Symbols
Version with display unit is equipped with 8 inputs, 4 outputs and 1 Ethernet interface.
Version without display unit is equipped with 8 inputs, 4 outputs and 1 Ethernet interface.
The digital module is equipped with 4 digital inputs and 4 digital outputs.
The digital module is equipped with 8 digital inputs and 8 digital outputs.
The analog module is equipped with 2 analog inputs or 2 analog outputs, according to
the device type.
The LOGO! TDE module is equipped with 2 Ethernet interfaces.
Versions
The following LOGO! versions are available:
Symbol
Designation
Supply voltage
Inputs
Outputs
Properties
LOGO! 12/24RCE 12/24VDC 8 digital
1)
4 relays
(10 A)
LOGO! 230RCE 115 VAC/VDC to
240 VAC/VDC
8 digital 4 relays
(10 A)
LOGO! 24CE 24 VDC 8 digital
1)
4 solid state
24 V/0.3 A
LOGO! 24RCE
3)
24 VAC/VDC 8 digital 4 relays
(10 A)
LOGO! 12/24RCEo 12/24 VDC 8 digital
1)
4 relays
(10 A)
no display unit
no keyboard
LOGO! 24CEo 24 VDC 8 digital
1)
4 solid state
24 V/0.3 A
no display unit
no keyboard
LOGO! 24RCEo
3)
24 VAC/VDC 8 digital 4 relays
(10 A)
no display unit
no keyboard
LOGO! 230RCEo
2)
115 VAC/VDC to
240 VAC/VDC
8 digital 4 relays
(10 A)
no display unit
no keyboard
1)
Of those can be used alternatively: 4 analog inputs (0 V to 10 V) and 4 fast digital inputs.
2)
230 VAC versions: Two groups consisting of 4 inputs each. Each input within a group must be
connected to the same phase. It is possible to interconnect groups with a different phase.
3)
The digital inputs can be operated with P or N action.