4998138694Er7.book Page 2 Thursday, March 1, 2007 8:42 AM 2 en | Legal F220 Series Detectors with F220-B6/C/E/R Bases 1 Legal 1.1 Trademarks CleanMe® is a registered trademark of GE Interlogix in the United States and/or other countries. Chamber Check® is a registered trademark of Bosch Security Systems, Inc. in the United States. Chambermaid™ is a trademark of Bosch Security Systems, Inc. in the United States. ENVI-RO-TECH™ is a trademark of Tech Spray L.P.
4998138694Er7.book Page 3 Thursday, March 1, 2007 8:42 AM F220 Series Detectors with F220-B6/C/E/R Bases General Information | en 3 use a can of clean, dry compressed air (such as TECHSPRAY ENVI-RO-TECH Duster) which is available at office and alarm supply stores. Shorten the plastic tube that comes with the compressed air to about 2 in. (5 cm). Place the tube or needle valve through the Chambermaid valve in the bottom of the detector (refer to Figure 2.2 on page 7).
998138694Er7.book Page 4 Thursday, March 1, 2007 8:42 AM 4 en | General Information F220 Series Detectors with F220-B6/C/E/R Bases Four-wire: Compatible with all UL Listed four-wire control panels. Refer to the control panel manufacturer’s installation instructions for proper end-of-line (EOL) resistor selection. 2.1.2 Base Comparisons The F220-B6 is a two-wire base, while the F220-B6C, F220-B6E, and F220-B6R are four-wire bases. All three of the four-wire bases have a Form A alarm relay.
4998138694Er7.book Page 5 Thursday, March 1, 2007 8:42 AM F220 Series Detectors with F220-B6/C/E/R Bases 2.1.3 General Information | en 5 Base Features 12 11 10 9 11 13 7 12 8 6 12 3 4 2 5 1 11 11 12 1. Terminal 1 8. Remote Terminal (c) 2. Terminal 2 9. Tamper Tab (Locking Bar) 3. Terminal 3 10. Tamper Tab (Locking Bar 4. Terminal 4 5. Terminal 5 6. Mount) 11. Alignment Key (4 places) Resettable Auxiliary Power 12. Snap Lock (4 places) Positive (+) In and Out 13.
4998138694Er7.book Page 6 Thursday, March 1, 2007 8:42 AM 6 en | General Information 2.2 F220 Series Detectors with F220-B6/C/E/R Bases F220 Series Detectors 2.2.1 About F220 Series Detector Heads The F220 Series Detector Heads listed inTable 2.1 each require an F220-B6 Series Base. ! WARNING! The F220-PTHC detects carbon monoxide (CO) as a component of a fire. Do not use the F220-PTHC as a stand-alone CO detector.
4998138694Er7.book Page 7 Thursday, March 1, 2007 8:42 AM F220 Series Detectors with F220-B6/C/E/R Bases 2.2.2 General Information | en 7 F220 Series Detector Features 1 5 2 6 4 3 1. Front of detector 2. Light-emitting diode (LED) 5. Back of detector Thermistor Chambermaid location 3. 4. 6. Unlocking port (heat detectors only) Fig. 2.2 2.2.3 Detector Features F220 Series Heat Detector Heads The F220 Heat Detector Heads can be identified by color coding (refer to Table 2.2).
4998138694Er7.book Page 8 Thursday, March 1, 2007 8:42 AM 8 en | General Information 2.2.4 F220 Series Detectors with F220-B6/C/E/R Bases F220 Series Smoke Detector Heads The F220 Series Smoke Detector Heads are UL Listed, openarea photoelectric smoke detectors that work with commercial fire protective signaling systems and household fire warning systems. Select the appropriate mounting base to configure the detectors for two-wire or four-wire versions (refer to Section 2.1.
4998138694Er7.book Page 9 Thursday, March 1, 2007 8:42 AM F220 Series Detectors with F220-B6/C/E/R Bases 2.3.2 General Information | en 9 Base Specifications Alarm Current (only base current, detector current excluded) F220-B6: Two-wire base; no base current F220-B6C: 31 mA at 12 VDC 35 mA at 24 VDC 40 mA maximum at 30 VDC 25 mA at 12 VDC F220-B6E: 30 mA at 24 VDC 34 mA maximum at 30 VDC 13.5 mA at 12 VDC F220-B6R: 16.
4998138694Er7.book Page 10 Thursday, March 1, 2007 8:42 AM 10 en | Install the Bases F220 Series Detectors with F220-B6/C/E/R Bases providing tamper protection. An EOL power supervision module, such as a D275 or an F220-B6E Power Supervision Base and an EOL resistor as specified by the control panel manufacturer, supervises power. 3 Install the Bases 3.1 Mount the Bases With the exception of the F220-B6E base, all four-wire bases can be used in any combination within a loop.
4998138694Er7.book Page 11 Thursday, March 1, 2007 8:42 AM F220 Series Detectors with F220-B6/C/E/R Bases 3.2 Install the Bases | en 11 Wire the Bases CAUTION! When wiring bases, all terminal screws ! 3.2.1 including those not wired must be tightened to prevent loose screw heads from making intermitent electrical contact with the detector head. Terminal Connections WARNING! Do not twist or loop the wires around the terminals.
4998138694Er7.book Page 12 Thursday, March 1, 2007 8:42 AM 12 en | Install the Bases 3.2.4 F220 Series Detectors with F220-B6/C/E/R Bases Four-wire Loop Termination One D275 End-of-Line Module (refer to Figure 3.6 on page 17) or F220-B6E Power Supervision Base (refer to Figure 3.4 on page 15) is required for each loop when using four-wire bases. 3.
4998138694Er7.book Page 13 Thursday, March 1, 2007 8:42 AM Install the Bases | en 13 F220 Series Detectors with F220-B6/C/E/R Bases 3.4 Wire F220-B6 Two-wire Bases The F220-B6 is a 12 VDC or 24 VDC base for two-wire conventional loops. Refer to Figure 3.2 for wiring details. 1 - - + + 2 F220-B6 b2 b1 4 3 5 1. 1 Initiating device circuit 2.
4998138694Er7.book Page 14 Thursday, March 1, 2007 8:42 AM 14 en | Install the Bases 3.5.1 F220 Series Detectors with F220-B6/C/E/R Bases F220-B6C: The F220-B6C base has a normally open alarm loop relay and auxiliary Form C (NC/C/NO) contacts. The contacts are rated for 0.5 A at 120 VAC/DC for resistive loads. Refer to Figure 3.3 for wiring details. _ 1 1 + b2 b1 F220-B6C 3 2 1. 2.
4998138694Er7.book Page 15 Thursday, March 1, 2007 8:42 AM Install the Bases | en 15 F220 Series Detectors with F220-B6/C/E/R Bases unnecessary. Use only one F220-B6E per zone run. It must be the last base on the run. Refer to Figure 3.4 for wiring details. _ 1 + 4 b2 b1 F220-B6E* 5 2 1. 2. C 4 NO 3 5 a1/a2 c C 2 NO 1 6 3 + _ Power input (positive [+] previous four-wire base. in on terminal b2; negative 3. Jumper connecting [-] in on terminal a1/a2) terminals 2 and 3.
4998138694Er7.book Page 16 Thursday, March 1, 2007 8:42 AM 16 en | Install the Bases 3.5.3 F220 Series Detectors with F220-B6/C/E/R Bases F220-B6R: The F220-B6R is the standard base for four-wire configurations. The Alarm Loop Relay (Terminals 1 and 2) is a normally-open relay rated for 0.5 A at 120 VAC/DC. The relay closes on alarm. Refer to Figure 3.5 for wiring details. 1 _ _ + + F220-B6R b2 b1 a1/a2 c C 4 3 5 + 2 . 1. 2.
4998138694Er7.book Page 17 Thursday, March 1, 2007 8:42 AM Install the Bases | en 17 F220 Series Detectors with F220-B6/C/E/R Bases 3.6 3.6.1 Wire Power Supervision Modules Wire F220-B6E Power Supervision Base Refer to Section 3.5.2 F220-B6E: for F220-B6E wiring instructions. 3.6.2 Wire D275 Power Supervision Module When a D275 Module (refer to Figure 3.6) is used with 12 VDC systems, connect the red wire to the output terminal (b1) on the last base in the run. The yellow wire remains unconnected.
4998138694Er7.book Page 18 Thursday, March 1, 2007 8:42 AM 18 en | Install the Detector Heads F220 Series Detectors with F220-B6/C/E/R Bases 4 Install the Detector Heads 4.1 Mount the Detector Heads CAUTION! Before mounting detector heads, all terminal ! 4.1.1 screws in the bases including those not wired must be tightened to prevent loose screw heads from making intermitent electrical contact with the detector head.
4998138694Er7.book Page 19 Thursday, March 1, 2007 8:42 AM Install the Detector Heads | en 19 F220 Series Detectors with F220-B6/C/E/R Bases 4.1.2 Mounting Skirt Align the four alignment keys (refer to Figure 2.1, Item 11 on page 5 and to Figure 4.2, Item 5) and press the skirt firmly down onto the mounting base (refer to Figure 4.2, Item 3) to engage the snap locks. 6 1 7 8 5 2 4 5 5 3 5 9 1.
4998138694Er7.book Page 20 Thursday, March 1, 2007 8:42 AM 20 en | Install the Detector Heads 4.1.3 ! F220 Series Detectors with F220-B6/C/E/R Bases Detector Head CAUTION! The mounting skirts and detector heads are keyed. Do not force them onto the mounting bases. Install: Install the detector head by lining up the LED on the detector head (refer to Figure 4.2, Item 6 on page 19) with the bar on the mounting skirt (refer to Figure 4.2, Item 7).
4998138694Er7.book Page 21 Thursday, March 1, 2007 8:42 AM F220 Series Detectors with F220-B6/C/E/R Bases 4.2 Install the Detector Heads | en 21 Set Detector Modes The F220 Series Smoke Detectors feature a unique magnet-operated sensitivity mode and detector test mode. 4.2.1 Test Mode Test the detector by placing the magnet next to the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 19) for three consecutive flashes to cause an alarm. 4.2.
4998138694Er7.book Page 22 Thursday, March 1, 2007 8:42 AM 22 en | Install the Detector Heads 4.3 F220 Series Detectors with F220-B6/C/E/R Bases Set CleanMe Feature The Clean Me feature monitors the smoke chamber’s sensitivity and sends a trouble signal to the control panel when the sensitivity degrades to a preset level. i NOTE! When a CleanMe signal is sent to a control panel that is not CleanMe compatible, the signal may be misinterpreted as an alarm. To activate the CleanMe feature: 1.
4998138694Er7.book Page 23 Thursday, March 1, 2007 8:42 AM F220 Series Detectors with F220-B6/C/E/R Bases Test the Installation | en 23 NOTE! Perform the visual check before resetting power. i After a reset the trouble indicators clear for 70 seconds. After 70 seconds, if the detector is in a trouble condition, trouble indications begin again. A unit with CleanMe activated double flashes (two flashes within a half second of each other) every eight seconds.
4998138694Er7.book Page 24 Thursday, March 1, 2007 8:42 AM 24 en | Test the Installation F220 Series Detectors with F220-B6/C/E/R Bases every eight seconds. This verifies the detector is receiving power and operating properly. NOTE! If a heat detector LED flashes at a rate of i 4 flashes/sec, the detector is either cold (below +32°F [0°C]), out of sensitivity range, or defective. If a smoke detector flashes at a rate of 4 flashes/sec, it is either out of sensitivity range or defective. 5.
4998138694Er7.book Page 25 Thursday, March 1, 2007 8:42 AM F220 Series Detectors with F220-B6/C/E/R Bases 5.3 Test the Installation | en 25 Test the Alarm Loop Checkthe voltage across the EOL resistor of each alarm loop to verify wiring losses do not exceed control panel manufacturer’s specifications. 5.4 Test CO Sensors Removing the detector head or resetting the detector’s power places the detector in a special test mode for 15 minutes.
4998138694Er7.book Page 26 Thursday, March 1, 2007 8:42 AM 26 en | Test the Installation 4998138694 -04 | 2007.01 F220 Series Detectors with F220-B6/C/E/R Bases Installation Manual Bosch Security Systems, Inc.
4998138694Er7.book Page 27 Thursday, March 1, 2007 8:42 AM F220 Series Detectors with F220-B6/C/E/R Bases Bosch Security Systems, Inc. Installation Manual Test the Installation | en 27 4998138694 -04 | 2007.
4998138694Er7.book Page 28 Thursday, March 1, 2007 8:42 AM Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450-9199 USA Customer Service: (800) 289-0096 Technical Support: (888) 886-6189 www.boschsecurity.us © Bosch Security Systems, Inc.