Fire Safety Products S-SA2 & S-SA2L Smoke Control Dampers - AAmulti User Manual
/40 | User Manual S-SA2 & S-SA2L | 201905 Table of Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating Conditions . . . . . . . . . . . . . . . . . . . . . 4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation Methods . . . . . . . . . . . . . . . . . . . .
201905 | User Manual S-SA2 & S-SA2L | 3/40 Introduction These are the original installation, inspection and operating instructions for the S-SA2 and S-SA2L smoke control dampers. EVERY S-SA2 AND S-SA2L SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS DOCUMENT! S-SA2 S-SA2L Rectangular smoke control damper without mesh for wall and ceiling installations. Rectangular smoke control damper with a mesh-fitted extension suited for vertical or horizontal duct installations.
/40 | User Manual S-SA2 & S-SA2L | 201905 Warnings Some damper parts may have sharp edges; therefore, to protect yourself, please use gloves during damper installation and manipulation. In order to prevent electric shock, fire or any other damage which could result from incorrect damper usage and operation, it is important to: 1. ensure that installation is performed by a trained person. 2. follow the written and depicted instructions provided within this User Manual closely. 3.
201905 | User Manual S-SA2 & S-SA2L | 5/40 Installation • The duct connected to the smoke damper must be supported or hung in such a way that the damper does not carry its weight. The damper must not support any part of the surrounding construction or wall which could cause damage and consequent damper failure. • The damper driving mechanism can be placed on either side of the wall, however, it needs to be situated to ensure easy access during inspection.
/40 | User Manual S-SA2 & S-SA2L | 201905 Installation Methods All S-SA2 and S-SA2L smoke dampers are CE certified according to EN 12101-8:2011, tested according to EN 1366–10 :2011+A1:2017, and classified according to EN 13501-4:2016. The smoke damper, together with its installation, form an inseparable part of the fire resistivity rating. Tab. 1: S-SA2 fire resistivity Certificate No.
201905 | User Manual S-SA2 & S-SA2L | 7/40 Legend ve Vertical supporting construction (wall, horizontal duct) ho Horizontal supporting construction (floor/ceiling, vertical duct) Wet Installation Installation into a soft crossing Damper placed on duct surface, bottom side of the duct Damper placed on duct surface, top side of the duct Damper placed on duct surface, left and right side of the duct Damper placed within the duct canal, outside of supporting construction Installation of S-SA2L on the
S-SA2 8/40 | User Manual S-SA2 & S-SA2L | 201905 Opening Preparation for S-SA2 Installation The S-SA2 smoke damper can be installed in a wall or ceiling between zones classified as “multi-multi”, “multi-single” and “single-multi”. Opening Preparation for a Rigid Wall W1 H1 1 s Fig. 1: Rigid wall/ceiling with a rectangular opening NOTE: Dimensions W1 and H1 are defined in every installation Legend 1 Concrete/Masonry/Cellular Concrete Tab.
201905 | User Manual S-SA2 & S-SA2L | 9/40 S-SA2 Opening Preparation for a Flexible Wall x ma 62 5 3 4 H1 2 4 1 1 3 H1 × W1 sCW W1 s s Fig. 2: Flexible (plasterboard) wall with a rectangular opening and vertical cross-section (right) Legend 1 On each side - 2 layers of plasterboard fireproof plate type F, EN 520 (thickness see Tab. 4) 2 Vertical CW-profiles (profiles with sCW based on fire resistivity, see Tab.
Standard Distances Between Damper Bodies According to the EN 1366-2 standard, the minimum distance from the wall or ceiling to the damper body is 75 mm. For multiple crossings through a fire resistive wall, the minimum distance between two damper bodies is 200 mm. This applies for distances between the damper body and a nearby foreign object crossing the fire resistive wall. Damper clearances vary from the type of mechanism and their rotation (please see Fig. 3 and see Tab. 5).
201905 | User Manual S-SA2 & S-SA2L | 11/40 Wet Using Concrete Filling 1. The supporting construction opening must be prepared in a way depicted in the “Opening preparation” section (as per Fig. 1 – Fig. 2). Opening surfaces must be even and cleaned. The flexible wall opening must be reinforced as per the standards for plasterboard walls. The opening dimensions are driven by the nominal dimensions of the damper with added clearance. The opening will be made with dimensions W1 and H1 ( Fig. 4 ). 2.
S-SA2 12/40 | User Manual S-SA2 & S-SA2L | 201905 Wet Legend for Figures of Wet Instalation 1 Smoke damper S-SA2 (actuator side) 2 Accessory LEAS/Connected ductwork tested according to EN 1366-9 3 Screw 5,5 DIN 7981 fixing the Damper through bendable hangers 4 Gypsum plaster; Mortar; Concrete filling - minimal category M2.5, EN 998-2 Damper‘s horizontal blade axis orientation Damper‘s vertical blade axis orientation 3 4 2 W1 =W +1 2 ±4 0( 0) 17 5 H1 = H + 120 (±40) H 1 W Fig.
201905 | User Manual S-SA2 & S-SA2L | 13/40 S-SA2 Wet H 1 × W1 ≥150 1 3 175 1 4 ≥150 175 H 1 × W1 2 3 4 Fig. 5: (EI120S) Cross-section of a wet installation in rigid wall 2 Fig. 7: (EI120S) Cross-section of a wet installation in rigid ceiling/floor (actuator above) ≥150 2 3 4 3 1 ≥150 4 175 175 H 1 × W1 2 1 H1 × W1 Fig. 6: (EI120S) Cross-section of a wet installation in flexible wall Fig.
S-SA2 14/40 | User Manual S-SA2 & S-SA2L | 201905 Installation into a Soft Crossing (up to Size 1000 × 800 mm) Soft EI90 - Using Mineral Wool Filling 1. The supporting construction opening must be prepared in a way described in the “Opening Preparation for S-SA2 Installation” section (as per Fig. 1, Fig. 2). Opening surfaces must be even and cleaned. The flexible wall opening must be reinforced as per the standards for plasterboard walls. 2.
201905 | User Manual S-SA2 & S-SA2L | 15/40 S-SA2 Soft 4 W 1 =W + 0( 12 0) ±4 17 5 2 H1 = H + 120 (±40) H 1 W Fig. 9: Wet installation of the S-SA2 smoke damper 175 ≥150 2 5 1 W1 × H1 5 100 3 100 3 175 4 Fig. 10: (EI90S) Cross-section of a soft cross installation in a flexible wall 2 1 W1 × H1 ≥150 4 Fig.
S-SA2 16/40 | User Manual S-SA2 & S-SA2L | 201905 Connecting S-SA2 to “multi” Ductwork Made of Boards The S-SA2 smoke damper can be connected to “multi” ductwork made of calcium silicate boards tested according to EN 1366-8. If mounted on a duct classified with lower fire resistivity, the fire resistivity of the S-SA2 smoke damper will be decreased to the duct level. This section does not depict duct hanger rules as those are dependent on the weight of the duct itself and must be statically approved.
201905 | User Manual S-SA2 & S-SA2L | 17/40 S-SA2 ≥150 175 175 ≥150 Multi-Single Fig. 14: (EI120S) Cross-section of a (for board dimensions follow Fig. 13) ≥150 Wet installation in a rigid ceiling/floor 175 10 5 6 W1 × H1 Pt 3 1 2 4 Fig. 12: Connection of the S-SA2 smoke damper to multi compartment ductwork on the damper side without a mechanism ≥150 Fig. 15: (EI120S) Cross-section of a 175 ≥150 10 175 10 5 5 3 100 6 3 1 4 Fig.
S-SA2 18/40 | User Manual S-SA2 & S-SA2L | 201905 ≥150 175 175 ≥150 Single-Multi Fig. 19: (EI120S) Cross-section of a (for board dimensions follow Fig. 18) Wet installation in a rigid ceiling/floor ≥150 175 10 3 6 ≥3 0 Fig. 20: (EI120S) Cross-section of a 3 1 6 7 1 Pt 120 100 W1 × H1 120 6 Pt W1 × H1 175 10 3 2 4 4 Fig. 18: (EI120S) Cross-section of a Wet installation in a flexible wall ≥150 175 10 2 1 2 4 Fig.
201905 | User Manual S-SA2 & S-SA2L | 19/40 S-SA2 ≥150 175 175 ≥150 Multi-Multi Fig. 24: (EI120S) Cross-section of a (for board dimensions follow Fig. 23) Wet installation in a rigid ceiling/floor ≥150 175 10 5 0 ≥3 3 ≥3 1 2 0 W1 × H1 ≥30 Pt 120 6 4 Fig. 22: Connection of the S-SA2 smoke damper to multi compartment ductwork on both sides of the damper ≥150 175 5 3 120 Pt 120 W1 × H1 Pt 1 7 2 1 4 4 Fig.
S-SA2L 20/40 | User Manual S-SA2 & S-SA2L | 201905 S-SA2L Installation The S-SA2L smoke damper can be installed on “single” (tested according to EN 1366-9) or “multi” (tested according to EN 1366-9) ductwork. If mounted on a duct classified with lower fire resistivity, the fire resistivity of the S-SA2L smoke damper will be decreased to the duct level. This section does not depict duct hanger rules as those are dependent on the weight of the duct itself and must be statically approved.
201905 | User Manual S-SA2 & S-SA2L | 21/40 S-SA2L Fig. 28: Removing the fixing screw Fig. 30: Fixing the bendable hanger in place 6 7 1 2 5 A Fig. 29: Hanger bending and rotating flush with suspension plane Fig. 31: Fixing the damper to the duct boards 2 6 B Fig. 32: Middle fixing to 40 mm thick board 1 2 5 6 C Fig.
S-SA2L 22/40 | User Manual S-SA2 & S-SA2L | 201905 L1V Installation on the Vertical Duct with a Ledge 1. Prepare the duct connection or opening as per Fig. 36 - Fig. 41, clean and flatten the connecting surface. 2. Apply a fire resistive coat (3) on the connection surfaces as depicted in Fig. 36 - Fig. 41. 3. Connect the damper’s flange (on the blade side) to the duct as per the section. “Fixing the S-SA2L Smoke Damper” 4.
201905 | User Manual S-SA2 & S-SA2L | 23/40 Fig. 34: Installation of S-SA2L on a vertical duct with ledge 240 350 Gd 40 (240) Gd = (≥H/2 + 100) Fig.
L1V 6 8 5 3 50 6 4 10 50 8 1 Fig. 36: Cross-section of connection to 25 mm thick board duct 50 6 8 5 2 3 5 9 W×H 1 6 8 5 7 4 1 W×H Fig. 38: Cross-section of connection to 40 mm thick board duct 4 5 9 2 50 20 50 1 20 3 M6 Fig. 40: Cross-section of connection to a mineral wool insulated sheet metal duct with the K1-S-SA2L accessory 10 2 50 10 Fig. 37: Cross-section of connection to 30 mm thick board duct W×H 4 W×H 30 t 3 Fig.
201905 | User Manual S-SA2 & S-SA2L | 25/40 1. Prepare the duct connection or opening as per L2V Fig. 43, clean and flatten the connecting surface. 2. Apply a fire resistive coat (8) on the connection surfaces as depicted in the detail in Fig. 43. 3. Connect the damper’s flange (on the blade side) to the duct as per the section. “Fixing the S-SA2L Smoke Damper” 4. From boards (4 and 5) create a collar overlapping the connection as depicted in Fig. 43. 5.
L2V Fig. 42: Installation of S-SA2L, directly on the vertical duct 2 W×H 350 1 20 140 7 6 100 S-SA2L 26/40 | User Manual S-SA2 & S-SA2L | 201905 5 ≥ (H/2) + 100 Fig.
201905 | User Manual S-SA2 & S-SA2L | 27/40 1. Prepare the duct connection or opening as per L1H Fig. 46 - Fig. 51, clean and flatten the connecting surface. 2. Apply a fire resistive coat (3) on the connection surfaces as depicted in Fig. 46 - Fig. 51. 3. Connect the damper’s flange (on the blade side) to the duct as per the section. “Fixing the S-SA2L Smoke Damper” 4. From boards (4 and 7) create a collar overlapping the connection as depicted in Fig. 46 - Fig. 51. 5.
S-SA2L 28/40 | User Manual S-SA2 & S-SA2L | 201905 L1H Fig. 44: Installation of S-SA2L on the vertical duct with a ledge 240 350 Gd 40 (240) Gd = (≥H/2 + 100) Fig.
201905 | User Manual S-SA2 & S-SA2L | 29/40 6 8 5 3 50 6 4 10 50 8 1 Fig. 46: Cross-section of connection to 25 mm thick board duct 50 6 8 5 2 3 5 9 W×H 1 6 8 5 7 4 1 W×H 40 Fig. 48: Cross-section of connection to 40 mm thick board duct 4 5 9 2 50 20 50 1 20 3 M6 Fig. 50: Cross-section of connection to a mineral wool insulated sheet metal duct with the K1-S-SA2L accessory 10 2 50 10 Fig.
S-SA2L 30/40 | User Manual S-SA2 & S-SA2L | 201905 L2H Installation Directly on the Horizontal Duct 1. Prepare the duct connection or opening as per Fig. 53, clean and flatten the connecting surface. 2. Apply a fire resistive coat (8) on the connection surfaces as depicted in Fig. 53 3. Connect the damper’s flange (on the blade side) to the duct as per the section. “Fixing the S-SA2L Smoke Damper” 4. From boards (4 and 5) create a collar overlapping the connection as depicted in Fig. 53. 5.
201905 | User Manual S-SA2 & S-SA2L | 31/40 Fig. 52: Installation of S-SA2L on the vertical duct with a ledge 2 W×H 350 1 20 140 7 100 6 5 ≥ (H/2) + 100 Fig.
/40 | User Manual S-SA2 & S-SA2L | 201905 Electrical Connections Legend for Tab. 6 and Tab. 7 IMPORTANT: Danger of electric shock! One actuator per damper For Belimo „Bxxx-ST“ versions add 4 W and 10 VA For Gruner „Gxxx-ST“ versions add 2 W and 2 VA Switch off the power supply before working on any electrical equipment. Two actuators per damper For Belimo „Bxxx-ST“ versions add 8 W and 20 VA Only qualified electricians are allowed to work on the electrical system.
201905 | User Manual S-SA2 & S-SA2L | 33/40 AC 230 V AC/DC 24 V 1 2 ~ ⊥ L1 N + – 3 1 S1 S2 S3 S4 S5 S6 <3° 2 3 S1 S2 S3 S4 S5 S6 <3° <87° <87° Fig. 54: B230 connection scheme; actuator BELIMO Fig. 55: B24 connection scheme; actuator BELIMO NOTES: NOTES: • Caution! Main power supply voltage! • When power supply is connected to wires 1 and 3, actuator drives to position OPEN. • Parallel connection of several actuators possible.
/40 | User Manual S-SA2 & S-SA2L | 201905 AC/DC 24 V AC 230 V N L L 1 2 3 S1 S2 S3 S4 S5 S6 <5° ~ ~ ⊥ – + + 1 2 3 S1 S2 S3 S4 S5 S6 <5° <85° Fig. 58: G230 connection scheme; actuator GRUNER <85° Fig. 59: G24 connection scheme; actuator GRUNER NOTES: • Caution! Main power supply voltage! • Parallel connection of several actuators possible. • Power consumption and switching thresholds must be observed! • Connect power supply to wire 1+2, actuator drives to position OPEN (1).
201905 | User Manual S-SA2 & S-SA2L | 35/40 C Power In Power Out R1 C R1 C A2 A2 1 DI1 C 1 4 3 5 5 3 6 4 2 6 D1 A P 2 A1 Coms C B P DI2 C A1 120 Ω B C D2 S4 S5 S6 Power Close Close RX TX Open D1 DAMPER OUT 1 C S1 S2 S3 S1 S2 S3 Sc Open CONF DAMPER OUT ON 2 S4 S5 S6 So 1 C 2 1 2 3 4 5 6 7 8 ON Test Button 1 2 3 4 5 6 7 8 ADDRESS Test Button Fig.
/40 | User Manual S-SA2 & S-SA2L | 201905 Operation Manual After installation, it is necessary to adjust the damper into its operating position “closed”. In case, that the damper is used for extraction of pollutants, adjust the damper into its operating position “open”. Connect the actuator to the relevant electric power supply ( Fig. 54 - Fig. 61). The electromotor is activated and adjusts the damper into its operating position.
201905 | User Manual S-SA2 & S-SA2L | 37/40 Recommended Course of Action and Inspection Log as per EN 12 101: 1. Identification of damper 2. Date of inspection 3. Check actuator wiring for damage 4. Check the wiring of the end switches for damage 5. Check the damper cleanliness and clean where necessary 6. Check the inspection lid, cover tightness 7. Check the blade and sealings, and correct and record where necessary (where applicable) 8.
/40 | User Manual S-SA2 & S-SA2L | 201905 Operating Journal Activation of the Damper Mark the Applied Installation Method with a Cross: Date Wet Wet Wet Wet Soft Soft Soft Soft On a Duct On a Duct On a Duct On a Duct Description of the Discovered Defects and the Date of the Following Inspection after the Elimination of Deficiencies.
201905 | User Manual S-SA2 & S-SA2L | 39/40 Periodic Damper Inspections – at Least Once Every 3 Months Date Description of the Discovered Defects and the Date of the Following Inspection after the Elimination of Deficiencies Inspection Technician’s Signature
/40 | User Manual S-SA2 & S-SA2L | 201905 1396 1396 Systemair Production a.s. 15 1396-CPR-0112 Systemair Production a.s.