User's Manual
F220 Series Detectors with F220-B6/C/E/R Bases General Information | en 9
Bosch Security Systems, Inc. Installation Manual 4998138694 -04 | 2007.01
2.3.2 Base Specifications
2.3.3 Detector Specifications
2.4 Electrical Supervision
When the F220-B6 Series Bases are wired according to the
instructions in this document, the control panel initiates a
trouble signal when a detector is removed from its base,
Alarm Current (only base current, detector current excluded)
F220-B6: Two-wire base; no base current
F220-B6C: 31 mA at 12 VDC
35 mA at 24 VDC
40 mA maximum at 30 VDC
F220-B6E: 25 mA at 12 VDC
30 mA at 24 VDC
34 mA maximum at 30 VDC
F220-B6R: 13.5 mA at 12 VDC
16.5 mA at 24 VDC
19 mA maximum at 30 VDC
Standby Current
F220-B6/C/R: No current draw in standby
F220-B6E: 16 mA maximum at 30 VDC
Voltage
F220-B6 (two-wire): 8.5 VDC to 32.0 VDC
F220-B6C/E/R (four-wire): 10.0 VDC to 30.0 VDC
Table 2.4 F220-B6 Series Base Specifications
Current
Alarm: 20 mA minimum at 8.5 VDC
35 mA maximum at 32 VDC
Standby: 0.12 mA maximum
Startup: 0.12 mA maximum
Powerup Time 22 second maximum
Rate of Rise
F220-135: 15°F/min (9°C/min) or greater
Voltage
Operating: 8.5 VDC to 32.0 VDC
RMS Ripple: 25% of DC input
Table 2.5 F220 Series Detector Heads Specifications
4998138694Er7.book Page 9 Thursday, March 1, 2007 8:42 AM