10-4. CENTRAL DRAIN PAN
HOW TO INSTALL CENTRAL DRAIN PAN
All components and parts including drain pan and piping materials are to be procured
locally.
If a drain pan is installed, refrigerant piping cannot be routed out the bottom.
Do not locate the unit over an area that cannot get wet.
It is possible under certain circumstances that some water may not be captured by the drain
pan.
Do not use a drain pan where freezing conditions in the pan or piping may occur.
If drain pan piping connections are routed out the bottom of the pan, provide a foundation to
raise the unit a minimum of 7-7/8 (200).
DRAIN PAN INSTALLATION PROCEDURE
Drill holes in dowels located in base feet as shown in the gure
above (total 8).
Attach drain pan using self tapping screws at dowel locations.
Model name Dimension F
AOUA72TLBV
5-1/2 (139)
AOUA96TLBV
AOUA120TLBV 17-11/16 (449)
7-7/8
(200)
13/16 (20)
5-5/16
(135.7) 7-1/2 (190) 7-1/2 (190)F
Found-
ation
Found-
ation
Drain pan
Cabinet
Dowel (at 4 positions in total)
Provide sufcient space under unit for
access to piping for maintenance.
(Recommended height of foundation:
7-7/8 (200) or more.
Be sure all piping joints and connections
do not leak.