Configuration User Manual
100 Rockwell Automation Publication ENET-UM001L-EN-P - March 2014
Chapter 8 Communicate with PanelView Terminals
Logix5000 Controller Combinations
Your controller type determines which communication module to use.
You must complete these tasks before your controller can communicate with
PanelView terminals over an EtherNet/IP network:
• Set the IP addresses for the controller’s EtherNet/IP communication
module and the HMI terminal.
• Connect all wiring and cabling.
Connections to PanelView
Terminals
To establish communication between a PanelView or PanelView Plus terminal,
specify controller connections.
Table 21 - Choosing a Communication Module
Controllers Communication Modules
ControlLogix 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-
EN2TXT, 1756-EN3TR, or
1756-EN2TSC communication modules
1768 CompactLogix 1768-ENBT communication module
1769-L23E-Q1B, 1769-L23E-QBFC1B, 1769-L32E, or 1769-
L35E CompactLogix
A built-in EtherNet/IP port
PowerFlex 700S with DriveLogix 1788-ENBT EtherNet/IP communication module
Table 22 - PanelView Terminal Connections
Type of Communication
Terminal Type
PanelView PanelView Plus
Implicit (connected)
• Logix controller communicates to the PanelView terminal like
an I/O module.
• You must add the PanelView terminal to the I/O configuration
tree for the controller project.
Supported Not supported
Explicit (unconnected)
• Communication is set up in PanelBuilder or RSView ME
software.
• All communication is initiated by the PanelView or PanelView
Plus terminal.
Supported Supported