Data Sheet

● Voltage, relative to output range, (+/-)
1%
● Current, relative to output range, (+/-)
1%
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-)
0.8%; Linearity error ±0.06 %
● Current, relative to input range, (+/-)
0.8%; Linearity error ±0.06 %
● Resistance, relative to input range, (+/-)
0.8%; Linearity error ±0.2 %
● Resistance thermometer, relative to input
range, (+/-)
0.8%
● Voltage, relative to output range, (+/-)
0.8%
● Current, relative to output range, (+/-)
0.8%
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of
interference < rated value of input range), min.
30dB
● Common mode interference, min.
40dB
Interfaces
Number of industrial Ethernet interfaces 1; 2 ports (switch) RJ45
Number of PROFINET interfaces 1; 2 ports (switch) RJ45
Number of RS 485 interfaces 1; Combined MPI / PROFIBUS DP
Number of RS 422 interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200mA
Protocols
● MPI
Yes
● PROFIBUS DP master
Yes
● PROFIBUS DP slave
Yes
● Point-to-point connection
No
MPI
● Transmission rate, max.
12Mbit/s
Services
— PG/OP communication
Yes
— Routing
Yes
— Global data communication
Yes
— S7 basic communication
Yes
— S7 communication
Yes
— S7 communication, as client
No; but via CP and loadable FB
— S7 communication, as server
Yes
PROFIBUS DP master
● Transmission rate, max.
12Mbit/s
6ES7314-6EH04-0AB0 Subject to change without notice
Page 11/
20
09/13/2019 © Copyright Siemens