Outback Power GS4048A and GS8048A Operator's Manual

Table Of Contents
Troubleshooting
54 900-0161-01-00 Rev A
Table 6 Troubleshooting
Symptom
Possible Cause
Possible Remedy
Generator, external
fan, etc. fails to start
when signal is
provided by AUX
output.
AUX output is not connected.
Test the generator or device to confirm functionality. Test the
appropriate AUX terminals with a DVM. (If the RELAY AUX
terminals are in use, test for continuity. If the 12V AUX terminals
are in use, test for 12 Vdc.) If the proper results are present when
the menu indicates the function is
On
(and the device still does
not work), then there is an external connection problem. If the
proper results are not present with the function
On
, the AUX
circuit may be damaged. Contact OutBack Technical Support.
6
Wrong AUX terminals have
been programmed.
MATE3 system display only: Confirm that the AUX menu that was
programmed matches the terminals that are in use. The
Auxiliary
Output
menu programs the 12V AUX terminals. The
Auxiliary
Relay
menu programs the RELAY AUX terminals.
Wrong AUX terminals are in use. If generator or external device requires 12 Vdc, confirm the 12V
AUX terminals have been connected. The RELAY AUX terminals
do not provide voltage.
Advanced
Generator Start
(
AGS
) fails to
activate when
conditions are met
(or starts when
conditions are not
met).
MATE3 system display only:
AGS
function does not work if
another valid input is present.
Check both inputs for a second AC source (utility grid). If the
inverter detects an acceptable AC source, it will not allow
AGS
.
This is true even if it is internally disconnected from the source
(due to
HBX
mode,
Mini Grid
mode, or similar programming).
MATE3 system display is not
present.
AGS
programming is located in the MATE3 and cannot function if
the MATE3 is removed.
Other AUX functions are in
operation.
Gen Alert
or another AUX function may try to start or stop the
generator using the wrong criteria. Make sure all other AUX
functions are disabled.
AGS
or
Gen Alert
functions start the
generator, but the
inverter does not
accept the power
and shuts off the
generator again.
The inverter’s
GRID
input is in
use and the input priority is set
to
GRID
.
If the input priority is set to
GRID
and the
GRID
terminals are
energized, an automatically controlled generator will shut down.
This could indicate that the generator has been wired to the
GRID
input, or it could indicate that another AC source is active on
the
GRID
input while the generator is using the
GEN
input.
The
GEN
input must be the only terminals in use when
automatically controlling a generator.
Either the
GRID
or
GEN
input can be used when manually
controlling a generator.
Module Select
The GS8048A uses two high-frequency H-Bridge FET modules. The dual design allows half the inverter
to shut down for lower idle consumption. Normally this is automatically selected. If one module fails
or if troubleshooting is otherwise needed, the module selection can be performed manually. The
GS8048A can be directed to use a single, specified module (left or right), or it can be directed to turn
on both modules continuously. This procedure should only be performed if directed by OutBack
Technical Support
6
.
Although the GS4048A has only a single module, this command is still available. The default setting is
Left
, which is the location of the module. Do not change this setting in the GS4048A.
The Module Select menu options are displayed as part of Table 16, which begins on page 65.
6
See inside front cover of this manual.