User guide
4-26
FlexPak 3000 DC Drive Software Reference
DIG
IN
0
SELECT
(P.428)
Determines which
function is controlled
by digital input 0
(terminal 12 on the
Regulator board).
Parameter Range:
1 =
BRUSH
WEAR
INPUT
2 =
JOG
SPEED
SELECT
3 =
OCL
ENABLE
Default Setting:
1
Parameter Type:
Configurable
OIM Menu Path(s):
Additional Parameters (listed by parameter number)
The functions can be:
•
BRUSH
WEAR
: The input is from a brush wear indicator. If the input is
OFF
, the
MOTOR
BRUSH
WEAR
LOW
alarm is generated. You must have the E.S.P. Brush
Monitor Detector kit installed to use this option.
•
JOG
SPEED
SELECT
: The input determines whether
JOG
SPEED
1 (P.012) or
JOG
SPEED
2 (P.017) will be used when the drive is jogging.
•
OCL
ENABLE
: Enables the outer control loop if
CONTROL
SOURCE
SELECT
is not set
to
NETWORK
and if the I/O Expansion kit is not installed. If an I/O Expansion kit is
installed, the outer control loop enable signal is digital input 5. See section 9.1 for
information.
JOG
ACCEL
/
DECEL
TIME
(P.013)
Sets the minimum
time that the jog
reference can change
from zero to
TOP
SPEED
(P.011) and
from
TOP
SPEED
to
zero.
Parameter Range:
0.1 to 300.0 seconds
Default Setting:
3.0 seconds
Parameter Type:
Tun abl e
OIM Menu Path(s):
Drive Reference - Drive Reference Ramp
Quick Start
The
S
-
CURVE
ROUNDING
parameter does not affect the setting of this parameter.