AccuSpec V4.24ha Transaction #: 13741711 JOB TITLE: Date: 11/13/2019 Approved By: Submittal review and approval required prior to listed unit(s) being released for production and shipment. Unit(s) configured based on information provided. The Approver is responsible for ensuring the units, options, and accessories meet the job specifications.
AccuSpec V4.24ha SUBMITTAL SCHEDULE & DATA Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces Job Name: Location: Submitted by: R Patrick McGovern Date: 11/13/2019 Engineer: Architect: Contractor: Unit Tag Model Number Quantity of Units Btu/Hr Input Btu/Hr Output CFM Altitude Temperature Rise (degrees F) External Static Pressure (E.S.P) Total Static Pressure (T.S.P.
AccuSpec V4.24ha SUBMITTAL SCHEDULE & DATA Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces Job Name: Location: Submitted by: R Patrick McGovern Date: 11/13/2019 Engineer: Architect: Contractor: Unit Tag Model Number Quantity of Units Btu/Hr Input Btu/Hr Output CFM Altitude Temperature Rise (degrees F) External Static Pressure (E.S.P) Total Static Pressure (T.S.P.
AccuSpec V4.24ha SUBMITTAL SCHEDULE & DATA Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces Job Name: Location: Submitted by: R Patrick McGovern Date: 11/13/2019 Engineer: Architect: Contractor: Unit Tag Model Number Quantity of Units Btu/Hr Input Btu/Hr Output CFM Altitude Temperature Rise (degrees F) External Static Pressure (E.S.P) Total Static Pressure (T.S.P.
AccuSpec V4.24ha SUBMITTAL SCHEDULE & DATA Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces Job Name: Location: Submitted by: R Patrick McGovern Date: 11/13/2019 Engineer: Architect: Contractor: Unit Tag Model Number Quantity of Units Btu/Hr Input Btu/Hr Output CFM Altitude Temperature Rise (degrees F) External Static Pressure (E.S.P) Total Static Pressure (T.S.P.
AccuSpec V4.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 55 55,000 51,150 1097 618 43 12 43 4.35 0.3 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 55,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC55 29.8 18.13 19.03 17 16.24 4.71 7.19 10.22 3.1 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 12.81 6 9.07 3.3 1.9 16 40.19 28.19 1/2 14 3 3 93 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 65 65,000 60,450 1141 650 49 12 43 4.35 0.4 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 65,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC65 29.8 18.13 19.03 17 16.24 4.71 7.19 10.22 3.1 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 12.81 6 9.07 3.3 1.9 16 40.19 28.19 1/2 14 3 3 103 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 85 85,000 79,050 1650 619 44 13 48 4.35 0.5 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 85,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC85 35.53 20.31 22.05 22.52 18.42 4.50 7.98 10.27 1.32 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 6.73 8.74 12.13 3.86 1.54 22.03 45.83 30.69 1/2 18 3 3 148 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 110 110,000 102,300 1750 668 54 13 46 6.75 0.7 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 110,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC110 35.53 20.31 22.05 22.52 18.42 4.50 7.98 10.27 1.32 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 6.73 8.74 12.13 3.86 1.54 22.03 45.83 34.23 1/2 18 3 3 128 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 135 135,000 125,550 2160 719 54 14 51 6.75 1 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 135,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC135 35.53 23.06 22.05 22.52 21.18 4.50 7.98 10.18 2.15 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 8.09 8.45 12.95 3.48 1.54 22.03 45.83 33.83 1/2 20 3 3 165 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Propeller Unit to have two point adjustable suspension points to allow for level hanging with a variety of accessories. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 156 155,000 144,150 2600 862 51 18 62 6.75 1.1 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 155,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC156 35.53 23.06 22.05 22.52 21.18 4.50 7.98 10.18 2.15 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 8.09 8.45 13.45 3.98 1.54 22.03 45.83 33.83 1/2 20 4 4 165 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Propeller Unit to have two point adjustable suspension points to allow for level hanging with a variety of accessories. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 180 180,000 167,400 3020 676 51 15 53 6.75 1.3 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 180,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC180 42.53 25.81 22.05 29.52 23.93 4.50 7.98 10.36 1.73 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 9.47 9.82 14.92 3.98 3.97 26.6 45.83 33.83 1/2 22 4 4 215 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Propeller Unit to have two point adjustable suspension points to allow for level hanging with a variety of accessories. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 215 215,000 199,950 4585 699 48 17 60 9.15 1.6 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 215,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC215 42.53 31.31 22.05 29.52 29.43 4.50 7.47 9.86 1.63 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 6.72 12.58 17.58 3.72 3.97 26.6 45.83 33.83 3/4 24 4 4 265 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Propeller Unit to have two point adjustable suspension points to allow for level hanging with a variety of accessories. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 260 260,000 241,800 4585 831 49 20 70 10.95 1.9 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 260,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC260 42.53 31.31 22.05 29.52 29.43 4.50 7.47 9.86 1.63 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 6.72 12.58 17.58 3.72 3.97 26.6 45.83 34.83 3/4 24 4 4 265 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Propeller Unit to have two point adjustable suspension points to allow for level hanging with a variety of accessories. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.
AccuSpec V4.
AccuSpec V4.24ha GENERAL PERFORMANCE DATA General Performance Data Model At 0’ Elevation Btu/Hr. Input Btu/Hr. Output Entering Airflow (CFM) Outlet Velocity Air Temp. Rise (°F) Mounting Height (Max Ft.)1 Heat Throw (Max. Mtg. Ft.) 2 Unit Total Power (Amps) Condensate Produced (gal/hr) PTC 310 310,000 288,300 5400 765 49 19 67 9.85 2.3 As Configured at 0-2000 Ft. Elevation Btu/Hr. Input 310,000 Btu/Hr.
AccuSpec V4.24ha DIMENSIONS – UNIT Model PTC Dimensions Model Size Dimensions (inches) A B C D E F G H I PTC310 42.53 39.56 22.05 29.52 37.68 4.50 8.12 9.79 1.88 Gas Connection Fan Diameter Vent Pipe Connection Size Combustion Air Inlet Pipe Connection Size Approx. Shipping Weight 1 2 J K L M N P Q2 R 10.84 16.19 22.19 4.62 3.97 26.6 45.83 34.83 3/4 26 4 6 310 lbs. All models have 4 holes for mounting. Listed is the hole diameter and threads per inch to accept threaded rod.
Standards All unit(s) shall include: ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance Mechanical Configuration Condensing furnace section with 93% minimum efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.
The unit gas controls shall be provided with the following: Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit fires at 100% full fire based on a call for heat from a room thermostat. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.
The unit shall be equipped with tapped holes to accept 3/8”-16 threaded rod for suspension. Propeller Unit to have two point adjustable suspension points to allow for level hanging with a variety of accessories. Unit to have 4 suspension points. Accessories The following field installed accessory control devices shall be provided with the unit: A condensate drain kit consisting of one threaded PVC elbow and two specially designed condensate traps to allow the unit to operate and drain properly.