Data Sheet

● parameterizable
Yes; by software
— for resistance thermometer
Pt 100
Cable length
● shielded, max.
100m
Analog outputs
Number of analog outputs 2
integrated channels (AO) 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 55mA
Current output, no-load voltage, max. 14V
Output ranges, voltage
● 0 to 10 V
Yes
● -10 V to +10 V
Yes
Output ranges, current
● 0 to 20 mA
Yes
● -20 mA to +20 mA
Yes
● 4 mA to 20 mA
Yes
Connection of actuators
● for voltage output two-wire connection
Yes; Without compensation of the line resistances
● for voltage output four-wire connection
No
● for current output two-wire connection
Yes
Load impedance (in rated range of output)
● with voltage outputs, min.
1kΩ
● with voltage outputs, capacitive load, max.
0.1µF
● with current outputs, max.
300Ω
● with current outputs, inductive load, max.
0.1mH
Destruction limits against externally applied voltages and currents
● Voltages at the outputs towards MANA
16V; Permanent
● Current, max.
50mA; Permanent
Cable length
● shielded, max.
200m
Analog value generation for the inputs
Measurement principle Actual value encryption (successive approximation)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
12bit
● Integration time, parameterizable
Yes; 16.6 / 20 ms
● Interference voltage suppression for
interference frequency f1 in Hz
50 / 60 Hz
● permissible input frequency, max.
400Hz
● Time constant of the input filter
0.38ms
6ES7314-6EH04-0AB0 Subject to change without notice