OPzV GEL ABSORPTION CHARGE TIME
Where : T = 0.38 x C /I
T = ABSORPTION CHARGE TIME
C = 20 hr RATED CAPACITY (total battery bank)
I = Charging Current (Amps) (recommended 20% of C/20 discharge
rate) 0.38 = ( 20%/50%) + 5% (5% is added due to losses)
EXAMPLE:
1 string of 2-Volt S2-1380GEL models
20 hr AH rate = 1571 AH
I = 20% of 1571 AH = 314 Amps
T = 0.38 x 1571/314 = 1.9 hrs
OPzV GEL FLOAT STAGE AND TERMINATION
To maintain the battery bank at 100% SOC, the charger continues to apply a Float
charge to the battery bank at the End Amps output current indefinitely or until the
charger is shut off or unplugged.
OPzV GEL REFRESH CHARGE
If Rolls OPzV GEL batteries are properly charged they should not experience
varied capacity loss or require balancing. If they were not properly charged and
there is a decrease in capacity, fully recharge the batteries at the recommended
voltage. It is important to prevent heavy discharge. If the batteries will be stored for
extended periods of time, apply a periodic refresh charge. Frequency will depend
on storage temperature as noted:
DISPOSAL PROCEDURE
Batteries must NEVER be disposed of in household waste. To reduce
environmental impact, bring your spent OPzV GEL batteries to a certified
recycling depot to be recycled.
NOTE:
If charger output is 288 Amps max
(ex 3 x 96 Amp controllers), 288 is used.
T = 0.38 x 1571/288 = 2.1 hrs
Storage Temperature Refresh Charge Interval
Below 20ºC (68ºF) 9 Months
20ºC (68ºF) - 30ºC (86ºF) 6 Months
Higher than 30ºC (86ºF) 3 Months
TABLE 8: OPzV GEL Storage Temperature & Refresh Charge