le el nn ha C ha C C 3 2 nn el el ha nn nn nn ha C ha 91 L 1 U MODEL C 3 el Product Selection Matrix ab e ju d te ua A Ev al ay el R SH
Intrinsically Safe Relay Model ISS-100 / ISS-101 single-channel intrinsically safe switch, either din rail mount (100) or 8-pin socket mount (101) The Model ISS-100 & ISS-101 Features: For more information on the ISS-100 see: See Appendix A, page 69, Figure 11 for dimensional drawing.
Intrinsically Safe Relay Model ISS-102 two-channel intrinsically safe switch, din rail mount, options include switch only (-DCS), single latching output (-LC), or multi-function controller (-MC) The ISS-102 SymCom’s Model ISS-102 two-channel, intrinsically-safe switch is designed for multiple uses including a pump-up/pump-down (latching) controller or two-channel switch.
Intrinsically Safe Relay Model ISS-105 five-channel intrinsically safe switch, din rail mount, programmable for alternating/control of 2, 3 or 4 pumps or 5-channel relay, optional 5-channel switch only (-ISO) The ISS-105 IS Super Cell is a “smart” five-channel intrinsically safe relay and pump controller. The IS Super Cell can be configured for a wide variety of applications including alternating or non-alternating duplex, duplex separate pump stop (SPS), triplex and quadplex applications.
Single-Phase PumpSavers SEE OUR SINGLE-PHASE PUMPSAVER CATALOG FOR OUR FULL LINE OF SINGLE-PHASE PUMPSAVERS (AVAILABILITY SUBJECT TO CHANGE). TABLE OF CONTENTS Submersible Pumps - Optimized Protection Whose Control Box do you have? Franklin™, CentriPro™ or Pentek® ................................................................... 2 115VAC ¹⁄з-½hp... 111-Insider-P 230VAC ¹⁄з-1hp... 231-Insider-P Grundfos® ....................................................................................................
Load Sensors SymCom’s load sensors are designed to be adaptable to many different applications. They utilize a CT (current transformer) inside the unit to read the current of the equipment being monitored. The Model LSR-0 is a self-powered unit used as a proof relay. The LSRX and LSRX-C units are also self-powered proof relays with either 0.25” fast-on connectors (LSRX) or depluggable connectors (LSRX-C) for use in OEM equipment.
Load Sensor Model LSR-0 self-powered load sensor / low-cost proof relay The Model LSR-0 is a self-powered load sensor intended for use as a proof relay. It is used to verify that current is flowing as intended. It has a guaranteed 15A pullin current and 2.5A drop-out current. Proof relays are typically used to interlock fans, compressors, motors, heating elements and other devices.
Load Sensor Model LSR-24 load sensor, Form C contacts to switch alarm circuits, contactors or any resistive or inductive load The Model LSR-XXX load sensors use current levels to determine feed rates, tool wear, loss of prime on pumps, mixer viscosity and all types of overload and underload conditions. They may also be used to stage pump motors, chillers and other machinery.
Load Sensor Model LSRU load sensor, choice of three types of control logic and three amperage ranges The Model LSRU is a microcontroller-based family of load sensors. The LSRU family of products employ three basic types of control logic: motor control logic, alarm logic and feed control logic.
Load Sensor Model LSRX self-powered load sensor, low-cost proof relay The Model LSRX is an AC current sensor designed to energize the output contact whenever 4.5 Amps or greater is present. The LSRX is used commonly as an AC current proof relay to indicate if a motor is operating.
Auxiliary Products • • • • • • • • • • T-10 Timers CP-5 Single-phase Current Monitors Current Transformers (donut style & foot mounted) NEMA-3R Enclosures Steel Enclosure for RM-1000 Electronic Megohmmeter Informer Infrared Kit OL-RESET Manual Remote Reset Kit Octal Sockets www.symcom.com • 800-843-8848 • fax: 605-348-5685 CATALOG_SYMCOM_2014.
Timer Model T-10 on-delay timer, 115, 230 or 460V control power, 6 seconds to 10 minutes adjustable, LED indicator The Model T-10-(xxx) on-delay timer is a solid-state electronic device that provides accurate and reliable timing for control circuits up to 460VAC. The T-10 features a user-selectable time delay from 6 seconds to 10 minutes (0.5 to 12 seconds on the T10S-400 model) and SPDT output contacts. When power is applied to the T-10, it immediately begins its timing cycle.
Single-Phase Current Monitor Model CP-5 single-phase current monitor, adjustable trip delay, adjustable trip level, trips on undercurrent Features: The Model CP-5 is an undercurrent monitor designed to monitor one leg of a 3-phase system. It is commonly used as a tower monitor on center pivot irrigation systems to detect stalled or jammed towers to prevent overwatering. The CP-5 has both an adjustable trip level and an adjustable trip delay timer.
Current Transformers instrumentation and metering transformers, choice of donut or foot mounted and 1 - 3” diameter opening Current Transformers SymCom offers a wide array of instrument rated current transformers.
Auxiliary Products enhanced ground fault protection, enclosures, diagnostic tool, enhancements/accessories for multiple SymCom products Enclosure Metal NEMA-3R electrical box (6” H x 6” W x 4” D) with lenses for viewing the single-phase PumpSaver® status lights Part Number: NEMA-3R-L The RM-1000-ENCL is a steel enclosure for protecting a SymCom RM-1000 remote communications monitor from adverse affects of weather and vandalism, while allowing normal communications connections to the RM-1000 unit.
Appendix A - Dimensional Drawings Figure 1 (777, 77C, 601) Figure 2 (COM modules) 0.200 [5.08] 2.650 [67.31] 2.280 [57.91] 2.08 [52.83] 3.050 [77.47] 3.100 [78.74] 3.600 [91.44] 3.850 [97.79] 2.900 [73.66] OPTIONAL LOOP HOLES B MAIN CONDUCTOR PASS HOLES A 1.200 [30.48] C 0.77 [19.56] 4.700 [119.38] D. 0.650 [16.51] 2.16 [54.86] 5.050 [128.27] inches [millimeters] 3.600 [91.44] 3.850 [97.79] inches [millimeters] Figure 3 (CIO modules) DEPLUGGABLE TERMINAL BLOCKS 0.830 [21.
Appendix A - Dimensional Drawings Figure 4 (RM-1000) 4.544 [115.417] 0.75 [19.05] 2.5 [63.5] 3.619 [91.922] 1.425 [36.195] 0.9 [22.86] inches [millimeters] Figure 5 (RM-2000) 1.02 [25.98] 5.97 [151.51] 0.99 [25.15] 0.75 [19.05] 3.5 [88.9] 6.37 [161.67] #6 MOUNTING SCREWS PROVIDED inches [millimeters] PANEL 0.062 - 0.100 THICK [1.574 - 2.54] www.symcom.com • 800-843-8848 • fax: 605-348-5685 CATALOG_SYMCOM_2014.
Appendix A - Dimensional Drawings Figure 6 (80) Figure 7 (102, 250, 350, 355, 455, 50R, CP-5, T10) 2.0 [50.8] 1.47 37.2 NC L1 190 - 480 VAC 50/60 HZ COM NO CONTACT RATING 10 A @ 240 VAC RELAY ON 2.93 74.4 2.0 [50.8] MODEL 80 NRTL/C REVERSE PHASE RELAY L2 L3 P/N - 80 - A 200V 400V 4.50 114.3 MADE IN USA 0.38 9.5 5.27 133.9 MOUNTING HOLE FOR NO. 8 TO 0.25" SCREW inches [millimeters] 0.50 [12.7] 0.375 [9.525] 2.17 55 Typ. 0.75 [19.05] 0.25 [6.35] 2.95 [74.9] Max inches [millimeters] 0.
Appendix A - Dimensional Drawings Figure 10 (Informer, Informer-MS) Figure 11 (460, ISS-100, ISS-102, PC-102) Figure 12 (520-CP, 520-CS) FRONT 8.25 [209.55] 7.5 [190.50] 6.75 [717.45] BOTTOM 2.5 [63.50] 3.75 [95.25] 5.25 [133.35] www.symcom.com • 800-843-8848 • fax: 605-348-5685 CATALOG_SYMCOM_2014.indd 69 3.25 [82.
Appendix A - Dimensional Drawings Figure 13 (ISS-105, PC-105) Figure 14 (LSR, LSR-0, LS-524, LSRU) 0.192 [0.488] 3.56 [90.43] 1.07 1.67 [42.42] [27.18] 3.511 [89.179] 3.12 [79.25] 0.621 [15.773] 3.750 [89.18] 0.725 [18.415] 5.025 [127.365] 2.30 [58.42] inches [millimeters] 2.350 [59.690] Figure 15 (LSRX) 0.72 18.2 inches [millimeters] 2.50 63.4 1.78 45.1 0.20 5.1 SIDE VIEW 2.70 68.5 2.25 57.2 1.13 28.6 C L C'BORE FOR #8 SCREW TOP VIEW LED STATUS INDICATOR 70 CATALOG_SYMCOM_2014.
Appendix B - Typical Wiring Diagrams Figure 1 Figure 2 TYPICAL WIRING DIAGRAM FOR MODEL 777 (20 TO 90 amps) Figure 3 TYPICAL WIRING DIAGRAM FOR MODEL 77C WITH MOTOR CONTROL Figure 4 TYPICAL WIRING DIAGRAM FOR MODEL 77C WITH EXTERNAL CT A www.symcom.com • 800-843-8848 • fax: 605-348-5685 CATALOG_SYMCOM_2014.
Appendix B - Typical Wiring Diagrams Figure 5 TYPICAL WIRING DIAGRAM FOR RM-1000 Figure 6 TYPICAL WIRING DIAGRAM FOR RM-2000 72 CATALOG_SYMCOM_2014.indd 72 www.symcom.
Appendix B - Typical Wiring Diagrams Figure 7 Figure 8 TYPICAL WIRING DIAGRAM FOR MODEL 601-CS-D-P1 L1 L2 L3 L1 200 400 L2 CONTROL VOLTAGE 240 VAC MAX.
Appendix B - Typical Wiring Diagrams Figure 13 Figure 14 TYPICAL WIRING DIAGRAM FOR MODEL 201A-AU WITH MOTOR CONTROL TYPICAL WIRING DIAGRAM FOR MODEL 201A-AU WITH MOTOR CONTROL L1 L1 L2 L2 L3 L3 Figure 15 Figure 16 TYPICAL WIRING DIAGRAM FOR MODEL 201A-AU TYPICAL WIRING DIAGRAM MODEL 201-xxx-DPDT WITH ALARMFOR CONTROL INPUT POWER TYPICAL WIRING DIAGRAM FOR MODEL 201A-AU WITH ALARM CONTROL L1 L2 L1 L2 L3 L3 L3 L2 L1 6 7 8 LIGHT HORN 9 7 8 9 10 10 4 4 3 11 1 11 2 2 3 LIGHT H
Appendix B - Typical Wiring Diagrams Figure 19 TYPICAL WIRING DIAGRAM FOR MODEL 250A Figure 20 TYPICAL WIRING DIAGRAM FOR MODEL 350 WITH MOTOR CONTROL MODEL 250 Figure 21 TYPICAL WIRING DIAGRAM FOR MODEL 355 WITH MOTOR CONTROL Figure 23 TYPICAL WIRING DIAGRAM FOR MODEL 455 WITH MOTOR CONTROL USING A 3-POLE CONTACTOR www.symcom.com • 800-843-8848 • fax: 605-348-5685 CATALOG_SYMCOM_2014.
Appendix B - Typical Wiring Diagrams Figure 25 Figure 26 TYPICAL WIRING DIAGRAM FOR MODEL 460 WITH MOTOR CONTROL Figure 27 TYPICAL WIRING DIAGRAM FOR MODEL 601 WITH MOTOR CONTROL TYPICAL WIRING DIAGRAM FOR MODEL 460-14/15 WITH MOTOR CONTROL Figure 28 TYPICAL WIRING DIAGRAM FOR MODEL 50R WITH MOTOR CONTROL 50R Figure 29 TYPICAL WIRING DIAGRAM FOR MODEL 201-SP WITH MOTOR CONTROL 76 CATALOG_SYMCOM_2014.indd 76 Figure 30 TYPICAL WIRING DIAGRAM FOR MODEL 201-xxx-SP-DPDT www.symcom.
Appendix B - Typical Wiring Diagrams Figure 31 TYPICAL WIRING DIAGRAM FOR MODEL 202-200-SP WITH MOTOR CONTROL Figure 33 TYPICAL WIRING DIAGRAM FOR MODEL460-xxx-SP WITH MOTOR CONTROL Figure 32 TYPICAL WIRING DIAGRAM FOR MODEL 202-200-SP WITH ALARM CONTROL Figure 34 TYPICAL WIRING DIAGRAM FOR MODEL 520 WITH MOTOR CONTROL MODEL 520 www.symcom.com • 800-843-8848 • fax: 605-348-5685 CATALOG_SYMCOM_2014.
Appendix B - Typical Wiring Diagrams Figure 35 Figure 36 TYPICAL WIRING DIAGRAM FOR PC-102CICI-DL TYPICAL WIRING DIAGRAM FOR PC-102CICI-LT Figure 37 Figure 38 TYPICAL WIRING DIAGRAM FOR PC-xxx-LLC-CZ 78 CATALOG_SYMCOM_2014.indd 78 TYPICAL WIRING DIAGRAM FOR PC-xxx-LLC-GM www.symcom.
Appendix B - Typical Wiring Diagrams Figure 39 Figure 40 TYPICAL WIRING DIAGRAM FOR MODEL 460-15-100-SLD TYPICAL WIRING DIAGRAM FOR MODEL 460-15-100-LLS Figure 41 Figure 42 TYPICAL WIRING DIAGRAM FOR MODEL ALT-S TYPICAL WIRING DIAGRAM FOR MODEL 201-xxx-SLD Figure 43 Figure 44 TYPICAL WIRING DIAGRAM FOR A MODEL ALT-X (CROSS CONNECTED) TYPICAL WIRING DIAGRAM FOR ALT-xxx-1-SW ALTERNATING RELAY S1 F1 1 8 S2 2 7 3 6 L1 4 F2 L2 5 F1 - F2: 1-2A TYPICAL SIZE FOR CONTACTOR COILS F3 PUMP #1 M
Appendix B - Typical Wiring Diagrams Figure 45 TYPICAL WIRING DIAGRAM FOR ALT-xxx-3-SW Figure 47 Figure 46 TYPICAL WIRING DIAGRAM FOR MODEL 50R-400-ALT Figure 48 TYPICAL WIRING DIAGRAM ACBC-120 Figure 49 TYPICAL WIRING DIAGRAM FOR MODEL LSRU 80 CATALOG_SYMCOM_2014.indd 80 www.symcom.
Appendix B - Typical Wiring Diagrams Figure 50 TYPICAL WIRING DIAGRAMS FOR MODEL LSR-0 Figure 51 TYPICAL WIRING DIAGRAM FOR MODEL T-10 Figure 52 TYPICAL WIRING DIAGRAM FOR MODEL CP-5 www.symcom.com • 800-843-8848 • fax: 605-348-5685 CATALOG_SYMCOM_2014.
NOTES 82 CATALOG_SYMCOM_2014.indd 82 www.symcom.
NOTES www.symcom.com • 800-843-8848 • fax: 605-348-5685 CATALOG_SYMCOM_2014.
NOTES 84 CATALOG_SYMCOM_2014.indd 84 www.symcom.
Index 102A ................................................................. 19 520CS ............................................................... 38 ISS-100 ............................................................. 52 201-XXX-DPDT ................................................. 22 520CP ............................................................... 39 ISS-101 ............................................................. 52 201-XXX-SP ......................................................
For over 85 years, Littelfuse products have helped protect electrical equipment used in mining, petrochem, marine, alternative energy, HVAC and other industrial applications. We offer Littelfuse Startco protection relays and custom power centers as well as Littelfuse Selco generator protection, controls and alarm panels. Now a part of Littelfuse, SymCom and SSAC manufacture electronic products for monitoring, protecting and controlling motors, pumps, timing controls, and custom designs.