User’s Manual Protector® Work Stations Models 3930000, 3930001, 3930020 and 3930021 To receive important product updates, complete your product registration card online at register.labconco.com Labconco Corporation 8811 Prospect Avenue Kansas City, MO 64132-2696 800-821-5525, 816-333-8811 FAX 816-363-0130 E-MAIL labconco@labconco.com HOME PAGE www.labconco.com Please read the User’s Manual before operating the equipment.
Copyright © 2004, 2007, 2010, 2014 Labconco Corporation. All rights reserved. The information contained in this manual and the accompanying products are copyrighted and all rights reserved by Labconco Corporation. Labconco Corporation reserves the right to make periodic design changes without obligation to notify any person or entity of such change. Warranty Labconco provides a warranty on all parts and factory workmanship.
ORIGINAL INSTRUCTIONS TABLE OF CONTENTS CHAPTER 1: INTRODUCTION Typographical Conventions 1 3 CHAPTER 2: PREREQUISITES Support, Vibration & Movement Requirements Location and Air Current Requirements Exhaust and Blower Requirements Electrical Requirements Space Requirements 4 5 5 5 6 6 CHAPTER 3: GETTING STARTED Unpacking Your Enclosure Installing the Enclosure on a Supporting Structure & Work Surface Connecting to the Exhaust System Installation of Carbon Filters for Room Exhaust Connecting the Electr
CHAPTER 6: MAINTAINING YOUR ENCLOSURE Routine Maintenance Schedule Setting the Inflow Face Velocity with the Speed Control Adjustment Guardian 500 Airflow Monitor Kit No. 3944700 or 3944701 Guardian 500 Component Identification Guardian 500 Installation Procedure Guardian 500 Calibration Procedure Guardian 500 Alarm Activation Guardian Digital Kit No.
Chapter 1: Introduction Congratulations on your purchase of a Labconco Protector® Work Station. Your enclosure provides personnel protection through superior containment while conserving energy at OSHA approved velocities as low as 60 feet per minute. It is the result of Labconco’s more than 50 years of experience in manufacturing fume hoods and more than 30 years of experience in manufacturing filtered enclosures.
Chapter 1: Introduction No. 1. Use Protector Work Station Model No’s. 3930000 (115V) 3930020 (230V) 2. 3930001 (115V) Filter 3930001 (115V) 3930021 (230V) Application Carbon Filter* Organic Vapor, Formaldehyde or Ammonia Built-In Integral Motorized Impeller None Remote Blower or House Exhaust FilterMate Carbon Filter* and/or HEPA Filter for particulates FilterMate Portable Exhauster 3930021 (230V) 3.
Chapter 1: Introduction Typographical Conventions Recognizing the following typographical conventions will help you understand and use this manual: ! ! Steps required to perform a task are presented in a numbered format. Comments located in the margins provide suggestions, reminders, and references. Critical information is presented in boldface type in paragraphs that are preceded by the exclamation icon.
Chapter 2: Prerequisites Before you install the enclosure, you need to prepare your site for installation. You must be certain that the area is level and of solid construction. In addition, a dedicated source of electrical power should be located near the installation site to power the enclosure, and other apparatus. Additionally, the enclosure should be strategically placed in the lab to provide efficient workflow.
Chapter 2: Prerequisites Support, Vibration and Movement Requirements At a minimum, the supporting structure usually consists of a base cabinet or base stand and chemical-resistant work surface. See Chapter 3 for setting up installation. Location and Air Current Requirements The Protector Work Stations have been designed to contain hazards by negating typical cross drafts and turbulence within the opening. Normal air movement does not affect installation of the Protector Work Station.
Chapter 2: Prerequisites Labconco offers accessory remote blowers and transition adapters listed in Chapter 7. Labconco also offers accessory FilterMate Portable Exhausters listed in Chapter 7. Contact Labconco for blower sizing assistance. ! If the enclosure is connected directly to a house exhaust system, an adjustable damper (or valve) must be installed to control the airflow properly. This is equally important when a house exhaust system is controlling multiple enclosures.
Chapter 3: Getting Started Now that the site for your Protector Work Station is properly prepared, you are ready to unpack, inspect, install, and validate your system. Read this chapter to learn how to: Unpack and move the enclosure. Set up the enclosure with the proper supporting structure and work surface. Connect to an exhaust system (only applicable for remote blower). Installation of carbon filters (only applicable for integral blower exhausted to the room). Connect the electrical supply.
Chapter 3: Getting Started Unpacking the Enclosure The United States Interstate Commerce Commission rules require that claims be filed with the delivery carrier within fifteen (15) days of delivery. Carefully remove the shrink-wrap or carton on the enclosure and inspect it for damage that may have occurred in transit. If damaged, notify the delivery carrier immediately and retain the entire shipment intact for inspection by the carrier. DO NOT RETURN GOODS WITHOUT THE PRIOR AUTHORIZATION OF LABCONCO.
Chapter 3: Getting Started Work Surface Specifications The work surface should be smooth, rigid, and durable, such as a chemicalresistant epoxy resin. The surface should be non-porous and resistant to the powders, solvents and chemicals used in conjunction with the enclosure. The work surface should also contain a dished recessed area for containing primary spills. Work Surface and Enclosure Installation 1. Level the base cabinet or stand and the work surface.
Chapter 3: Getting Started 3912401 (6") Exhaust Transition shown for Connection to Remote Blower 3930001 Protector Work Station, 115V Remote Blower 3944700 Guardian 500 Airflow Monitor (115V) Control Panel 3908402 Dished Work Surface 3746702 Telescoping Base Stand 3930000 Protector Work Station, 115V w/ Integral Blower Exhausts through Carbon Filters to the Room Typical Exhaust Holes Integral Blower Power Inlet connected via Power Cord from Back of Control Panel Digital Airflow Sensor 3908800 Guardia
Chapter 3: Getting Started Connecting to the Exhaust System (Required on Protector Work Station for Remote Exhaust) ! ATTENTION: The weight of the exhaust ductwork system must be supported independently of the enclosure superstructure or damage may occur. The exhaust system should be installed by a qualified HVAC contractor. The exhaust connection on the remote Protector Work Station Enclosure has been designed to accept a 2" x 10" (5.1cm x 25.4cm) nominal transition adapter.
Chapter 3: Getting Started 3930001 Protector Work Station for Remote Exhaust (115V) 3912400 5" ID Top Exhaust Adapter included with FilterMate 5" ID Hose included with FilterMate Optional 3944700 Guardian 500 Airflow Monitor (115V) Accessory 3908402 Dished Work Surface Optional FilterMate Portable Exhauster Accessory 4' Base Cabinet Figure 3-2 5" Top Exhaust for Remote Protector Work Station Connected to a FilterMate Portable Exhauster 12 Product Service 1-800-522-7658
Chapter 3: Getting Started 3930001 Protector Work Station for Remote Exhaust (115V) Optional Accessory Airflow Monitor 3913100 Exhaust Cover Plate moved to Top 3912403 6" Lower Exhaust Transition Adaptor (Accessory) Figure 3-3 Back View of Protector Work Station with Lower 6" Remote Exhaust Product Service 1-800-522-7658 13
Chapter 3: Getting Started Installation of Carbon Filters for Room Exhaust For carbon filter installation, first unthread the knobs on the perforated baffle located inside the enclosure in the upper corners. Use caution when slowly lowering the perforated baffle. See Figure 6-4 in Chapter 6 for location of the perforated baffle and knobs. See the following list of available carbon filters below and in Chapter 7. All carbon filters are simply installed with the gasket side on the downstream exhaust side.
Chapter 3: Getting Started Connecting the Electrical Supply Source to the Enclosure 115V Models Simply connect the 115V power cord supplied to the IEC electrical supply plug on the back of the enclosure, then connect the integral blower power cord from the motorized impeller outlet on the exhaust to the back of the upper light control panel. If operating at 50 Hz operations, integral blower performance maximum airflow will be reduced by 17%. See Figure 3-4 on the following page.
Chapter 3: Getting Started Back of Airflow Monitor Speed Control Main Inlet Power Switched Power Outlet to Blower Motor (Regulated by Speed Control) Circuit Breaker Auxiliary Switched Power Outlet for Airflow Monitor Blower Motor Power Cord Connection Integral Blower Motorized Impeller Power Inlet Exhausts to the Room Figure 3-4 Protector Work Station with Integral Blower Power Cord and Speed Control 16 Product Service 1-800-522-7658
Chapter 3: Getting Started Main Inlet Power Switched Power Outlet to Remote Blower Motor using Modified Power Cord Not Shown – Auxiliary Switched Outlet for Airflow Monitor For 6" Connection to Remote Blower Circuit Breaker Figure 3-5 Protector Work Station for Remote Exhaust Product Service 1-800-522-7658 17
Chapter 3: Getting Started 230V Models The same procedure applies for the 230V except it is shipped without a plug. Install the appropriate plug for your electrical specifications per local codes. ! Do not use any detachable power cord that is not adequately rated for the unit. Ne pas utliser un fil électrique amovible qui n’est pas du tension nominale de l’appareil.
Chapter 3: Getting Started ! NOTE: Face velocity profiles and smoke testing should be performed frequently per your organization’s quality system to ensure safe performance. Sealing the Enclosure to the Work Surface When the enclosure has been set in place it may be sealed at the work surface to prevent spilled materials from collecting under the walls. A bead of silicone sealant is recommended to seal the enclosure to the work surface.
Chapter 4: High Performance Features and Safety Precautions High Performance Features The patented1 Protector Work Stations are designed to meet the needs of the laboratory scientist, and provide superior containment while conserving energy at OSHA approved “low flow” velocities as low as 60 feet per minute. The enclosures have been tested to effectively contain toxic and noxious materials when properly installed and operated.
Chapter 4: High Performance Features & Safety Precautions 19 3 10 14 6 15 5 4 2 7 7 9 8 1 13 17 7 20 Not Shown 16 Not Shown Figure 4-1 Protector Work Station for use with Remote Blower Product Service 1-800-522-7658 21
Chapter 4: High Performance Features & Safety Precautions 11 3 10 14 12 6 5 13 2 15 18 4 7 1 8 17 w/ Sink 20 Not Shown 16 Not Shown Figure 4-2 Protector Work Station with Integral Blower 22 Product Service 1-800-522-7658
Chapter 4: High Performance Features & Safety Precautions 1. Aerodynamic Clean-Sweep™ Air Foil has a unique shape that allows air to sweep the work surface for maximum containment. The Clean-Sweep™ openings create a constant protective barrier from contaminants. Should the operator inadvertently block the airflow entering the air foil, air continues to pass under the air foil and through the Clean-Sweep openings. See Figures 4-1, 4-2 and 4-3. Figure 4-3 2.
Chapter 4: High Performance Features & Safety Precautions 3. Upper Dilution Air Supply provides bypass air from above the work area. This feature constantly bathes the inside of the sash with clean air and reduces chemical concentrations along the sash plane, near the critical breathing zone. Five to seven percent of the required air volume is introduced through the upper dilution air supply. The upper dilution air supply also reduces stagnant pockets of air in the upper interior. See Figures 4-1 and 4-2.
Chapter 4: High Performance Features & Safety Precautions 12. Speed Control (Integral Blower Models Only) regulates the speed of the motorized impeller and is used by the certifier to validate and adjust the inflow velocity. It is located behind the upper light assembly. See Figures 4-2 and Figure 3-4. 13. Space-Saving Design increases effective laboratory workspace, because the impeller and carbon filter are self-contained on integral blower models.
Chapter 4: High Performance Features & Safety Precautions 4. Blocking large portions of the rear baffle will change the airflow pattern in the enclosure causing turbulence. (Do not store containers or supplies against the rear baffle, as this will affect airflow). 5. Always work with your hands as far back into the enclosure as possible. Keep all chemicals, materials and apparatus inside the lower air foil of the enclosure. 6. Do not work in this enclosure without the exhaust system running. 7.
Chapter 4: High Performance Features & Safety Precautions 20. If the work station is to be used in a confined space, make sure the space is well ventilated and the concentration of toxic contaminants cannot accumulate greater than the TWA. 21. Proper operation of the enclosure depends largely upon the enclosure location and the operator’s work habits.
Chapter 5: Appropriate Applications for Your Enclosure Now that the installation of your enclosure is completed, you are ready to use your Protector Work Station. Read this chapter to learn about: 1. Routine Daily Work Procedures. 2. Suitable Applications. 3. Carbon Filter Applications. 4. Definition of Terms. 5. Appropriate Chemicals for Carbon Filters. 6. Hazardous Misapplications for Carbon Filters. 7. Chemical Carcinogen use with Carbon Filters. 8. Prohibited Acid Use.
Chapter 5: Appropriate Applications for Your Enclosure Loading Materials and Equipment Load only the materials required for the procedure. Do not overload the enclosure. Do not obstruct the air foil, or rear baffle slots. Large objects should not be placed close together and should be elevated above the work surface to permit airflow to sweep under the equipment. After loading, wait one minute to purge airborne contaminants from the work area.
Chapter 5: Appropriate Applications for Your Enclosure Carbon Filter Applications (sold as an accessory for Integral Blower Models) Release of low concentrations of vapors effectively adsorbed or treated in carbon based filters. Treatment of low-level carcinogens or suspected carcinogens. (See Chemical Carcinogens in Chapter 5) Procedures that may have traditionally been done on the open bench (low levels only). Odoriferous chemicals that are an unpleasant nuisance.
Chapter 5: Appropriate Applications for Your Enclosure Saturation Level or Time – There is a limit to the amount of chemical that can be adsorbed by activated carbon or neutralized by chemically-treated carbon. Once the capacity of the carbon is reached, it is considered to be saturated and will adsorb (or neutralize) no further material; the outlet concentration of the chemical will equal the inlet concentration from that point until the filter is replaced.
Chapter 5: Appropriate Applications for Your Enclosure Hazardous Misapplications for Carbon Filters with Volatile Chemicals There is one scenario where the accessory carbon filter misapplication would be a part of a hazardous condition. If the user continues to operate the enclosure with any of the following conditions present a potentially hazardous condition will exist: 1. The inlet concentration of vapors is greater than the TWA. 2. The carbon filter becomes saturated. 3.
Chapter 5: Appropriate Applications for Your Enclosure Prohibited Acid Use The Protector Work Station with Integral Blower motorized impeller cannot be exposed to acids. Where applications require the use of acids a vented fume hood, or vented enclosure should be used with a remote blower and ducted to the outside. Consult Labconco for other small enclosures suitable for acid work.
Chapter 6 Maintaining Your Enclosure Monitoring airflow and changing the carbon filters (if equipped) is the primary maintenance required. Review this chapter on maintenance for the following: 1. Routine Maintenance. 2. Speed control adjustment and setting the inflow face velocity. 3. Operating and calibrating the airflow monitors. 4. Determination of when to replace carbon filters and how to replace. 5. Calculating carbon filter life. 6. Fluorescent light replacement. 7. Motorized impeller replacement. 8.
Chapter 6: Maintaining Your Enclosure Monthly (or more often as required) Determine the actual face velocity through the sash opening of the enclosure where the average reading should be at the specified velocity. (Use calibrated thermal anemometer or other approved apparatus). Airflow alarms are recommended for constant monitoring. The enclosure rear baffle should be checked for any blockage to ensure that the enclosure is maintaining proper airflow. All weekly activities.
Chapter 6: Maintaining Your Enclosure Exhausts to the Room Speed Control Adjusted Slowly with Small Phillips Screwdriver (CCW to Increase or CW to Decrease Figure 6-1 Speed Control Used on Integral Blower Protector Work Station Guardian™ 500 Airflow Monitor Kit No. 3944700 or 3944701 The Guardian 500 Airflow Monitor is designed to continuously monitor airflow through enclosures and fume hoods.
Chapter 6: Maintaining Your Enclosure Guardian 500 Component Identification See Figure 6-2 below. 1. Air Inlet A portion of the air coming into the enclosure passes through the air inlet and across the flow sensors. 2. Normal Flow Indicator This green light indicates normal flow conditions. 3. Alarm Indicator This red light is activated approximately 10-30 seconds after the low flow set point is reached. Low flow set points are 10-20 fpm below normal flow. 4.
Chapter 6: Maintaining Your Enclosure Guardian 500 Installation Procedure 1. The enclosure comes prepared to except the Guardian™ 500 Airflow Monitor. 2. First remove the large 1.19" dia. gray hole plug. See Figure 6-3. See Figure 6-4 only to reference internal assembly of the airflow monitor. Locate the elbow, locknut, and washer and install it in the 1.19" dia. hole per Figure 6-3 and Figure 6-4. The enclosure baffle pivots down to install the elbow, washer and locknut. 3.
Chapter 6: Maintaining Your Enclosure Remove Large 1.19" Dia.
Chapter 6: Maintaining Your Enclosure Display Guardian 500 Monitor Figure 6-4 Guardian 500 Details Guardian 500 Calibration Procedure Each alarm module and enclosure/fume hood is unique and needs to be individually calibrated in the field. The procedure for the adjustment is as follows: 1. Double check the installation to make sure that monitor and power supply are properly installed. 2. Allow 10 minutes for the monitor to warm up once power has been connected. 3.
Chapter 6: Maintaining Your Enclosure 6. If the red light alarm is on, slowly turn the adjustment screw counterclockwise until the green light is activated. If the green light is on, slowly turn the adjustment screw clockwise until the red light comes on. Slowly turn the adjustment screw back until the red light is activated. It is important that these adjustments be done in small increments, at intervals about 30 seconds apart to allow for delayed reaction of the alarm itself.
Chapter 6: Maintaining Your Enclosure Accessory Light Enclosure Hose Cover Monitor Figure 6-5 Guardian 500 Installation 42 Product Service 1-800-522-7658
Chapter 6: Maintaining Your Enclosure Guardian™ Digital Kit No 3908800 or 3908801 Guardian Digital 1000 Operation The Guardian Digital Airflow Monitor consists of the airflow sensor, the Alarm Unit and the 15 VDC power supply. For 115V operation the alarm unit is powered by plugging the power supply into the factory-prepared digital airflow monitor socket. For 230V operation, the Alarm Unit is powered by plugging the power supply into a building outlet.
Chapter 6: Maintaining Your Enclosure Remove Large 1.19" Dia.
Chapter 6: Maintaining Your Enclosure Accessory Light Enclosure Hose Cover Monitor Figure 6-8 Digital 1000 Airflow Monitor Installation Product Service 1-800-522-7658 45
Chapter 6: Maintaining Your Enclosure Digital 1000 Calibration 1. Calibrate the airflow monitor according to the instruction manual that comes with the kit. To successfully calibrate, it will be necessary to change the face velocity by adjusting the airflow exhaust volume. The exhaust volume can be adjusted with the speed control on the FilterMate or by using an adjustable damper on the exhaust blower.
Chapter 6: Maintaining Your Enclosure 9. Be sure to enter “DONE” after successfully completing the low and high calibration set points. 10. Once calibration is completed, go to “RUN” and hit “ENTER”. The value should read close to the high calibration set point. 11. To lower the face velocity to the operating point, simply alter the exhaust volume with the speed control on the FilterMate or exhaust damper.
Chapter 6: Maintaining Your Enclosure 5. To complete the CAL CONFIGURATION, be sure to enter “DONE”. If needed, refer to the Configuration procedure provided on the following page for additional details. 6. To start the calibration mode, enter “CALIBRATION” mode on the display from the SETUP menu. 7. Follow the instructions on the display and simulate the low exhaust volume by fully opening the sash.
Chapter 6: Maintaining Your Enclosure Note: Enter Button stores information and +/- Buttons allow for scrolling. 1. Push the “ENTER” Button on the face of the alarm until the “SET UP” Menu is displayed. 2. Scroll to “SET UP” and hit “ENTER”. 3. The PASSWORD MENU displays (The Password is 0000). Press the ENTER button repeatedly until the CAL CONFIG MENU is displayed. 4.
Chapter 6: Maintaining Your Enclosure Guardian 1000 Digital Alarm (Digital Display, LED’s, Keypads) Airflow Sensor Back of Guardian 1000 Digital Alarm Module Switched Auxiliary Power Outlet for Airflow Monitor Power Supply Route Sensor Cable here from alarm Module to Airflow Sensor Airflow Sensor Spacer (2 Required) Airflow Sensor Figure 6-9 Guardian 1000 Digital Airflow Monitor 50 Product Service 1-800-522-7658
Chapter 6: Maintaining Your Enclosure Determination of When to Replace Carbon Filters and How to Replace Both carbon filters MUST be replaced when any one of the following two conditions are met: 1. The filtered enclosure outlet (exhaust) concentration approaches the inlet concentration, indicating filter saturation. 2. The odor in the work area becomes intolerable or the concentration of the chemical in the work area is greater than the TWA.
Chapter 6: Maintaining Your Enclosure Time - For applications that have very consistent inlet concentrations and operating time, “Time” can be used to anticipate saturation or TWA levels based on prior experience. However, this does not replace the need for sampling. Consult Labconco technical specialist for an estimate of carbon filter life based on chemical usage. Detector tubes, or analytical instrumentation should always be used to determine concentrations in the carbon filter.
Chapter 6: Maintaining Your Enclosure First Carbon Filter Knob for Releasing Carbon Filters First Carbon Filter Gasket Handle to Lower Motorized Impeller located here after both carbon filters Perforated Baffle Second Carbon Filter Perforated Baffle Pivot Figure 6-10 Carbon Filter Replacement Product Service 1-800-522-7658 53
Chapter 6: Maintaining Your Enclosure Calculating Carbon Filter Life Labconco developed a modeling program to estimate the filter life for typical carbon filters. Since filter life is dependent on the chemical used, the airflow, filter size, and the dwell time, refer to the Chemical Guide for the Paramount® Filtered Enclosure.
Chapter 6: Maintaining Your Enclosure Ammonia only For ammonia, use 10% of the impregnated carbon weight. Assume use of a 50% solution of ammonia for these calculations. These values are for one filter. If using two filters, then double the adsorption volume. Number of Filters 1 Filter Size 36 x 18 x 1 Pounds of Ammonasorb II Carbon 15.2 Adsorbed weight of Ammonia 1.52 lbs./ 690 g Adsorbed Volume of 50% Ammonia Solution 1382ml Fluorescent Light Replacement 1. Disconnect the power. 2.
Chapter 6: Maintaining Your Enclosure 5. Remove four nuts in the motor bracket and the four screws and lockwashers to the bracket. ! ATTENTION: High-speed blower. Never operate impeller with housing off. 6. Replace the capacitor with a new one of equal voltage and capacity. 7. Reassemble the new motorized impeller by reversing the assembly steps.
Chapter 6: Maintaining Your Enclosure Speed Control Replacement 1. Follow the procedure to replace the fluorescent light to access the speed control. 2. Remove the light reflector after following the light removal procedure. This allows access to the speed control. 3. Remove the two nuts holding the speed control. Refer to Appendix A for Replacement Parts Diagram. 4. Disconnect all wires leading to the speed control. Connect wires on new speed control in the same position as the old speed control. 5.
Chapter 7: Accessorizing and Modifying Your Enclosure There are several ways to accessorize the enclosure for your individual requirements. These include the addition of accessory work surfaces, airflow monitors, exhaust transition adapters, remote blowers, exhaust dampers, FilterMate Portable Exhausters, carbon filters, storage cabinets, stands and utility shelf kit. 1. Work Surfaces An optional dished work surface is available to attach to the enclosure.
Chapter 7: Accessorizing & Modifying Your Enclosure 6942003 Work Surface with Sink Fabricated from durable epoxy resins, this unique work surface is designed to accept standard dissecting boards and is dished to contain spills. It resists corrosion and will not stain or absorb liquids. Easy to clean, the work surface comes with a 10" x 14" x 6" deep molded epoxy sink. Fixtures include a chrome-plated gooseneck faucet with vacuum breaker, two chrome-plated faucet controls, and a spray nozzle with hose.
Chapter 7: Accessorizing & Modifying Your Enclosure 2. Guardian™ 1000 Digital Airflow Monitor or Guardian™ 500 Airflow Monitor The Guardian 1000 Digital Airflow Monitor or Guardian 500 Airflow Monitor allows you to continuously monitor airflow through the enclosure. The rear exhaust plenum and upper light is factory prepared to mount either monitor.
Chapter 7: Accessorizing & Modifying Your Enclosure Figure 7-1 5. Exhaust Dampers (For Remote Protector Work Station Only) Exhaust dampers allow an adjustment required to maintain proper airflow for roof-mounted blowers or house exhaust systems. Catalog # 3924000 4724200 Description 6" Epoxy Coated Steel In-Line adjustable damper 6" PVC In-line adjustable damper 6.
Chapter 7: Accessorizing & Modifying Your Enclosure HEPA Filter Bag-In/Bag-Out Bag (For FilterMate Only) Part #3776002 helps contain hazardous particulate matter during filter changing operations. Carbon Filter (for FilterMate Only) Provides granular activated carbon or impregnated carbon. Filter Classification Organic Formaldehyde Ammonia Part # 3923400 3923401 3923402 x Pounds 12.0 lbs. activated carbon 14.0 lbs. impregnated carbon 16.0 lbs. impregnated carbon 7.
Chapter 7: Accessorizing & Modifying Your Enclosure 8.
Chapter 7: Accessorizing & Modifying Your Enclosure 10. Hoses, Hose Clamps, and Hose Kits Provides alternatives for ducting. Catalog # 4868600 1921000 3927500 3927600 1921500 64 Description 8 Feet of 5" ID gray flexible polypropylene hose (included with FilterMate). General purpose chemical resistant hose suitable in pharmaceutical applications. 5" T-Bolt Hose Clamp (two included with FilterMate) 8 Feet of 5" ID Clear smooth bore static dissipation hose with two hose clamps.
Chapter 8: Troubleshooting Refer to the following table if your Protector Work Station fails to operate properly. If the suggested corrective actions do not solve your problem, contact Labconco for additional assistance. PROBLEM CAUSE CORRECTIVE ACTION Contaminants outside of enclosure. Improper user techniques for the enclosure. See “Certifying the Enclosure” Chapter 3 and “Safety Precautions” Chapter 4 sections in the manual. (Ref. Appendix D).
Chapter 8: Troubleshooting PROBLEM Blower won’t operate. Low face velocity or poor containment of contaminants. Blower and lights won’t operate. Lights do not work. Airflow monitor malfunction. CAUSE Unit not plugged into outlet. Circuit breaker(s) or Ground Fault Interrupter. Blower wiring is disconnected. Blower switch is defective. Motorized impeller or blower is defective. Enclosure sash not closed. CORRECTIVE ACTION Plug the enclosure into appropriate electrical service. Reset circuit breaker.
Chapter 8: Troubleshooting PROBLEM Airflow Monitor Malfunction (Continued) CAUSE Wrong alarm set point. Constant audible alarm. Continuous alarm. Monitor alarms; air way to airflow monitor sensor is blocked by insects, dust or debris. Audible disable will not stay operational. Product Service 1-800-522-7658 CORRECTIVE ACTION Airflow monitor was not properly adjusted. Repeat calibration steps outlined in this manual in Chapter 6 or in the supplied Guardian 1000 Digital Monitor Manual.
Appendix A: Enclosure Components and Replacement Parts The components that are available for your Protector Work Station are listed. The parts shown are the most commonly requested. If other parts are required, please contact Product Service.
Appendix A: Enclosure Components & Replacement Parts Item 1 2 3 4 5A 5B 6A 6B 7A 7B 7C 7D 8A 8B 8C 9 10A 10B 11A 11B 12A 12B 13 14A 14B 15 16 17A 17B 18A 18B 19 20A 20B 21A 21B 21C 22A 22B 23A 23B Qty. 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2.3 Ft.
Appendix A: Enclosure Components & Replacement Parts Item 24 25 26 27 28A 28B 29 30 31 32A 32B 70 Qty. 1 1 1 2 1 2 1 1 2 1 2 Part Number 1306000 1595619 1595621 1879400 3931500 3931600 3938400 3929200 3932700 3913100 1893008 Description Integral Blower Power Cord, IEC Hole Plug, 0.50 Dia. Hole Plug, 1.187 Dia.
Appendix A: Enclosure Components & Replacement Parts 31, Internal 28 30, Internal 15 Guardian 1000 Digital Monitor 7 3 16 2 6 13, Not Shown 11 27, Not Shown 12 5 4 21 1 9 22 Guardian 1000 Digital Monitor 23 19, Internal 24 20 14, Internal 17, 18, Internal 25 Guardian Digital Sensor 26 30, Internal Figure A-1 Protector Work Station with Integral Blower Product Service 1-800-522-7658 71
Appendix A: Enclosure Components & Replacement Parts 31, Internal 6" Exhaust Collar Shown 15 Guardian 500 Monitor 7 16 29 3 13, Not Shown 6 12 11 8 10 2 1 9 4 16 5 15 15 24 23 Guardian 500 Monitor 19, Internal 6" Exhaust Collar Shown 14, Internal 25 26 20 32 22 Figure A-2 Protector Work Station for use with Remote Blower 72 Product Service 1-800-522-7658
Appendix B: Dimensions and Exhaust Options Product Service 1-800-522-7658 73
Appendix B: Dimensions & Exhaust Options B-1 74 Product Service 1-800-522-7658
Appendix C: Protector Work Station Specifications This Appendix contains technical information about all the Protector Work Station enclosures including electrical specifications and environmental operating conditions. Electrical Specifications 10 Amps, 115V, 50/60 Hz 5 Amps, 230V, 50/60 Hz Environmental Conditions Indoor use only. Maximum altitude: 6562 feet (2000 meters). Ambient temperature range: 41° to 104°F (5° to 40°C).
Appendix D: Quick Chart for the Protector Work Stations Model Size Sash Height from Work Surface (inches) Total Open Area with Bypass (sq. ft.) Exhaust Airflow Volume at 80fpm (CFM) Alarm Airflow Volume at 60 fpm (CFM) *Motor Horsepower (HP) *Capacitor (MFD, Volts) Fluorescent Lights 4' 8.00 2.50 200 150 0.30 15MFD, 115V 4MFD, 230V F25T8 *excludes remote Protector Work Station, since it has no integral blower.
Appendix E: References on Ventilation, Safety, Occupational Hazards, Biosafety & Decontamination Many excellent reference texts and booklets are currently available. The following is a brief listing: Laboratory Ventilation Standards Federal Register 29 CFR Part 1910 Non-mandatory recommendations from “Prudent Practices.” Fume hoods should have a continuous monitoring device Face velocities should be between 60-100 linear feet per minute (lfpm) Average 2.
Appendix E: References ASHRAE 110-1995 Method of Testing Performance of Fume Hoods Evaluates fume hood’s containment characteristics Three part test: Smoke generation, Face velocity profile, Tracer gas release @ 4 liters per minute Rated As Manufactured (AM), As Installed (AI) and As Used (AU) American Society of Heating, Refrigerating, and Air Conditioning Engineers 1791 Tullie Circle N.E. Atlanta, GA 30329 (404) 636-8400 www.ashrae.org ANSI Z9.
Appendix E: References General References American Conference of Governmental Industrial Hygienists. Industrial Ventilation, A Manual of Recommended Practice, Cincinnati, OH ASHRAE Standard Committee. ASHRAE Standard Atlanta: ASHRAE Publications Sales Department, 1995 British Standards Institution, Laboratory Fume Cupboards.
80 Product Service 1-800-522-7658