Cyclic HART Input Data
The HART input data holds the primary variables for the "live" HART
device, and other information gathered during the normal HART scan.
Additional "documentary" data is available through the pass through message
interface in the device information tables. Pass through messages are defined
in detail in the User Manual.
IMPORTANT
The HART Input Data for a channel may be zeroes if HART communications is
disabled for that channel. For more information on disabling HART
communications, refer to the Disable HART communications and HART
Disable functions in the Configuration Map table.
HART Input Data
Word Bit
1514131211109876543210
0 Reserved Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0
(HART Communications Status)
1 Reserved
2 Ch0 HART Field Device Status Ch0 HART Comm Status
3 Reserved Ch0 HART Loop Status
4 Ch0 HART Primary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
5
6 Ch0 HART Secondary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
7
8 Ch0 HART Tertiary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
9
10 Ch0 HART Fourth (Quaternary) Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
11
12 Ch0 Secondary Value Units Code Ch0 Primary Value Units Code
13 Ch0 Fourth Value Units Code Ch0 Tertiary Value Units Code
14 Ch1 HART Field Device Status Ch1 HART Communication Status
15 Reserved Ch1 HART Loop Status
16 Ch1 HART Primary Value
17