Quick configuration guide Access SW 4.0 1 04 to 4.1 1.00 157618 A004

Table Of Contents
Quick configuration guides |
9
5.4.2 Configuration
Configure the number of connected room temperature sensors in the Configuration > Functions > Tempera-
ture control menu.
Overview:
Configuration > Functions > Temperature control
11 Dec 10:33
Room temperature sensor
1
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Temperature control
4. Select number of connected Room temperature sensors
5.4.3 Allocation
Select I/O (in-/output) placement for where the room temperature sensors are connected to the controller in the Con-
figuration > I/O allocation settings > Analog inputs menu.
Overview:
Configuration > I/O allocation settings > Analog
inputs
11 Dec 10:33
Analog inputs
Device Position
Room temperature 1
Controller Select I/O
Room temperature 2
Controller Select I/O
Room temperature 3
Controller Select I/O
Room temperature 4
Controller Select I/O
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select the input connected to the sensor (e.g. UI1) as position for Room temperature 1/2/3/4
5. Repeat step 4 for any remaining room temperature sensors.
157618 | A004