Outback Power GS4048A and GS8048A Operator’s Manual
Table Of Contents
- Table of Contents
- List of Tables
- List of Figures
- 3TIntroduction
- Commissioning
- Operation
- Inverter Functionality
- Description of AC Input Modes
- Description of Inverter Operations
- System Display-Based Functions
- Metering
- Troubleshooting
- Specifications
- Index
Specifications
900-0161-01-00 Rev A 67
Table 16 Radian Inverter Settings
Field Item Default Minimum Maximum
(Gen Alert) OFF: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Gen Alert OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Vent Fan) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Vent Fan) Off Delay
0.5 minutes
0.1 minutes
25.0 minutes
(DC Divert)
ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(DC Divert ON) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(DC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(DC Divert OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(AC Divert) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(AC Divert ON)
Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) OFF: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(AC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
Inverter Stacking
Stack Mode Master Master, Slave
Power Save
Ranking
Mode = Master:
Master Power Save Level
0
0
31
Mode =
Slave
:
Slave Power Save Level
1 1 31
Grid-Tie Sell
Grid-Tie Enable
Y
Y or N
Sell Voltage
52.0 Vdc
44.0 Vdc
64.0 Vdc
Module Control
Module Control
GS8048A Auto Auto, Left, Right, Both
GS4048A
Left
Auto, Left, Right, Both
Calibrate
Grid AC Input Voltage
X
0 Vac
–7 Vac
7 Vac
Gen AC Input Voltage
X
0 Vac –7 Vac 7 Vac
Output Voltage X 0 Vac –7 Vac 7 Vac
Battery Voltage
X
0.0 Vdc –0.8 Vdc 0.8 Vdc
Grid Interface Protection Menu
Operating Frequency
Operating Frequency
X
60 Hz
50 Hz, 60 Hz
Stage 1 Voltage Trip
Over Voltage Clearance Time X 1.0 seconds 0.12 seconds 5.0 seconds
Over Voltage Trip X 132 Vac 120 Vac 150 Vac
Under Voltage Clearance Time
X
2.0 seconds
0.12 seconds
5.0 seconds
Under Voltage Trip
X
106 Vac
80 Vac
120 Vac
Stage 2 Voltage Trip
Over Voltage Clearance Time
X
0.16 seconds 0.12 seconds 5.0 seconds
Over Voltage Trip X 144 vac 120 Vac 150 Vac
Under Voltage Clearance Time X 0.16 seconds 0.12 seconds 5.0 seconds
Under Voltage Trip
X
60 Vac
60 Vac
120 vac
Frequency Trip
Over Frequency
Clearance Time
X
0.16 seconds 0.12 seconds 5.0 seconds
Over
Frequency
Trip
60-Hz system
X
60.5 Hz 60.1 Hz 65.0 Hz
50-Hz system 50.5 Hz 50.1 Hz 55.0 Hz
Under Frequency
Clearance Time
X
0.16 seconds 0.12 seconds 5.0 seconds
Under
Frequency
Trip
60-Hz system
X
59.3 Hz 55.0 Hz 59.9 Hz
50-Hz system 49.3 Hz 45.0 Hz 49.9 Hz
Mains Loss
Clearance Time X
2.0 seconds 1.0 seconds 5.0 seconds
Reconnect Delay
X
300 seconds 2 seconds 302 seconds
Sell Current Limit
Maximum
Sell Current
GS8048A
X
30 Aac
5 Aac
30 Aac
GS4048A
15 Aac
5 Aac
15 Aac