Specifications
  ST900 Family General Handbook 
667/HB/32900/000 Issue 12  Page 48 of 265 
3.5  Mains Input 
WARNING
When considering the connection of the controller to the incoming 
mains supply, it is important to verify from the supplier that the mains 
supply short-circuit current does NOT exceed 16,000 Amps. 
If the mains supply short-circuit current can exceed 16,000 Amps, refer to Siemens 
Poole for further information. 
WARNING
The Master Controller Switch is a double-pole isolator and this must 
be switched off before replacing the Master Controller Fuse. 
3.5.1  Supply Transients 
The ST900 ELV Controller has been designed to withstand transients as defined in 
BS EN 50293:2001. 
3.6  Lamp Supply Transformer 
The ELV transformer has primary terminations that enable connection to the Mains 
supplies shown below: 
Nominal Voltage
  Minimum Voltage*  Maximum Voltage* 
250V **  213V  276V 
240V  204V  276V 
230V  196V  264V 
220V  187V  253V 
120V  102V  138V 
110V  94V  126V 
* Refer to the /HE/ handbook for the recommended input tap for a specific mains voltage. 
** Available from issue 4 onwards of the Lamp Supply Transformer 
The nominal secondary voltages are as follows: 
  48V Bright Lamp supply, 27.5V Dim Lamp supply 
  24V Detector supply 
  48V Regulatory Sign supply 
  Logic supplies for LSLS cards (one supply per LSLS card) 
The transformer has an earthed screen to reject common mode disturbances on the 
Mains supply. 