Datasheet

www.symcom.com • 800-843-8848 • fax: 605-348-5685
20
Available Models:
Features:
Low voltage trip
Single-phase trip
Reverse-phase trip
Fixed 6% voltage unbalance trip
Single LED diagnostics
Optional high voltage trip
8-pin plug-in; DIN rail or surface mount
Separate indicators for:
Power-up restart delay
Reverse-phase trip
Good voltage/relay energized
Unbalance/single-phase trip
High/low voltage trip
A
pprovals:
201A
201A-9
Specications
The Model 201A
is a 3-phase, auto-ranging, dual-range voltage
monitor that protects 190-480VAC, 50/60Hz
motors regardless of size. The product provides
a user selectable nominal voltage setpoint and the
voltage monitor automatically selects between the
200V and 400V range. The Model 201A includes
advanced single LED diagnostics, where five
different light patterns distinguish between faults
and normal conditions.
This unique microcontroller-based voltage and
phase-sensing device constantly monitors the
3-phase voltages to detect harmful power line
conditions. When a harmful condition is detected,
the MotorSaver’s output relay is deactivated after
a specified trip delay. The output relay reactivates
after power line conditions return to acceptable
levels.
For more information see:
See Appendix A, page 68, Figure 8 for dimensional
drawing.
See Appendix B, pages 73 & 74, Figures 12 & 13 for
typical wiring diagrams.
Option
9 - High Voltage Detection
Auxiliary Products:
8-pin octal socket (P/N: CT0T08-PC)
Model 201A
3-phase voltage/phase monitor, 8-pin socket mount, optional high voltage trip
3-Phase Voltage Monitor
Terminal Torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 in.-lbs.
Wire Gauge ....................................12-22 AWG Solid or stranded
Transient Protection (Internal) ...................2500V for 10 ms
Standards Passed
Electrostatic Discharge (ESD) .....................IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity (RFI), Radiated ........150MHz, 10V/m
Fast Transient Burst .............................IEC 61000-4-4, Level 3, 3.5kV input power
& controls
Surge Immunity
IEC ............................................IEC 61000-4-5, Level 3, 4kV line-to-line;
Level 4, 4kV line-to-ground
ANSI/IEEE .....................................C62.41 Surge and Ring Wave Compliance to a
level of 6kV line-to-line
Hi-potential Test ................................Meets UL508 (2 x rated V + 1000V for 1 minute)
Safety Marks
UL (OT08-PC octal socket required) ...............UL508 (File #E68520)
CE ............................................IEC 60947-6-2
Dimensions ....................................1.750” H x 2.375” W x 4.125” D (with socket)
(44.45 x 60.325 x 104.775mm)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.7 lbs. (11.2 oz., 317.51 g)
Mounting Method ..............................DIN rail or surface mount (plug in to
OT08-PC socket)
Socket Available ...............................Model OT08-PC (UL Rating 600V)
The 600V socket can be surface mounted or installed on DIN Rail.
Input Characteristics
Line Voltage ...................................190-480VAC
Frequency .....................................50/60Hz
Functional Characteristics
Low Voltage (% of setpoint)
Trip ..........................................90%
Reset .........................................93%
Voltage Unbalance (NEMA)
Trip ..........................................6%
Reset .........................................4.5%
Optional High Voltage (% of setpoint)
Trip ..........................................110%
Reset .........................................107%
Trip Delay Time
High/Low Voltage Fault ........................4 seconds
Unbalance & Phasing Faults .....................2 seconds
Restart Delay Time
After a Fault ...................................2 seconds
After a Complete Power Loss ....................2 seconds
Output Characteristics
Output Contact Rating (SPDT)
Pilot Duty .....................................480VA @ 240VAC
General Purpose ................................10A @ 240VAC
General Characteristics
Temperature Range ..............................
-20
°
to 70
°
C (-4
°
to 158
°
F)
Trip & Reset Accuracy ..........................±1%
Maximum Input Power .........................5 W
Relative Humidity ..............................10-95%, non-condensing per IEC 68-2-3
Must use Model OT08-PC or RB08-PC
socket for UL Rating!
Note: Manufacturer’s recommended screw
terminal torque for the RB Series and
OT Series Octal Sockets is 12 in.-lbs.
CATALOG_SYMCOM_2014.indd 20 6/10/14 11:06 AM