Geniox Core Control system 41.04.02 230V & 400V

Cable Plan
Path
Sheet
Geniox
Access CU27 Controller
-W343, -W442, -W444, -W102, -W102
'
Project:
Date:
Geniox-Core CS 41.04.02 GB
14-08-2020
Rev.:
initials:
MIKE
41.04.02
115
Sheet:
116
Next sheet:Total sheets:
17
=
A3-W343
Cable-type: 2x0,25mm2
Remark: Effencicy Temp.
Eff. Temp
Pt1000
+
DVE-SA-BT4
BK Black 0.25
24 2
mm
² +
DVE-SA-BP1:T2
+
WH White 0.25
24 2
mm
² +
DVE-SA-BP1:T2-
=
A3-W442
Cable-type: 2x0,25mm2
Remark: Exhaust Temp./de-ice
Exhaust Temp.
Pt1000
+
DVAF-EA-BT2
BK Black 0.25
25 2
mm
² +
DVE-EA-BP2:T2
+
WH White 0.25
25 2
mm
² +
DVE-EA-BP2:T2-
=
A3-W444
Cable-type: 2x0,25mm2
Remark: Extract Temp.
Extract Temp.
Pt1000
+
DVAF-EA-BT3
BK Black 0.25
24 1
mm
² +
DVE-SA-BP1:T1
+
WH White 0.25
24 1
mm
² +
DVE-SA-BP1:T1-
=
EC single
+
Extract air-W102
Cable-type:
Remark: motor extract air
L1
L2
L3
PE
=
EC Single/Twin-GQ2
BK Black
21 2
mm
²
-F1:3
BN Braun
21 2
mm
²
-F1:1
G
Y
Gray
21 2
mm
²
-F1:5
PE GN
Y
E
21 3
mm
² =
A1-X1:PE
=
EC single
+
Extract air-W102
'
Cable-type:
Remark: motor extract air
PE
N
L
1
-GQ2
'
BN Braun
20 5
mm
²
-F1:5
BU Blue
20 5
mm
²
-F1:N
PE GN
Y
E
20 6
mm
² =
A1-X1:PE