Chapter 5: Inspection, Repair, and Replacement of CSST
5.1 Minimum Inspection Requirements Checklist
All installations shall be inspected by the authority having jurisdiction in accordance with
state and local mechanical, electric, and/or plumbing codes, or in the absence of such codes,
the National Fuel Gas Code (NFPA 54/ANSI Z 223.1), the International Fuel Gas Code (IFGC), the
National Electric Code (NFPA 70), and/or the Uniform Plumbing Code (UPC), as applicable.
Installer has HOME-FLEX® or VPC Alpha-FLEX™
Qualied Installer Card
Inspection and pressure test completed at rough-in
(Chapter 6)
Only xed appliances are directly connected to the
HOME-FLEX® system
(Section 4.6)
Connections to moveable appliances are made with
HOME-FLEX® Flexible Appliance Connectors, or similar
approved devices
(Section 4.6)
System properly sized to deliver pressure required for
all appliances
(Section 3.2 and Chapter 7)
Regulator, if required, is installed in an accessible
location with a shut-o valve mounted ahead of it
(Section 4.8)
If routed underground or through masonry,
HOME-FLEX® tubing is properly sleeved
(Section 4.3)
Striker plate protection in place where required
(Section 4.4)
HOME-FLEX® tubing is supported at proper interval
(Section 4.1 and Table 4.2)
No damaged tubing dents or defects
(Section 5.2)
Direct bond to the electrical service grounding
electrode system
(Section 4.10)