Installation Manual

®
English
P/N 031260 Rev C 03/13
* 180° field of view
** 360° field of view
Occupancy Sensor
LOS-C Series
Installation Instructions
Description
The LOS-C Series of ceiling-mounted sensors incorporate ultrasonic (CUS), infrared (CIR), and dual
technologies (CDT). They integrate into LutronR systems or function as stand-alone controls using a
LutronR power pack.
Features
Intelligent, continually adapting sensors
20 to 24 V-, IEC PELV/NECR, 33 mA nominal
• 450 ft
2
to 2000 ft
2
(42 m
2
to 140 m
2
) coverage, as indicated in model number (when mounted on 8 ft to 12 ft /
2.4 m to 3.7 m ceiling)
Dry contact closure available on -R models
LED indicators: Ultrasonic (US)-green, Infrared (IR)-red, Dual Tech (DT)-red and green
For indoor use only
Coverage and Placement
The occupant sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets,
shelves, hanging fixtures, etc.
For -CIR models, do not place sensor within 4 ft (1.2 m) of air vents, air handlers, windows, fans, etc., as this
may cause false triggering.
For -CDT and -CUS models, do not place sensor within 6 ft (1.2 m) of air vents, air handlers, windows, fans,
etc., as this may cause false triggering.
If installing a 180° occupant sensor, place the sensor on the same wall as the doorway so that hallway traffic
will not affect the sensor; otherwise, place in center of room.
Closely follow the diagrams for major and minor motion coverage.
Decrease total coverage area by 15% for “soft“ rooms (e.g. heavy draperies or heavy carpeting).
Indicated range is when unit is mounted on an 8 ft to 12 ft (2.4 m to 3.7 m) ceiling.
(U)LOS-CUS-500 / 1000 / 2000
(U)LOS-CIR-450 / 1500
(U)LOS-CDT-500 / 500R / 1000 / 1000R / 2000 / 2000R
IEC PELV/NECR Class 2 Devices
Model US Minor Motion US Major Motion IR Minor
Motion
IR Major
Motion
CUS-500 * 16 ft x 16 ft (4.9 m x 4.9 m) 22 ft x 22 ft (6.7 m x 6.7 m) NA NA
CUS-1000 * 23 ft x 23 ft (7.0 m x 7.0 m) 32 ft x 32 ft (9.8 m x 9.8 m) NA NA
CUS-2000 ** 23 ft x 45 ft (7.0 m x 13.7 m) 32 ft x 64 ft (9.8 m x 19.8 m) NA NA
CIR-450 ** NA NA 6.5 ft (1.9 m) 12 ft (3.7 m)
CIR-1500 ** NA NA 12 ft (3.7 m) 22 ft (6.7 m)
CDT-500 * 23 ft x 16 ft (7.0 m x 4.9 m) 32 ft x 22 ft (9.8 m x 6.7 m) 12 ft (3.7 m) 22 ft (6.7 m)
CDT-1000 * 23 ft x 23 ft (7.0 m x 7.0 m) 32 ft x 32 ft (9.8 m x 9.8 m) 12 ft (3.7 m) 22 ft (6.7 m)
CDT-2000 ** 23 ft x 45 ft (7.0 m x 13.7 m) 32 ft x 64 ft (9.8 m x 19.8 m) 12 ft (3.7 m) 22 ft (6.7 m)
Range Diagram and Dimensions
US Major Motion
US Minor Motion
US
Minor
Motion
US
Major
Motion
IR Minor Motion
IR Major Motion
US - Ultrasonic
IR - Infrared

Summary of content (16 pages)