GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage
for many different applications. Voltages are selected by
applying jumpers (6) to the voltage change-over board
(Figure 13). To obtain some of the voltages as listed in
Table 7 (see below) will require a fine adjustment using
the voltage regulator (VR) control knob located on the
control panel.
Voltage Change-Over Board
The voltage change-over board (Figure 13) is located on
the control box, behind the generator control panel. This
board has been provided for eae of voltage selection.
Figure 13. Voltage Change-Over Board.
Generator Amperage
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed..
CAUTION
NEVER attempt to place jumper plates on the voltage
change-over board while the generator is in operation.
There exist the possibility of electrocution, electrical
shock or burn, which can cause severe bodily harm
or even death!.
Table 7. Voltages Available
Three Phase
(Switchable)
208V 220V 240V 416V 440V 480V
Single Phase
(Switchable)
120V 1127V 139V 240V 254V 277V
Table 8. Generator Maximum Amps
Rated Voltage Maximum Amps
1Ø 120 Volt 400 amps (4 wire)
1Ø 240 Volt 200 amps (4 wire)
3Ø 240 Volt 433 amps
3Ø 480 Volt 216 amps
HOW TO READ THE OUTPUT TERMINAL GAUGE
The AC ammeter and AC voltmeter gauges are controlled
by the AC ammeter and AC voltmeter change-over switches,
Both of these switches are located on the control panel and
DO NOT effect the generator output. They are provided to
help observe the phase to phase voltage and the current
flowing to the load at the UVWO terminals lugs.
Observe that the voltage change-over board (Figure 14)
has been configured for 3Ø, 240V operation.