User guide
Configuring a Network
10-7
10.2 Configuring Parameters for DeviceNet
These parameters are specific to the DeviceNet network. For more information, see
the DeviceNet Network Communication manual (HE-FP3).
DEVNET
POLL
MSG
TYPE
(P.913)
Selects which
predefined set of data
will be part of the
DeviceNet poll
connection
command/response
messages.
Parameter Range:
CONTROL
ONLY
CONTROL
+
CONFIG
Default Setting:
CONTROL
ONLY
Parameter Type:
Configurable
OIM Menu Path(s):
Network Communications
If the AutoMax network is being used, this parameter has no effect.
CONTROL
ONLY
: The smaller amount of data transmitted in the
CONTROL
ONLY
poll
message type allows greater network density and performance.
CONTROL
+
CONFIG
: The larger amount of data transmitted in the
CONTROL
+
CONFIG
poll message type allows some degree of drive configuration but decreases the
network scan rate.
NETWORK
BAUD
RATE
(P.912)
Sets the baud rate for
the DeviceNet
Interface kit. Entering
a value of 0.0 Kbaud
disables DeviceNet
network
communication.
Parameter Range:
0.0 Kbaud
125.0 Kbaud
250.0 Kbaud
500.0 Kbaud
Default Setting:
0.0 Kbaud
Parameter Type:
Configurable
OIM Menu Path(s):
Network Communications
The baud rate for the AutoMax network is not adjustable. If AutoMax network is
being used, this parameter has no effect.