Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Användarhandbok SE Appendix SmartSolar charge controllers MPPT 100/30 MPPT 100/50
1. General Description EN NL 1.1 PV voltage up to 100V The charge controller is able to charge a lower nominal-voltage battery from a higher nominal voltage PV array. The controller will automatically adjust to a 12 or 24V nominal battery voltage. FR 1.
1.8 Flexible charge algorithm Fully programmable charge algorithm, and eight preprogrammed algorithms, selectable with a rotary switch. 1.9 Adaptive three step charging The Controller is configured for a three step charging process: Bulk – Absorption – Float. 1.9.1. Bulk During this stage the controller delivers as much charge current as possible to rapidly recharge the batteries. 1.9.2.
EN 1.11 Configuring and monitoring - Bluetooth Smart (built-in): connect to a smartphone or tablet running iOS or Android. - Use the VE.Direct to USB cable (ASS030530000) to connect to a PC, a smartphone with Android and USB On-The-Go support (requires additional USB OTG cable). - Use a VE.Direct to VE.Direct cable to connect to a MPPT Control, a Color Control panel or a Venus GX. NL FR Several parameters can be customized with the VictronConnect app.
2. Safety instructions SAVE THESE INSTRUCTIONS - This manual contains important instructions that shall be followed during installation and maintenance. Danger of explosion from sparking Danger of electric shock ● Please read this manual carefully before the product is installed and put into use. ● This product is designed and tested in accordance with international standards. The equipment should be used for the designated application only. ● Install the product in a heatproof environment.
3. Installation FR DE ES SE Appendix 5 NL 3.2 Grounding ● Battery grounding: the charger can be installed in a positive or negative grounded system. Note: apply a single ground connection (preferably close to the battery) to prevent malfunctioning of the system. ● Chassis grounding: A separate earth path for the chassis ground is permitted because it is isolated from the positive and negative terminal.
WARNING: WHEN A GROUND FAULT IS INDICATED, BATTERY TERMINALS AND CONNECTED CIRCUITS MAY BE UNGROUNDED AND HAZARDOUS. 3.3 PV configuration (also see the MPPT Excel sheet on our website) ● Provide a means to disconnect all current-carrying conductors of a photovoltaic power source from all other conductors in a building or other structure.
Pos 28,2 27,6 31,8 @8% -32 Gel Victron deep discharge 32,2 Gel Exide A200 28,6 27,6 -32 @8% AGM Victron deep discharge Stationary tubular plate (OPzS) Default setting Gel Victron deep discharge 32,4 2 Gel Exide A200 28,8 27,6 -32 @8% AGM Victron deep discharge Stationary tubular plate (OPzS) AGM spiral cell 33,0 3 Stationary tubular plate 29,4 27,6 -32 @8% (OPzS) Rolls AGM 33,4 -32 4 PzS tubular plate traction 29,8 27,6 batteries or @25% OPzS batteries 33,8 -32 5 PzS tubular plate traction 30,2 27,6 ba
On all models with software version V 1.12 or higher a binary LED code helps determining the position of the rotary switch. After changing the position of the rotary switch, the LEDs will blink during 4 seconds as follows: Switch position 0 1 2 3 4 5 6 7 LED Bulk 1 0 0 0 1 1 1 1 LED Abs 1 0 1 1 0 0 1 1 LED Float 1 1 0 1 0 1 0 1 Blink frequency Fast Slow Slow Slow Slow Slow Slow Slow Thereafter, normal indication resumes, as described below.
EN 3.7 Battery charging information The charge controller starts a new charge cycle every morning, when the sun starts shining.
3.8 Automatic equalization Automatic equalization is default set to ‘OFF’. With the Victron Connect app (see sect 1.10) this setting can be configured with a number between 1 (every day) and 250 (once every 250 days). When automatic equalization is active, the absorption charge will be followed by a voltage limited constant current period. The current is limited to 8% of the bulk current for the factory default battery type, and to 25% of the bulk current for a user defined battery type.
4. Troubleshooting EN Problem Solution Reversed PV connection Connect PV correctly Reverse battery connection Non replacable fuse blown. Return to VE for repair Check battery connection Only for a 24V system: wrong system voltage chosen (12V instead of 24V) by the charge controller Set the controller manually to 24V (see section 1.
5. Specifications SmartSolar Charge Controller MPPT 100/30 Battery voltage Rated charge current Nominal PV power, 12V 1a,b) Nominal PV power, 24V 1a,b) Maximum PV open circuit voltage MPPT 100/50 12/24V Auto Select 30A 50A 440W 880W 100V 700W 1400W 100V Max.
Estados de fallo LED Carga inicial Absorción Flota ción Nota (*2): Por ejemplo, se ha perdido la calibración y/o los datos de ajuste, problema con el sensor de corriente. Charger temperature too high Charger over-current Charger over-voltage Internal error (*2) 3.7 Información sobre la carga de las baterías El controlador de carga inicia un nuevo ciclo de carga cada mañana, cuando empieza a brillar el sol.
EN Figure 1: Power connections NL FR DE ES SE Appendix
Victron Energy Blue Power Distributor: Serial number: Version Date : 09 : January 10th, 2019 Victron Energy B.V. De Paal 35 | 1351 JG Almere PO Box 50016 | 1305 AA Almere | The Netherlands General phone E-mail www.victronenergy.com : +31 (0)36 535 97 00 : sales@victronenergy.