Dimension Guide

Microwave Hood Combination
PRODUCT MODEL NUMBERS
KMHC319E KMHP519E KMHS120E
Rectangular to Round Transition:
NOTE: The minimum 3" (7.6 cm) clearance must exist between the top
of the microwave oven and the rectangular to round transition piece so
that the damper can open freely and fully.
Because Whirlpool Corporation includes a continues commitment to improve our
products, we reserve the right to change materials and specifications without notice.
Dimensions are for planning purposes only. For complete details, see Installation
Instructions packed with product. Specifications subject to change without notice.
VENTING REQUIREMENTS
Required:
A 120 volt, 60 Hz, AC only, 15- or 20-amp electrical supply with a fuse
or circuit breaker.
Recommended:
A time-delay fuse or time-delay circuit breaker.
A separate circuit serving only this microwave oven.
ELECTRICAL REQUIREMENTS
Ref. W10724870A
2/10/15
Page 1 of 2
A. Roof cap
B. 6" (15.2 cm) min. diameter round vent
C. Elbow (for wall venting only)
D. Wall cap
E. 3
1
4" x 10" to 6" (8.3 x 25.4 cm to 15.2 cm)
rectangular to round transition piece
F. Vent extension piece, at least 3" (7.6 cm) high
A
B
C
E
F
D
3" (7.6 cm)
Recommended Standard Fittings
The following length equivalents are for use when figuring vent length.
See the examples in “Recommended Vent Length.”
A. Rectangular to round transition piece: 3
1
4" x 10" to 6" = 5 ft
(8.3 x 25.4 cm to 15.2 cm = 1.5 m)
B. Roof cap: 3
1
4" x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m)
C. 90° elbow: 3 " x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m)
D. 90° elbow: 6" = 10 ft (15.2 cm = 3 m)
E. Wall cap: 3
1
4" x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m)
F. 45° elbow: 6" = 5 ft (15.2 cm = 1.5 m)
G. 90° flat elbow: 3
1
4" x 10" = 10 ft (8.3 x 25.4 cm = 3 m)
A B C
D E F G
Recommended Vent Length
A 3
1
4" x 10" (8.3 x 25.4 cm) rectangular or 6" (15.2 cm) round vent
should be used.
The total length of the vent system including straight vent, elbow(s),
transitions and wall or roof caps must not exceed the equivalent of
140 ft (42.7 m) for either type of vent. See “Recommended Standard
Fittings” section for equivalent lengths.
For best performance, use no more than three 90° elbows.
To calculate the length of the system you need, add the equivalent
lengths of each vent piece used in the system. See the following
examples:
3
1
4" x 10" (8.3 x 25.4 cm) vent system = 73 ft (22.2 m) total
A B
C
6 ft (1.8 m)
2 ft
(0.6 m)
A. One 3
1
4" x 10" (8.3 x 25.4 cm) 90° elbow = 25 ft (7.6 m)
B. 1 wall cap = 40 ft (12.2 m)
C. 2 ft (0.6 m) + 6 ft (1.8 m) straight = 8 ft (2.4 m)
6" (15.2 cm) vent system = 73 ft (22.2 m) total
A B
C D
6 ft (1.8 m)
2 ft
(0.6 m)
A. Two 90° elbows = 20 ft (6.1 m)
B. 1 wall cap = 40 ft (12.2 m)
C. 1 rectangular to round transition piece = 5 ft (1.5 m)
D. 2 ft (0.6 m) + 6 ft (1.8 m) straight = 8 ft (2.4 m)
If the existing vent is round, a rectangular to round transition piece must
be used. In addition, a rectangular 3" (7.6 cm) extension vent between
the damper assembly and rectangular to round transition piece must be
installed to keep the damper from sticking.