b) in open-loop PWM control
The fail safe function set value denotes a modulation level:
%100
65536
bytes Data
[%]set valuefunction safe Fail
The value zero means motor standstill
2.37 Fail safe function time lag
Address : D15E
Write authorisation : ebm-papst, customer
Only for source set value = 0x01 (RS485):
If no command is sent to the fan for the time specified here, the fan will automatically switch to the fail safe
function set value (see 2.36 Fail safe function set value), provided that the fail safe function is activated. For
more information about the function, see 2.35.
Encoding:
msms 100bytes Data][lag imefunction t safe Fail
The MSB is of no relevance!
2.38 Fail safe function running direction
Address : D15B
Write authorisation : ebm-papst, customer
If the fail safe function is activated and a break in the MODBUS connection is detected, the direction of
rotation is set to the value defined here. The setting for the Preferred running direction parameter (see 2.11) is
then irrelevant.
Encoding:
Value
Fail safe function running direction
0
anti-clockwise
1
Clockwise
2
none (configured direction of rotation remains unchanged)
The MSB is of no relevance!
Permitted value range: 0 to 2