Supply options for MACX Analog (Ex)/MACX PL
105810_en_01 PHOENIX CONTACT 51
Figure 5-4 Supply by means of redundant power supplies
Example for supply via a MACX MCR-PTB… power terminal block
32 MACX MCR-SL-RTD-I temperature transducers (Order No. 2865065), 40 MACX MCR-
SL-NAM-R NAMUR signal conditioners (Order No. 2865997), and 26 MACX MCR-EX-SL-
RPSSI-I Ex i repeater power supplies (Order No. 2865340) are to be supplied at an operat-
ing voltage of 24 V DC.
First determine the current consumption of the modules from the package slips. For the tem-
perature transducers it is 40 mA per module and for the NAMUR signal conditioners it is
21 mA. The intrinsically safe repeater power supplies require 60 mA each.
Then determine the maximum total current consumption of all 98 modules.
The total current consumption of 3680 mA is less than the maximum permissible current for
supply via the MACX MCR-PTB…. To ensure that the built-in fuse in the MACX MCR-PTB
definitely trips in the event of a short circuit, the 24 V DC supply in this example is provided
by QUINT-PS/ 1AC/24DC/ 3.5 power supplies (Order No. 2866747), which provide a short-
circuit current of 15 A. The structure is shown in Figure 5-5 on page 52. The wiring is as
shown in Figure 5-4 on page 51.
1.2
2.2
3.2
12
3.3
14
1.1
2.1
3.1
11
Fault out
PWR 2
PWR 1
–
–
+
+
Faultsignal
GND
+24V
LFD
+
–
PSU
TBUS
+
–
PSU
Modul
1
Modul
n
I = n * I + n * I + n * I + ...
1 module12module23module3
I= 32 * 40 mA + 40 * 21 mA + 26 * 60 mA = 3680 mA < 3750 mA