2.11.1.14/2
By adding additional bus devices at a later time one or
more of the additional individual addresses could be
assigned twice. When during normal operation the
learning button is pressed for more than 10 seconds all
additional individual addresses in the IP Interface
N148/22 are reset to the default value (15.15.255) and
the programming LED is turned off.
IP address assignment
Please consult your network administrator regarding
configuration of the parameters device IP address,
subnet mask, and DHCP.
The IP address of the IP Interface N148/22 is assigned
manually using ETS, automatically by a DHCP server in
the IP network, or by the device itself (AutoIP).
Assignment of the IP address by a DHCP server allows
for changes of the device IP address without using
ETS. Configuration of the DHCP server may require the
MAC address, which is printed on the device. If a
DHCP server is not available the device assigns itself
an IP address (AutoIP).
Default factory settings
The IP Interface ships with these default factory
settings:
· Physical address of the IP Interface:
15.15.15 (= FFFF hex)
· IP address assignment via DHCP
Application programs
The IP Interface N148/22 can be configured with
ETS2 v1.2 or higher.
It requires the application program "12 CO IP
Interface 720002".
Example of Operation
L
N
Bus
AC/DC 24 V
Spannungsversorgung
N 125/21
Linie 1
IP Schnittstelle
N 148/22
Ethernet
TCP / IP
Hub
PC
ETS3
Visualisierung
Example of Operation 1 with external auxiliary power
supply
L
N
Bus
DV 29 V
Spannungsversorgung
N 125/21
Linie 1
IP Schnittstelle
N 148/22
Ethernet
TCP / IP
Hub
PC
ETS3
Visualisierung
Example of Operation 2 with auxiliary power supply
from unchoked bus power supply