UserManual S SA2 S SA2L202010
Table Of Contents
- Table of Contents
- Introduction
- Warnings
- Operating Conditions
- Installation
- Installation Methods
- Opening Preparation for S-SA2 Installation
- Standard Distances Between Damper Bodies
-  Installation into a Soft Crossing (up to Size 1000 × 800 mm)
- Connecting S-SA2 to “multi” Ductwork Made of Boards
- S-SA2L Installation
-  Installation on the Vertical Duct with a Ledge
-  Installation Directly on the Horizontal Duct
- Electrical Connections
- Operation Manual
- Smoke Damper Functionality Check
- Smoke Damper Inspection
- Warranty Conditions
- Operating Journal
- Warranty Service
4/40 | User Manual S-SA2 & S-SA2L | 201905
Warnings
Some damper parts may have sharp edges; therefore, to protect yourself, please use gloves during damper
installation and manipulation. In order to prevent electric shock, re or any other damage which could result from
incorrect damper usage and operation, it is important to:
1. ensure that installation is performed by a trained person.
2. follow the written and depicted instructions provided within this User Manual closely.
3. perform damper inspection in accordance with this User Manual.
4. check the damper’s functionality as per the
“Smoke Damper Functionality Check” chapter before you
install the smoke damper. This procedure prevents the installation of a damper that has been damaged during
transportation or handling.
IMPORTANT: Do not install non-functioning dampers!
Operating Conditions
S-SA2 and S-SA2L smoke dampers are intended:
• for installation in places which are protected against weather disruptions.
• for ducts, distributing air without any mechanical or chemical contamination.
• for a maximum air ow velocity 12 m/s.
• for a storage temperature range of -20°C to 50°C.
List of Accessories
• D1-S-SA2: Duct Extension with Mesh for S-SA2
• K1-S-SA2L: Kit for Sheet-Metal Duct Installation