Datasheet

LM2599
www.ti.com
SNVS123C APRIL 1998REVISED APRIL 2013
The maximum voltage appearing across the regulator is the absolute sum of the input and output voltage, and
this must be limited to a maximum of 40V. In this example, when converting +20V to 5V, the regulator would
see 25V between the input pin and ground pin. The LM2599 has a maximum input voltage rating of 40V.
Figure 44. Inverting Regulator
Figure 45. Maximum Load Current for
Inverting Regulator Circuit
An additional diode is required in this regulator configuration. Diode D1 is used to isolate input voltage ripple or
noise from coupling through the C
IN
capacitor to the output, under light or no load conditions. Also, this diode
isolation changes the topology to closely resemble a buck configuration thus providing good closed loop stability.
A Schottky diode is recommended for low input voltages, (because of its lower voltage drop) but for higher input
voltages, a IN5400 diode could be used.
Because of differences in the operation of the inverting regulator, the standard design procedure is not used to
select the inductor value. In the majority of designs, a 33 μH, 3.5A inductor is the best choice. Capacitor
selection can also be narrowed down to just a few values. Using the values shown in Figure 43 will provide good
results in the majority of inverting designs.
This type of inverting regulator can require relatively large amounts of input current when starting up, even with
light loads. Input currents as high as the LM2599 current limit (approximately 4.5A) are needed for 2 ms or more,
until the output reaches its nominal output voltage. The actual time depends on the output voltage and the size of
the output capacitor. Input power sources that are current limited or sources that can not deliver these currents
without getting loaded down, may not work correctly. Because of the relatively high startup currents required by
the inverting topology, the Soft-start feature shown in Figure 43 is recommended.
Also shown in Figure 43 are several shutdown methods for the inverting configuration. With the inverting
configuration, some level shifting is required, because the ground pin of the regulator is no longer at ground, but
is now at the negative output voltage. The shutdown methods shown accept ground referenced shutdown
signals.
UNDERVOLTAGE LOCKOUT
Some applications require the regulator to remain off until the input voltage reaches a predetermined voltage.
Figure 46 contains a undervoltage lockout circuit for a buck configuration, while Figure 47 and 30 are for the
inverting types (only the circuitry pertaining to the undervoltage lockout is shown). Figure 46 uses a zener diode
to establish the threshold voltage when the switcher begins operating. When the input voltage is less than the
zener voltage, resistors R1 and R2 hold the Shutdown /Soft-start pin low, keeping the regulator in the shutdown
mode. As the input voltage exceeds the zener voltage, the zener conducts, pulling the Shutdown /Soft-start pin
high, allowing the regulator to begin switching. The threshold voltage for the undervoltage lockout feature is
approximately 1.5V greater than the zener voltage.
Copyright © 1998–2013, Texas Instruments Incorporated Submit Documentation Feedback 33
Product Folder Links: LM2599