ga GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs) 2020005003 (12/09) Page 1 of 18
TABLE OF CONTENTS IMPORTANT NOTICE………………………………………………………………………………………………………………………………………..3 Transformer X0 Bond Warning Statement………………………………………………………………………………..3 PRODUCT DESCRIPTION…………………………………………………………………………………………………….…….…………………….4 APPLICATION GUIDELINES…………………………………………………………………………………………………….………….….……….4 SPD Type…………………………………………………………………………………………………………………………………………….4 Maximum Continuous Operating Voltage (MCOV).…………………………………………………..…………….5 Electrical System Configuration…………………………………………………………………………….………….…….
IMPORTANT NOTICE THE ENTIRE CONTENT OF THIS MANUAL MUST BE READ AND FULLY UNDERSTOOD BEFORE ATTEMPTING ANY INSTALLATION OR ENERGIZATION OF THE SPD. If there are any questions about the operational status, or integrity of the electrical system prior to installation of the SPD, please consult a qualified trained electrician before attempting to continue.
PRODUCT DESCRIPTION: GE TRANQUELL Series Type 2 Surge Protective Devices (formerly called TVSS), are for installation on low voltage electrical distribution systems. GE SPDs are designed to protect electrical equipment loads against the damaging effects of transient voltages that can be induced or generated as a result of remote lightning, power equipment switching or high frequency disturbances.
MAXIMUM CONTINUOUS OPERATING VOLTAGE (MCOV) This value defines the maximum line-to-line or line-to-neutral continuous AC voltage that can be safely applied to the protector. MCOV levels for GE Tranquell Series SPDs are set at 115% of nominal system voltage. For 120-volt AC systems, the MCOV is 125%.
WARNING THE EQUIPMENT COVERED BY THESE INSTRUCTIONS SHOULD BE INSTALLED AND SERVICED ONLY BY COMPETENT, QUALIFIED PERSONNEL UTILIZING PROPER SAFETY PRACTICES AND PROCEDURES THESE INSTRUCTIONS ARE WRITTEN FOR SUCH PERSONNEL AND ARE NOT INTENDED AS A SUBSTITUTE FOR ADEQUATE TRAINING AND EXPERIENCE IN SAFE PROCEDURES FOR THIS TYPE OF EQUIPMENT. PRE-INSTALLATION REQUIREMENTS: Prior to energization of the GE Tranquell SPD, it is critical that the following items have been addressed.
VOLTAGE RATINGS & POWER SOURCE CONFIGURATIONS TRANQUELL MODEL NOMINAL VOLTAGE (50/60Hz) MAXIMUM CONTINOUS OPERATING VOLTAGE (MCOV) SYSTEM TYPE SOURCE CONFIGURATION L1 Single Phase 3 Wire + Ground N L2 TLE / TME 120S 120 / 208240V L1 150V (L-N / L-G) N Dual Phase 3 Wire + Ground L2 TLE / TME 120Y 120 / 208V 150V (L-N / L-G) L1 TLE / TME 220Y 220 / 380V 320V (L-N / L-G) TLE / TME 240Y 240 / 415V 320V (L-N / L-G) TLE / TME 277Y 277 / 480V 320V (L-N / L-G) Three Phase WYE, 4 Wire + G
Example of an NEC Compliant Grounding Arrangement for a Separately Derived System PHASE C PHASE B PHASE A X2 X1 NEUTRAL GROUND SPD N X0 Primary Dist. Panel w/Overcurrent or Service Disconnect Means X3 Bonding Jumper Ref. NEC 250 -30 (a) (1) Grounding Electrode Conductor Ref. NEC 250.62 - 250.64 - 250.66 Grounding Electrode Ref. NEC 250 -30 (a) (4) Equipment Grounding Conductor Ref. NEC 250.
WARNING POWER MUST BE PROVEN DISCONNECTED BEFORE STARTING INSTALLATION, INSPECTION OR MAINTENANCE. FAILURE TO DO SO MAY CAUSE SERIOUS INJURY, DEATH AND/OR PROPERTY DAMAGE. INSTALLATION: Before attempting installation, make sure that the pre-installation requirements of this manual have been satisfied. If the status of the pre-installation requirements are not known, do not attempt to continue. 1. MOUNTING The GE Tranquell Wall Mounted SPD must be installed as close to the protected circuit as possible.
2.
SPD Model Type: TLE-WMF TLE/TR5 - WMF SPD Model Type: TME-WMF 2020005003 (12/09) Page 11 of 18
SPD Model Type: TLE-WM4 TLE/TR5 – WMF4 SPD Model Type: TME-WM4 TME/TR5 – WMF4 2020005003 (12/09) Page 12 of 18
INSTALLATION (CONT.): 3. CONDUIT FITTINGS A ¾” NPT Offset style conduit nipple is provided as an integral part of the SPD on WM and WMF models for routing the wiring pigtails into the electrical panel. Caution: Do not attempt to remove, twist, turn or alter the integral conduit nipple. This will cause irreversible damage to the SPD internal wiring and will void the warranty. An additional conduit spacer, adapter or fitting should be used only when necessary to facilitate installation.
POWER WIRING AND REMOTE ALARM LOCATIONS Labeled “Phase C” (Black) Labeled “Phase B” (Black) Labeled “Phase A” (Black) Neutral (White) Ground (Green) Power Wiring Alarm Contacts Remote Contact Status Modes NC (Blue) NO (Orange) COM (Yellow) Normal Indication: NO – COM = Closed NC – COM = Open Alarm Indication: NO – COM = Open NC – COM = Closed The above illustration represents the wiring and alarm contacts for both the TLE and TME Wall Mounted SPD for 3 phase applications.
INSTALLATION EXAMPLE X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X GE Surge Protective Device X X SPD connecting wires. Twisted together, using minimum lengths. X X X X X X X X X 30A 3-Pole Circuit Breaker.
INSTALLATION EXAMPLE (FLUSHMOUNT MODELS) Wall surface omitted to illustrate SPD mounting arrangement Wall Studs X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X GE Surge Protective Device Flush Mount Type Horizontal 2”x4” Cross Members X X X X X X X X X X X Neutral Bus Ground Bus Electrical Service Panel 2020005003 (12/09) Page 16 of 18
WARNING UPON ENERGIZATION OF THE SPD, IF ANY OF THE LAMPS OR ALARMS INDICATES AN ABNORMAL CONDITION, POWER SHOULD PROMPTLY BE DISCONNECTED FROM THE SPD. THE ELECTRICAL SYSTEM SHOULD BE INSPECTED AND THE PRE-INSTALLATION REQUIREMENTS SHOULD BE VALIDATED. DO NOT ATTEMPT TO LEAVE POWER APPLIED TO THE SPD, OR REENERGIZE THE SPD IN THE EVENT OF AN ALARM CONDITION. PLEASE CONTACT YOUR LOCAL GE REPRESENTATIVE FOR FURTHER ASSISTANCE.
SERVICING / TROUBLESHOOTING: The GE Tranquell Series SPD contains no user serviceable parts and requires no calibration. The rugged design of the SPD should provide many years of service. Should a condition occur that results in premature failure of the GE Tranquell SPD, the integral fusing or required circuit breaker will safely interrupt current flow through the SPD without disrupting power to the protected equipment.