Quick configuration guide Access SW 4.0 1 04 to 4.1 1.00 157618 A004

Table Of Contents
6
| Quick configuration guides
5. Select the sequence to rename (e.g Cooling 2)
6. Edit the name of the sequence by selecting Name.
5.1.4 Alarm naming
How to edit alarm names is described in chapter 5.2.
5.2 Alarm configuration
Configure any alarm available in the controller in the Configuration > Alarms menu.
Overview:
Configuration > ... > Extra alarm 1
11 Dec 10:33
Action: No action
Level: Disabled
Delay:
0 s
No:
68
Name:
Extra alarm 1
Step by step:
1.
Select Configuration from the navigation icons
2. Select Alarms
3. Select the desired alarm after scrolling through the list of all alarms and identifying the alarm via either name or alarm
number
4. Select the action the unit will take when the alarm is active (e.g Normal stop) as Action
5. Select the desired Alarm class or disable the alarm (e.g Class B) as Level
6. Adjust the time before the alarm activates as Delay
7. Adjust the name of the alarm as Name.
5.3 Fan control type (Pressure)
5.3.1 Activation
Activate pressure control.
Select Fan control type as Pressure in the Configuration > Functions > Function activation menu.
Overview:
Configuration > Functions > Function activation
11 Dec 10:33
Fan control type
Pressure
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Pressure as Fan control type.
157618 | A004