Datasheet

Operating Procedure
Troubleshooting
When an error has occurred, the display No.1 shows the error code.
Take necessary measure according to the error code, referring the following table.
The control output and the alarm output will turn OFF when an error occurs. (For s.err, the alarm output will be processed for a high temperature
error.)
If the input value exceeds the display limit (1999 to 9999) but it is still within the control range, [[[[ will be displayed for values under 1999.
Under these conditions, the control output and alarm output will operate normally.
*1. This error is displayed only when the process value and set point are displayed.
*2. If the display does not change, the Controller needs to be repaired.
If operation returns to normal, then noise may have caused the problem. Check for noise.
*3. e111 will be displayed on display No. 1 and sum will be displayed on display No. 2.
Display Meaning Action
s.err
(S.ERR)
Input error*1 Check the wiring of inputs, disconnections, short circuits and input type.
e111
(E111)
RAM memory error Turn the power OFF then back ON again.*2
e111/sum
(E111)/(SUM)*3
Non-volatile memory
memory error
Press the U and D Keys for at least 3 seconds to initialize the settings and clear the non-
volatile memory error.*2
t
p
a
o
Input Type
i.n.p.t
AT Execute/
Cancel
Temperature
Unit
t
p
k
o
Temperature
Input Shift
PID • ON/OFF
Alarm Value
Proportional
Band
Control Period
r.-.s
RUN/STOP
Integral Time
Direct/Reverse
Operation
Derivative
Time
Alarm Type
Hysteresis
Operation/
Adjustment
Protect
Initial
Setting
Protect
Operation
Control Key
Protect
PV/SP
Manual Reset
Value
Adjustment
Level
2.5
for less
for at least
3 seconds.
Protect
Level
Operation
Level
+
Adjustment
Level
POWER ON
Initial Setting
Level
M
M
M
M
Press
Press
than 1 second.
for at least 1 second. Press
for at least 3 seconds. Press
for at least
1 second.
+
Press
0
1
0
0
0
run
l.adj
at
s
ni
p
i
M
M
M
-
off
M
0.0
M
8.0
233
d
40
o.f.-.r
h.y.s
M
50.0
1.0
M
-t
n
d-u
cn.tl
cp
oreV
alt1
M
M
M
i
-t
0
M
c
M
onof
20
or-r
2
al-1
Parameters
Depending on the settings, some data may not be displayed.
For details, refer to the Instruction Manual.
Operation will stop when the level is switched from Operation Level to Initial
Setting Level.
H172-E2-01-X+E5CB+Datasheet .fm Seite 7 Mittwoch, 22. Juni 2011 5:46 17