If terminal "B" of the QAF… is connected to a controller, signal >10 V might drop
out (e.g. 11 V) which, with certain types of controllers, can lead to a fault status
message.
Fit a Zener diode to terminal "B" of the QAF.. or to the controller’s input to ensure
that the DC 0…10 V signal will not exceed 10 V.
Note
Remedy