Instructions
10
Electric installation
The panel is fitted with a two-conductor cable for 1/N 230 V / Hz with a plug for connection into a socket.
Removal of the plug and shortening of the supply lead will not result in loss of warranty.
Colour marking of the conductors:
Phase – brown
Central (live) conductor – blue
The power supply cable is connected to a box on the wall, see Fig 6.
The panel must not be placed directly under an electric socket.
The supply cable must be fitted with a device for disconnection from the mains in which the distance between the disconnected contacts is
at least 3 m for all poles.
If the supply cable of this appliance is damaged, it has to be replaced by the producer or a service technician.
Controlling the panel
We recommend controlling this panel using an external room thermostat with a switch.
The room thermostat maintains the set air temperature in the room.
Furthermore, the panel is fitted with a limit thermostat which ensures its safe operation.
Uninstalling the panel
Disconnect the panel from the mains using a two-pole switch before uninstalling it. Lift the panel upwards vertically and sideways in such a
way that it is released from the screws. Furthermore, the supply cable must be disconnected from the box on the wall.
Technical specifications
The panel can be installed on bases of flammability class A, B, C1 or C2.
Type
Dimensions (mm)
(LxWxH)
Weight
(kg)
Output
(W)
Current
(A)
Voltage
(V) AC
Protection
class
Coverage
GS 300 585x585x39 9,8 300 1,3
230 V II IP 44
GS 600 1185x585x39 17,5 600 2,6
GS 850 1185x785x39 21,6 850 3,7
GS 500 1200x400x39 10,8 500 2,2