User guide
7-2
FlexPak 3000 DC Drive Software Reference
METER
OUT
1
GAIN
ADJ
(P.400)
Scales the meter
output 1 signal at the
Regulator board
terminal strip.
Parameter Range:
1.100 to 1.900
Default Setting:
1.000
Parameter Type:
Tun abl e
OIM Menu Path(s):
Input/Output - Meter Outputs
METER
OUT
1
SELECT
(P.404) can be set to
FULL
SCALE
for an accurate gain
adjustment. See figure 7.1.
Adjust the zero point (
METER
OUT
1
ZERO
ADJ
(P.402)) before adjusting gain.
METER
OUT
1
SELECT
(P.404)
Selects the drive
output that will source
meter output 1
(terminals 24 and 25
on the Regulator
board).
Parameter Range:
See table 7.1 for options
Default Setting:
CML
FEEDBACK
Parameter Type:
Tun abl e
OIM Menu Path(s):
Input/Output - Meter Outputs
METER
OUT
1
ZERO
ADJ
(P.402)
Removes any offset
from the meter
output 1 signal at the
Regulator board
terminal strip.
Parameter Range:
–200 to 200
Default Setting:
0
Parameter Type:
Tun abl e
OIM Menu Path(s):
Input/Output - Meter Outputs
METER
OUT
1
SELECT
(P.404) can be set to
ZERO
for an accurate zero adjustment.
See figure 7.1.