Data Sheet

● supported
Yes
● to MPI, master
Yes
● to MPI, slave
Yes
● to DP, master
Yes; With DP slave only slave clock
● to DP, slave
Yes
● in AS, master
Yes
● in AS, slave
Yes
● on Ethernet via NTP
Yes; As client
Digital inputs
Number of digital inputs 24
● of which inputs usable for technological
functions
16
integrated channels (DI) 24
Input characteristic curve in accordance with IEC
61131, type 1
Yes
Number of simultaneously controllable inputs
horizontal installation
— up to 40 °C, max.
24
— up to 60 °C, max.
12
vertical installation
— up to 40 °C, max.
12
Input voltage
● Rated value (DC)
24V
● for signal "0"
-3 to +5V
● for signal "1"
+15 to +30V
Input current
● for signal "1", typ.
8mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable
Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of
the standard inputs during program runtime. Please note that
under certain circumstances your newly set filter time may not be
effective until the next filter cycle.)
— Rated value
3ms
for technological functions
— at "0" to "1", max.
8µs; Minimum pulse width/minimum pause between pulses at
maximum counting frequency
Cable length
● shielded, max.
1000m; 50 m for technological functions
● unshielded, max.
600m; for technological functions: No
for technological functions
— shielded, max.
50m; at maximum count frequency
6ES7314-6EH04-0AB0 Subject to change without notice