Manual

Compact High-density Analog Current Input Module 17
Publication 1769-IN085A-EN-P - August 2008
The bits are defined as follows:
SGN = Sign bit in 2’s complement format.
Nu = Not Used. Bit set to 0.
Sx = General Status bit for input channels 0…15.
Ox = Over range flag bits for input channels 0…15.
Ux = Under range flag bits for input channels 0…15.
Hx = High Alarm flag bits for input channels 0…15.
Lx = Low Alarm flag bits for input channels 0…15.
Configuration Data File
The manipulation of bits from this file is normally done with programming software
(for example, RSLogix 5000, RSLogix 500, or RSNetWorx for DeviceNet software)
during initial configuration of the system. In that case, graphical screens provided
by the programming software simplify configuration.
Some systems, like the 1769-ADN DeviceNet adapter system, also allow the bits to
be altered as part of the control program using communication rungs. In that case,
it is necessary to understand the bit arrangement.
Configuration Data Array
Word/Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word 0 0 Real Time Sample Value
Word 1 ETS Reserved
Word 2 EC Reserved EA AL
EI
(1)
Reserved Input Filter Sel Ch0
Word 3 Reserved Input Data
Format Ch0
Reserved Input Type/Range
Select Ch0
Word 4 SGN Process Alarm High Data Value Channel 0
Word 5 SGN Process Alarm Low Data Value Channel 0
Word 6 SGN Alarm Dead Band Value Channel 0
Word 7 Reserved
Word 8 EC Reserved EA AL
EI
(1)
Reserved Input Filter Sel Ch1
Word 9 Reserved Input Data
Format Ch1
Reserved Input Type/Range
Select Ch1
Word 10 SGN Process Alarm High Data Value Channel 1
Word 11 SGN Process Alarm Low Data Value Channel 1
Word 12 SGN Alarm Dead Band Value Channel 1
Word 13 Reserved