Geniox Core Control system 44.04.02 230V with pre heater

Cable Plan
Path
Sheet
Geniox
Access CU27 Controller
-W514, -W515/516, -W517/W520, -W531.1, -W531.1S
Project:
Date:
Geniox-Core CS 44.04.02 230V Pre-heat GB
06-08-2020
Rev.:
initials:
MIKE
44.04.02
106
Sheet:
107
Next sheet:Total sheets:
16
-W514
Cable-type:
Remark: Pressure Extract air external
DPT
Pressure transmitter
ANG 24V
0-10V
P
-BP4
BK Black
12 4
mm
²
-T15:AI5
BN Brown
12 5
mm
²
-T15:24V
G
Y
Gray
12 4
mm
²
-T15:0V
-W515/516
Cable-type:
Remark: C
O
2 sensor
Duct/Room
C
O
2 sensor
ANG 24V
0-10V
P
-BQ1/BQ2
BK Black
12 6
mm
²
-T16:0V
BN Brown
12 6
mm
²
-T16:AI4
G
Y
Gray
12 6
mm
²
-T16:24V
-W517/W520
Cable-type:
Remark: RH sensor
Extract/Room
RH sensor
G0 (0V) G (24V)
O
ut 1 (0-10V)
P
-BM1/BM4
BK Black
12 7
mm
²
-T16:0V
BN Brown
12 7
mm
²
-T16:AI4
G
Y
Gray
12 7
mm
²
-T16:24V
-W531.1
Cable-type:
Remark: Damper Supply
1
2
3
-QM31.1
BK Black
15 1
mm
² =
A1-X5:2
BN Brown
15 0
mm
² =
A1-X5:1
G
Y
Gray
15 1
mm
² =
A1-X5:3
-W531.1S
Cable-type:
Remark: Damper Supply
Damper Motor
1
2
-QM31.1S
BN Brown
15 1
mm
² =
A1-X5:1
BU Blue
15 1
mm
² =
A1-X5:3