Contents Contents 1 About this document 1.1 1.2 1.3 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. .. .. .. 5 5 5 5 5 6 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. 7 7 7 8 General instructions. . . . . . . . . . . . . . . . . . . . . Mounting instructions . . . . . . . . . . . . . . . . . . . . 9 9 Configuration. . . . . . . Principle of operation . Operation . . . . . . . . .
Contents 9 Supplement Technical data. . . . . . . . . . . . . . . . . . . . . . . . . 18 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 23409-EN-070316 9.1 9.
About this document 1 About this document 1.1 Function This operating instructions manual has all the information you need for quick setup and safe operation. Please read this manual before you start setup. 1.2 Target group This operating instructions manual is directed to trained, qualified personnel. The contents of this manual should be made available to these personnel and put into practice by them. 1.3 Symbolism used Information, tip, note This symbol indicates helpful additional information.
For your safety 2 For your safety 2.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the operator. For safety and warranty reasons, any internal work on the instruments must be carried out only by personnel authorised by the manufacturer. 2.2 Appropriate use VEGATOR 256C is a universal signal conditioning instrument for connection of a level switch.
For your safety 2.6 Safety instructions for Ex areas Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Exapproved instruments. 2.7 Environmental instructions Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection.
Product description 3 Product description 3.1 Configuration Scope of delivery The scope of delivery encompasses: l l Components VEGATOR 256C signal conditioning instrument Documentation - this operating instructions manual VEGATOR 256C consists of: l VEGATOR 256C signal conditioning instrument min. 1 max. 2 0 10 4 6 N 7 8 R 5 L1 power supply 200...250VAC 3VA Relais: max 250V, 5A, 750VA 3 1 2 Fig.
Product description 3.4 Storage and transport Packaging Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180. The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
Mount 4 Mount 4.1 General instructions Installation location VEGATOR 256C signal conditioning instrument with plug-in socket for mounting on carrier rail according to EN 50022. 4.2 Mounting instructions Mount You can mount the VEGATOR 256C signal conditioning instruments either to the wall (2 screws) or plug it onto a carrier rail. Carrier rail mounting Place the signal conditioning instrument onto the carrier rail (35x7.
Connecting to power supply 5 Connecting to power supply 5.1 Preparing the connection Note safety instructions Always keep in mind the following safety instructions: l l Connect only in the complete absence of line voltage If overvoltage surges are expected, overvoltage arresters should be installed Tip: We recommend VEGA overvoltage arresters B61-300 (power supply VEGATOR 256C) and B62-36G (sensor supply).
Connecting to power supply Pump control (min./max. control) min. 3 2 1 5 max. 4 1 2 3 3 0 2 1 10 4 5 6 L1 7 N 8 6 1 Fig. 1 2 3 4 5 6 3 2 4: Pump control Supply Relay output Mass max. min. Probe, e.g. EL3 Note: Mutiple rod probes connected to several signal conditioning instruments or to a multiple channel instrument need a ground rod to keep the signal conditioning instruments from influencing each other.
Connecting to power supply VEGATOR 256C The relay control lamp lights when the relay is energized and extinguishes when the relay is deenergized. VEGATOR 256B The relay control lamp extinguishes when the relay is energized and lights when the relay is deenergized.
Set up 6 Set up 6.1 Adjustment system min. 1 max. 2 0 10 4 6 N 7 8 R 5 L1 power supply 200...250VAC 3VA Relais: max 250V, 5A, 750VA 3 1 2 Fig. 5: Indicating and adjustment elements 1 Signal lamp - Relay output 2 Potentiometer for switching point adjustment 6.2 Adjustment elements Control lamp The yellow relay control lamp (LED) shows the switching condition of the relay. In general, the relay control lamp indicates the activated (energised) condition of the relay.
Set up Pump control (min./max.) l l l l l l at first, connect only the ground and max. electrode to VEGATOR 256C (terminal 2 and 3) Connecting the signal conditioning instrument to voltage supply Turn potentiometer (2) to position 0 Fill the vessel until the max. probe is covered approx. 1 cm by the product Turn potentiometer (2) slowly clockwise until the yellow LED extinguishes Connect min.
Maintenance and fault rectification 7 Maintenance and fault rectification 7.1 Maintenance When used as directed in normal operation, VEGATOR 256C is completely maintenance free. 7.2 Remove interferences Causes of malfunction VEGATOR 256C offers maximum reliability. Nevertheless, faults can occur during operation. These may be caused by the following, e.g.
Maintenance and fault rectification By doing this you help us carry out the repair quickly and without having to call for needed information. l l l l Print and fill out one form per instrument Clean the instrument and pack it damage-proof Attach the completed form and probably a safety data sheet outside on the packaging Please ask the agency serving you for the address of your return shipment. You find the respective agency on our website www.vega.
Dismounting 8 Dismounting 8.1 Dismounting steps Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order. 8.2 Disposal The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable. WEEE directive 2002/96/EG This instrument is not subject to the WEEE directive 2002/96/ EG and the respective national laws (in Germany, e.g. ElektroG).
Supplement 9 Supplement 9.1 Technical data General data Series Module unit for mounting on carrier rail 35x7.5 or 35x15 according to EN 50022 Dimensions W = 37 mm (1.46 in), H = 68 mm (2.68 in), D = 66 mm (2.6 in) Weight approx. 170 g (6 oz) Housing material Noryl SE100, Lexan 920A Voltage supply Supply voltage - Standard - optional Power consumption 200 … 250 V AC, 50/60 Hz 24 V, 42 V, 48 V, 100 … 130 V AC (+10 %, -15 %) 1 VA Sensor input Quantity 1x level detection or 1x pump control (min.
Supplement Ambient conditions Ambient temperature -20 … +50 °C (-4 … +122 °F) Storage and transport temperature -40 … +70 °C (-40 … +158 °F) Electromechanical data Spring-loaded terminals for wire cross-section up to 1.5 mm² (0.
Supplement 66 mm (1 19/32") min. 1 max. 2 3 10 0 4 6 L1 N R 5 7 8 power supply 200...250VAC 3VA Relais: max 250V, 5A, 750VA 68 mm (2 43/64") 9.2 Dimensions 37 mm (1 29/64") Fig.
23409-EN-070316 Supplement VEGATOR 256C - Signal conditioning instrument 21
Supplement 23409-EN-070316 22 VEGATOR 256C - Signal conditioning instrument
409-EN-070316 Supplement VEGATOR 256C - Signal conditioning instrument 23
VEGA Grieshaber KG Am Hohenstein 113 77761 Schiltach Germany Phone +49 7836 50-0 Fax +49 7836 50-201 E-mail: info@de.vega.com www.vega.com ISO 9001 All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information available at the time of printing.