Specification

VICTORY range hoods
| Q1
4
B02 |
5
IMPORTANT: Observe all governing codes and ordinances.
It is the customer’s responsibility:
To contact a qualified electrician
To assure that the electrical installation is adequate and in conformance with National Electrical
Code and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualied electrician
determine that the ground path is adequate.
A 120-Volt, 60 Hz, AC-only, fused electrical supply is required on a separate 15-amp circuit.
DO NOT ground to a gas pipe.
Check with a qualied electrician if you are not sure that the range hood is properly grounded.
DO NOT have a fuse in the neutral or ground circuit.
IMPORTANT: Save this Installation Guide for electrical inspectors use.
The range hood must be connected with copper wire/plug only.
The range hood should be connected directly to the fused disconnect (or circuit breaker) box through
exible armored or non-metallic sheathed copper cable. A U.L. - or C.S.A. - listed strain relief must be
provided at each end of the power supply cable.
Wire sizes (copper wire
only) and connections must conform with the rating of the appliance as specified
on the model/serial rating label. Wire sizes must conform to the requirements of the National Electrical
Code ANSI/NFPA 70 latest edition*, or CSA Standards C22.
ELECTRICAL REQUIREMENTS