User guide
2706-UM001A-US-P
D-4 Application Notes
Generate DL5 Variable Data
(Ctrl-V) Command
The conversion routine generates a DL5 Ctrl-V command. In this example,
the 16-bit signed integer is in N17:0. the ^V is in ST13:9 and
\\1\\127^M^M is in ST13:10 The ladder program below converts the
integer to an unsigned ASCII string (using the previous conversion
program) U:6 and then creates the Ctrl-V serial command string in ST13:20
This command can then be sent out to the DL5.
For example: Send 53272 to DL5 with address of 127
ASCII ^V53272\1\127^M
HEX 16h 35h 33h 32h 37h 32h 5Ch 35h 5Ch 31h 32h 37h 0Dh
CTRL-V
Variable
Data
\
Backslash
Variable Carriage
Return
Position
\
Backslash
DL5
Address
JSR
Jump to Subroutine
Prog File Number
0000
ACN
String Concatenate
Source A
ST18:5
Dest ST18:7
0001
Source B
ST18:6
0002
ACN
String Concatenate
Source A
ST13:9
Dest ST13:19
Source B
ST18:7
0003
ACN
String Concatenate
Source A
ST13:19
Dest ST13:20
Source B
ST18:10
RET
Return
0004
0005
END
U:6
To Previous Program