Data Sheet for Product

4 / 10
Siemens Frost detector A6V10432022_en--_e
Smart Infrastructure 2021-04-20
Type summary
When ordering, please give product number, stock number and description.
The mounting accessories not included in the scope of delivery must be ordered as
separate items.
1 x M16 cable gland for cable entry
2 x screw to DIN 7981-St 4.2 x 22 for direct mounting
1 x rubber grommet for capillary entries into air ducts
1) QAF64.6-J requires 2 AQM63.2
Notes
The frost detector operates on AC 24 V. The transformer used must be suited for
safety extra low voltage (SELV), 100% duty, and must have separate windings.
Fuses, switches, wiring and earthing must be in compliance with local safety regu-
lations. The permissible cable lengths must be observed.
If the capillary tube is mechanically damaged or if there is a leak in the diaphragm
system, the frost detector signals a low temperature and assumes the "Frost" posi-
tion. That is the case also if there is a power failure or if one of the major electronic
components fails.
In the case of large cross-sectional areas of the air duct, an air heating coil can be
monitored by several QAF64..:
QAF64.. valve control signal outputs/inputs in series, and
QAF64.. relay contacts in series
If the relay contacts Q11/Q12/Q14 do not operate on safety extra-low voltage
(SELV), the following applies:
Only authorized personnel may open the frost detector to make settings or the
relay circuit must be de-energized
For manual operation, an external button must be installed for the reset function
(see "Connection diagram")
Product number Stock number Description
QAF64.2-J S55700-P155 Frost detector with 2-m capillary
QAF64.6-J S55700-P156 Frost detector with 6-m capillary
Ordering
Accessories
Included in the scope
of delivery
Not included in the
scope of delivery
Product
number
Stock
number
Designation Parts
AQM63.0 BPZ:AQM63.0 Mounting flange 1 x depth-adjustable mounting
flange for the housing
AQM63.2
1)
BPZ:AQM63.2 Capillary
supports
3 x capillary tube clamp
3 x spacer
Engineering
CAUTION