User guide

Configuring the Speed/Voltage Loop
5-11
5.2.4 Configuring Speed Loop Feedback Lead/Lag Block
Lead/lag adjustments compensate for backlash or coupling issues because of the
feedback device.
To enable this block, set
SPD
LEADLAG
SELECT
(P.216) to
LEAD
/
LAG
or
LAG
/
LEAD
. To
disable this block, set
SPD
LEADLAG
SELECT
(P.216) to
BYPASS
.
When this block is enabled, the selected feedback signal is fed into the lead/lag block.
The
SPD
LEADLAG
LOW
FREQ
(P.214) and
SPD
LEADLAG
RATIO
(P.213) input values are
used to calculate the high break frequency.
SPD
LEADLAG
LOW
FREQ
(P.214) specifies
the low break frequency and the
SPD
LEADLAG
RATIO
(P.213) is the ratio maintained
between the low break and high break frequencies. The low break frequency and ratio
settings are multiplied to determine the high break frequency. For example, if the low
break frequency is 0.50rad/s and the ratio is 10, high break frequency is 5.00rad/s.
The transfer functions for lead/lag and lag/lead are:
Lead/Lag: Lag/Lead:
Where:
ω
low
=
SPD
LEADLAG
LOW
FREQ
(P.214)
ω
high
=
SPD
LEADLAG
LOW
FREQ
(P.214)
*
SPD
LEADLAG
RATIO
(P.213)
1
s
ω
low
----------+
1
s
ω
high
------------+
----------------------
1
s
ω
high
------------+
1
s
ω
low
----------+
----------------------
SPD
LEADLAG
LOW
FREQ
(P.214)
Specifies the low
break frequency of
the speed feedback
lead/lag block.
Parameter Range: 0.01 to 69.81
RAD
/
S
when:
FEEDBACK
SELECT
(P.200) =
ARMATURE
VOLT
SPD
LOOP
SCAN
TIME
(P.019) = 10
MS
0.01 to 139.62
RAD
/
S
when:
FEEDBACK
SELECT
(P.200)
ARMATURE
VOLT
SPD
LOOP
SCAN
TIME
(P.019) = 5
MS
Default Setting:
1.00
RAD
/
S
Parameter Type:
Tun abl e
OIM Menu Path(s):
Speed/Voltage Loop (
SPD
) - Speed/Voltage Loop
(
SPD
) Tuning
If
SPD
LEADLAG
SELECT
is set to:
BYPASS
: This parameter has no effect.
LAG
/
LEAD
: This parameter specifies the lead break frequency.
LEAD
/
LAG
: This parameter specifies the lag break frequency.