Installation Instructions FLEX I/O 8 Input HART Analog Module Catalog Number 1794-IE8H, Series B Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 4 North American Hazardous Location Approval 5 European Hazardous Location Approval 6 About the Module 7 Install the Module 7 Wire the Module 9 Ground the Module 11 Input Map 12 Configuration Map 13 Cyclic HART Input Data 17 Input Map (Series A Mode) 23 Configuration Map (Series A Mod
FLEX I/O 8 Input HART Analog Module Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices.
FLEX I/O 8 Input HART Analog Module 3 Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
FLEX I/O 8 Input HART Analog Module ATTENTION This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
FLEX I/O 8 Input HART Analog Module 5 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
FLEX I/O 8 Input HART Analog Module European Hazardous Location Approval European Zone 2 Certification (The following applies when the product bears the Ex or EEx Marking.
FLEX I/O 8 Input HART Analog Module 7 About the Module The HART analog modules can be used with ControlNet, Ethernet and Profibus-DP (1794-APBDV1 only) adapters. When using the Series B module with a Series B profile, you must have a ControlNet adapter Revision 5.1 or higher or an Ethernet adapater Revision 4.2 or higher. For this scenario (Series A profile with a Series B Module), the data maps (input, configuration and extended configuration) are designated as Series A Mode.
FLEX I/O 8 Input HART Analog Module ATTENTION IMPORTANT Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion. You must disable keying in your profile when replacing a series A module with a series B module. To install the module on a 1794 terminal base, refer to the figure and complete the following. 1.
FLEX I/O 8 Input HART Analog Module 9 Wire the Module If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. WARNING To connect two-wire transmitter devices for 1794-TB3G and 1794-TB3GS bases, refer to the tables and figure and complete the following.
FLEX I/O 8 Input HART Analog Module 3. Refer to the Figure for other configurations. 4. Connect +V DC power to terminal 34 on the 34 to 51 row (C). 5. Connect -V to terminal 35 on the 34 to 51 row (C). 6. If continuing power to the next terminal base unit, connect a jumper from terminal 50 (+V) on this base unit to terminal 34 on the next base unit. If continuing common to the next terminal base unit, connect a jumper from terminal 51 (-V) on this base unit to terminal 35 on the next base unit.
FLEX I/O 8 Input HART Analog Module 11 Ground the Module All I/O wiring must use shielded wire. Shields must be terminated external to the module, such as bus bars and shield-terminating feed-throughs. 44862 Inputs Each input can be operated from an analog field device signal. The channels in these modules are electrically connected to each other and have a common plus-line. When interconnecting several lines, you must consider the total accumulated power.
FLEX I/O 8 Input HART Analog Module Input Map Word Bit 15 0 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Input Data Channel 0 1 Input Data Channel 1 2 Input Data Channel 2 3 Input Data Channel 3 4 Input Data Channel 4 5 Input Data Channel 5 6 Input Data Channel 6 7 Input Data Channel 7 8 HA HA HA HA HA HA HA HA LA LA LA LA LA LA LA LA Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2 Ch 1 Ch 0 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2 Ch 1 Ch 0 9 SA SA SA SA SA SA SA SA Rem. Rem. Rem. Rem. Rem. Rem. Rem. Rem.
FLEX I/O 8 Input HART Analog Module 13 Configuration Map Word Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 NF VR FE FE FE FE Byte Ch7 Ch6 Ch5 Ch4 Order HS HSI FE FE FE FE Byte LEDs Ch3 Ch2 Ch1 Ch0 Order 1 HD HD HD HD HD HD HD HD HHE HHE HHE HHE HHE HHE HHE HHE Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0 Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0 2 Data Format Ch3 Data Format Ch2 Data Format Ch1 Data Format Ch0 3 Data Format Ch7 Data Format Ch6 Data Format Ch5 Data Format Ch4 4 HART Read Back Threshold C
FLEX I/O 8 Input HART Analog Module Configuration Map Word Bit 15 14 13 12 11 10 9 22 Low Alarm Limit Ch3 23 High High Alarm Limit (Remote) Ch3 24 Low Low Alarm Limit (Remote) Ch3 25 High Alarm Limit Ch4 26 Low Alarm Limit Ch4 27 High High Alarm Limit (Remote) Ch4 28 Low Low Alarm Limit (Remote) Ch4 29 High Alarm Limit Ch5 30 Low Alarm Limit Ch5 31 High High Alarm Limit (Remote) Ch5 32 Low Low Alarm Limit (Remote) Ch5 33 High Alarm Limit Ch6 34 Low Alarm Limit Ch6 35 High Hi
FLEX I/O 8 Input HART Analog Module 15 Byte Order Configuration Byte Order Byte Order Description(1) Group B Group A Bit 9 Bit 8 Bit 1 Bit 0 0 0 0 0 Little Endian Format (Default) = All data entries in true Little Endian format. 1 0 1 0 Word Swap = Word swap only values requiring more then one word, for example: 32 bit float values. 0 1 0 1 Byte Swap (reserved for future implementation) = Byte swap all words in data table.
FLEX I/O 8 Input HART Analog Module Data Format - Write Words 2 and 3 Data Format Bits 15 11 7 3 14 10 6 2 Format 13 9 5 1 Signal Range User Range 12 8 4 0 LO HI LO HI Resolution 6 0 1 1 0 4…20 mA as 4.00 √% 22.00 0 (0%) 10607 (106.07%) 0.17% of 4...20 mA 7 0 1 1 1 4…20 mA as 4.00 unsigned integer 20.00 0 (4 mA) 65535 (20 mA) 0.03% of 4...20 mA 8 1 0 0 0 Not assigned 9 1 0 0 1 10 1 0 1 0 11 1 0 1 1 0...20 mA as 0.00 A/D count 22.00 0 (0 mA) 55000 (22 mA) 0.04% of 0...
FLEX I/O 8 Input HART Analog Module 17 Cyclic HART Input Data The HART input data holds the primary variables for the "live" HART device, and other information gathered during the normal HART scan. Additional "documentary" data is available through the pass through message interface in the device information tables. Pass through messages are defined in detail in the User Manual. IMPORTANT The HART Input Data for a channel may be zeroes if HART communications is disabled for that channel.
FLEX I/O 8 Input HART Analog Module HART Input Data Word Bit 15 18 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Ch1 HART Secondary Value 19 20 Ch1 HART Teritiary Value 21 22 Ch1 HART Fourth Value 23 24 Ch1 HART Secondary Value Units Code Ch1 HART Primary Value Units Code 25 Ch1 HART Fourth Value Ch1 HART Tertiary Value Units Code 26 Ch2 HART Field Device Status Ch2 HART Communication Status 27 Reserved Ch2 HART Loop Status 28 Ch2 HART Primary Value 29 30 Ch2 HART Secondary Value
FLEX I/O 8 Input HART Analog Module 19 HART Input Data Word Bit 15 48 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Ch3 HART Secondary Value Units Code Ch3 HART Primary Value Units Code 49 Ch3 HART Fourth Value Ch3 HART Tertiary Value Units Code 50 Ch4 HART Field Device Status Ch4 HART Communication Status 51 Reserved Ch4 HART Loop Status 52 Ch4 HART Primary Value 0 53 54 Ch4 HART Secondary Value 55 56 Ch4 HART Tertiary Value 57 58 Ch4 HART Fourth Value 59 60 Ch4 HART Secondary Valu
FLEX I/O 8 Input HART Analog Module HART Input Data Word Bit 15 78 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Ch6 Secondary Value 79 80 Ch6 Tertiary Value 81 82 Ch6 Fourth Value 83 84 Ch6 HART Secondary Value Units Code Ch6 HART Primary Value Units Code 85 Ch6 HART Fourth Value Ch6 HART Tertiary Value Units Code 86 Ch7 HART Field Device Status CH7 HART Communication Status 87 Reserved Ch7 HART Loop Status 88 Ch7 HART Primary Value 89 90 Ch7 Secondary Value 91 92 Ch7 Tertiary
FLEX I/O 8 Input HART Analog Module 21 HART Input Data descriptions CHn: HART Communication Status 0: HART CMD3 Communication Disabled or No Error CHn: HART Comm Status (HART CMD3 Response first status byte): Refer to User Manual CHn: HART Field Device Status (HART CMD3 Response second status byte): Refer to User Manual Chn: HART Loop Status: Bit 0: HART enable Bit 1: Device Connected Bit 2: Response Error Bit 3: CMD 48 Update Bit 4: HART Loop Tolerance Error Bit 5: HART Update Bit 6: HART message B
FLEX I/O 8 Input HART Analog Module HART Read Back Threshold HART Read Back Decimal Value Bits 7 6 5 4 15 14 13 12 3 11 Disabled 0 0 0 0 0 0 Not applicable(1) 1 0 0 0 0 1 Not applicable 2 0 0 0 1 0 Not applicable 3 0 0 0 1 1 Not applicable 4 0 0 1 0 0 5% 5 0 0 1 0 1 6% 6 0 0 1 1 0 7% 7 0 0 1 1 1 8% 8 0 1 0 0 0 9% 9 0 1 0 0 1 10% 10 0 1 0 1 0 … … … … … … … 30% 30 1 1 1 1 0 31% 31 1 1 1 1 1 (1) 1,
FLEX I/O 8 Input HART Analog Module 23 Input Map (Series A Mode) Word Bit 15 0 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Input Data Channel 0 1 Input Data Channel 1 2 Input Data Channel 2 3 Input Data Channel 3 4 Input Data Channel 4 5 Input Data Channel 5 6 Input Data Channel 6 7 Input Data Channel 7 8 OA OA OA OA OA OA OA OA UA UA UA UA UA UA UA UA Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2 Ch 1 Ch 0 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2 Ch 1 Ch 0 9 RF RF RF RF RF RF RF RF LF LF LF LF LF LF LF LF
FLEX I/O 8 Input HART Analog Module Configuration Map (Series A Mode) Word Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 Reserved High and Low Error Level 0...3 u/d Filter Cutoff 0...3 0...3 Data Format 0...3 FM 0...3 1 Sq. Root High and Low Error Thresh. Level 4...7 u/d Filter Cutoff 4...7 4...7 Data Format 4...7 FM 4...7 Where: u/d = remote transmitter error up/down FM = fault mode Sq. Root Thresh.
FLEX I/O 8 Input HART Analog Module 25 Remote Transmitter Error Up/Down (Series A Mode) Word 0 Bit 08 Up/down for Channels 0...3 Word 1 Bit 08 Up/down for Channels 4...7 Where: O = up 1 = down Data Format (Series A Mode) Word Description Bits 0 04 03 02 01 1 04 03 02 01 Channels 0...3 Channels 4...7 0 0 0 0 0…22 mA = 0...22,000 with error steps (default) 0 0 0 1 0…22 mA = 0…110%, with error steps 0 0 1 0 0…22 mA = 0…104.
FLEX I/O 8 Input HART Analog Module Error Level 0.1 mA Steps (Series A Mode) Word Bits Description Word 0 13 12 11 10 09 Word 1 13 12 11 10 09 Error level channels 0...3 Error level channels 4...7 0 0 0 0 0 Disabled 0.1 mA * binary valve = remote fault alarm Examples Binary value = 7, 0.1 mA * 7 = 0.7 mA Remote fault alarm at -4.38% or +104.38% Data Format 2...22 mA -12.5...112.5% Binary value = 15, 0.1 mA * 15 = 1.5 mA Remote fault alarm at -9.38% or + 109.
FLEX I/O 8 Input HART Analog Module 27 Secondary Master Enable (SME)/ Primary Master Inhibit (PMI) (Series A Mode) 1 (Default) Bits(1) 2 3 4 1 PMI 8, 9, 10, 11, 12, 13, 14, 15 0 0 1 SME 0, 1, 2, 3, 4, 5, 6, 7 0 1 0 1 Pulsed On Off On HART Smooth Filter Rebuild On On Off Off HART Read Back On On Off Off Primary Master On On Off Off Secondary Master Off On Off On (1) Where: Ch 0 - bits 0 and 8; Ch 1 - bits 1 and 9; Ch 2 - bits 2 and 10; Ch 3 - bits 3 and 11 Ch 4 - bits
FLEX I/O 8 Input HART Analog Module Field Descriptions HART Rebuild Bit The HART Rebuild bit will trigger a HART Rebuild on a transition from 0 to 1. The HART Rebuild bit must remain 1 for HART communications to function after the rebuild completes. If the HART Rebuild bit is set to 0, HART communications are disabled. HART Rebuild Flag During the time the system is rebuilding the HART table, the HART rebuild flag is set.
FLEX I/O 8 Input HART Analog Module 29 Field Descriptions Extended Configuration(1) HART Status Indicators Configuration additions are needed for HART communications in Series A mode. An extended configuration area is provided. This Extended Configuration table is configured by writing a CIO or MSG instruction with the following: Class = 0x7D Instance = Product location on flexbus (Use 1 for the module located next to the adapter.
FLEX I/O 8 Input HART Analog Module If a fault occurs in the field transmitter supply of any channel, every channel’s field transmitter power is shutdown. The following graph depicts the typical transmitter load characteristic.
FLEX I/O 8 Input HART Analog Module 31 Repair ATTENTION This module is not field repairable. Any attempt to open the module will void the warranty. If repair is necessary, return the module to the factory.
FLEX I/O 8 Input HART Analog Module Specifications FLEX I/O 8 Input HART Analog Module - 1794-IE8H, Series B Attribute Value Number of inputs 8 single-ended, non-isolated Module base Catalog numbers 1794-TB3G, 1794-TB3GS Resolution 16 bits Absolute accuracy 0.1% Full Scale @ 20 °C (68°F) Accuracy drift with 0.05% Full Scale for 0 °C...55 °C (32...
FLEX I/O 8 Input HART Analog Module 33 FLEX I/O 8 Input HART Analog Module - 1794-IE8H, Series B Attribute Value Flexbus current external input(2) 5V DC 80 mA 24V DC 190 mA Power dissipation, max 3.9 W @ 31.2V DC Enclosure type rating None (open-style) Terminal base screw torque Determined by installed terminal base Wire size Determined by installed terminal base Wiring category(3) 2 - on signal ports 2 - on power ports Wire type Shielded on signal ports Thermal dissipation, max 13.
FLEX I/O 8 Input HART Analog Module Environmental Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...55 °C (-4...131 °F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): –40...85 °C (–40...
FLEX I/O 8 Input HART Analog Module 35 Environmental Attribute Value EFT/B Immunity IEC 61000-4-4: ±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on signal ports Surge Transient Immunity IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±2 kV line-earth(CM) on shielded ports Conducted RF Immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80%AM from 10 kHz...
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.