Instruction Manual GX Valve and Actuator D103175X012 August 2011 Fisherr GX Control Valve and Actuator System Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Valve Installation . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Table 1. Fisher GX Valve Specifications Specifications EN ASME Valve Body Size DN 15, 20, 25, 40, 50, 80, 100, 150 NPS 1/2, 3/4, 1, 1-1/2, 2, 3, 4, 6 Pressure Rating PN 10 / 16 / 25 / 40 per EN 1092-1 CL150 / 300 per ASME B16.34 End Connections Flanged raised face per EN 1092-1 Flanged raised face per ASME B16.5 1.0619 steel ASME SA216 WCC steel 1.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 control of the process. Do not expose this product to service conditions or variables other than those for which the product was intended. If you are not sure what these conditions are you should contact your Emerson Process Management sales office for more complete specifications. Provide the product serial number (shown on the nameplate, figure 2) and all other pertinent information. Figure 2.
GX Valve and Actuator Instruction Manual August 2011 D103175X012 4. If continuous operation is required during inspection or maintenance, install isolating valves on either side of the control valve with a bypass valve to control the flow while the control valve is receiving maintenance. WARNING Personal injury could result from packing leakage. Valve packing is tightened before shipment; however the packing might require some readjustment to meet specific service conditions.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 There are several optional actuator constructions, depending on supply pressure. Refer to the nameplate on the top of the actuator to determine the construction installed. Refer to figure 3 and table 2 for proper spring configuration. Note Older GX actuator nameplates do not contain spring configuration information.
GX Valve and Actuator Instruction Manual August 2011 D103175X012 Figure 3. Spring Configuration GG00398-B Actuator Disassembly (For Air-to-Close Constructions - see figure 20 or 21) 1. Remove the stem connector nut half (key 23), stem connector bolt half (key 24), and travel indicator (key 26). WARNING To avoid personal injury or property damage due to actuator springs (key 12) being under compression, remove the long cap screws (key 16) last.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 suddenly come loose and jump, due to the compressed energy of the springs. If the upper casing is stuck to the diaphragm and lower casing when you begin loosening the casing cap screws, pry the casings apart with a prying tool. Always ensure that the springs are dispersing energy and the upper casing is moving against the long bolts during disassembly. 2. Remove the short actuator casing cap screws and hex nuts (keys 17 and 18) first.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Table 4. Body Nut (Key 7) Torque Requirements VALVE SIZE TORQUE NSm lbfSft DN 15, 20, 25 (NPS 1/2, 3/4, 1) 45.5 33.5 DN 40 (NPS 1-1/2) 79.8 58.9 DN 50 (NPS 2) 79.8 58.9 DN 80 (NPS 3) 163 120 DN 100 and DN 150 (NPS 4 and 6) 282 208 Table 5.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 10. Connect a separate air supply to the actuator air supply connection (as shown on the yoke in figure 18 or 19) and apply sufficient air pressure to raise the actuator rod (key 22) to the travel stop. Note If converting from air-to-close to air-to-open action, first move the vent cap (key 21) from the air supply connection on the yoke leg (see figure 20 or 21) to the top of the casing (see figure 18 or 19). 11.
GX Valve and Actuator Instruction Manual August 2011 D103175X012 2. Install the diaphragm (key 10) on the diaphragm plate (key 11). Place the diaphragm O-ring (key 109) and the washer (key 15) over the center hole of the diaphragm, so that the convex part of the washer is facing down toward the diaphragm and contains the O-ring. Ensure the convex part of the washer is guided in the diaphragm center hole as shown in figure 20 or 21. 3.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 FIELDVUE DVC2000 Digital Valve Controller Mounting This section provides instruction on mounting the FIELDVUE DVC2000 digital valve controller to the GX control valve. For further detail on the operation and maintenance of the DVC2000, refer to the DVC2000 instruction manual.
GX Valve and Actuator August 2011 Instruction Manual D103175X012 A. Mounting the DVC2000 to an air-to-open GX actuator (spring-to-close) (see figure 4 and figure 18 or 19): 1. Attach the magnetic feedback array (supplied with the DVC2000) to the valve stem connector using the alignment template (supplied with the mounting kit) for accurate alignment. 2. Remove the plug (R1/8) from the back of the DVC2000 housing (Port B in figure 4).
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Packing Adjustment For spring-loaded single PTFE V-ring packing (figure 15) or for Graphite ULF packing (figure 16), the Belleville spring pack (key 34) maintains a sealing force on the packing. If leakage is detected around the packing follower (key 29) check to be sure that the packing follower (key 29) is tight. Using a wrench, tighten the packing follower (key 29) in 1/4 turn intervals until the leakage is stopped.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 WARNING If there is evidence of process fluid under pressure leaking from the joint, retighten the valve body/joint nuts and return to the Warning at the beginning of the Maintenance section to ensure proper steps have been taken to isolate the valve and relieve process pressure, thus avoiding property damage or personal injury. 5.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 CAUTION Inspect the valve stem, threads and packing box surfaces for any sharp edges that might cut the packing. Scratches or burrs could cause packing box leakage or damage the new packing. 13. Inspect the valve stem, threads and packing box surfaces for any sharp edges that might cut the packing. Scratches or burrs could cause packing box leakage or damage the new packing.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Table 9. Stem Extension Torque Requirements VALVE SIZE TORQUE DN NPS Nm Lbfft 15, 20, 25, 40, 50 1/2, 3/4, 1, 1-1/2, 2 40 30 80, 100 3, 4 120 89 Table 10. Bellows Nut Torque Requirements VALVE SIZE TORQUE DN NPS Nm Lbfft 15, 20, 25, 40, 50 1/2, 3/4, 1, 1-1/2, 2 350 260 80, 100 3, 4 650 480 25. Tighten the packing follower (key 29) to the torque specified in table 7.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Note The following step also provides additional assurance that the valve body fluid pressure has been relieved. 7. For standard bonnet constructions (figures 18, 19, 20, and 21), body nuts (key 7) attach the actuator yoke (key 8) to the valve body (key 1). Loosen these nuts approximately 3mm (1/8 inch). For extension and bellows bonnet constructions, bonnet nuts (key 46) attach the actuator yoke (key 8) to the extension bonnet (key 39).
Instruction Manual GX Valve and Actuator August 2011 D103175X012 16. Remove the Belleville spring pack (key 34) and packing spacer (key 30) from the bonnet (key 4). Carefully push out the remaining packing box parts from the bonnet (key 4) using a rounded rod or other tool which will not scratch the packing box wall. Clean the packing box and the metal packing box parts. Table 11.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 27. Tighten the stem connector cap screws (key 25) to 35 Nm (26 lbfft). 28. Tighten the packing follower (key 29) to the torque specified in table 7. Alternately, the packing follower can be tightened by the following method: a. Tighten the packing follower until the Belleville springs are compressed 100% (or completely flat), as detected by a rapid increase in nut torque. b.
GX Valve and Actuator Instruction Manual August 2011 D103175X012 5. Use a wrench to unscrew the plug/stem assembly (key 3) from the stem extension (key 40) or from bellows/stem assembly (key 49) as follows: a. Insert the wrench onto the stem extension hex flats (see figures 22 and 23). CAUTION In the following procedure, take precautions to ensure the valve plug and stem finish are not damaged. b.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 5. Seat Ring Removal and Installation Tool A A A A B G B G B E B H K E E H D E F D D F F D J F C C C C C C DN15, 20, 25 (NPS 1/2, 3/4, 1) DN40, 50, 80, 100 (NPS 1-1/2, 2, 3, 4) DN150 (NPS 6) DN25 Cav III (NPS 1) GG01215 GE02918-6 Table 12.
GX Valve and Actuator Instruction Manual August 2011 D103175X012 1. Before installing the new seat ring / cage, thoroughly clean the threads in the valve body port. Apply suitable lubricant to the threads and to the 60 surface of the new seat ring (key 4). Screw the seat ring into the valve body. Using the seat ring tool, tighten the seat ring and torque according to the values in table 8. Remove all excess lubricant after tightening. 2. For standard bonnet constructions, perform the following.
Instruction Manual D103175X012 GX Valve and Actuator August 2011 f. Clean the body/extension bonnet seating gasket surface and install the gasket (key 5). g. Install the extension bonnet and plug/stem assembly onto the valve body. Install the body/yoke nuts (key 7) and tighten evenly using a cross-tightening procedure. See table 4 for torque requirements.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 D Date of maintenance D Trim material D Port diameter D Flow capacity (Cv / Kv) D Flow characteristic D Actuator Action ATO/ATC Bellows Maintenance This section provides instruction on the replacement of the bellows / stem assembly (see key 49 in figure 23). 1. Remove the actuator, bonnet assembly as described in the Replacing Packing section (steps 1 through 10). 2.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 7. Fisher GX Handwheel Orientation and Grease Zerk Location GE05810-D GE05809-D APPLY LUBRICANT AIR-TO-OPEN, SPRING-TO-CLOSE AIR-TO-CLOSE, SPRING-TO-OPEN Handwheel Operation CAUTION This handwheel is designed only for use with size 225 and 750 actuators with 20 mm travel. To avoid equipment damage, do not assemble this handwheel on size 750 actuators with 40 mm travel or size 1200 actuators.
GX Valve and Actuator Instruction Manual August 2011 D103175X012 During normal pneumatic operation when the handwheel is not needed, a locking screw (see figure 6) is provided on the side of the handwheel housing to lock the handwheel levers out of the way. WARNING To avoid personal injury or equipment damage due to possible sudden shifting or falling of the valve assembly, do not lift the valve assembly by the handwheel. GX Handwheel Installation (for use with 20mm travel only) 1.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 8. Fisher GX Travel Stop Assembly ADJUSTABLE CAP SCREW (2) COVER PLATE LEVER CAP SCREW (4) STUD AND NUT (4) DOWNSTOP LEVER COVER PLATE CAP SCREW (4) STUD AND NUT (4) ADJUSTABLE CAP SCREW (2) UPSTOP GX Travel Stop Installation Downstop 1. Note the orientation of the lever to the stem connector for downstop positioning, as shown in figure 9.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Figure 9.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 10. Fisher GX Balanced Trim (Standard for DN 80 and 100 [NPS 3 and 4]) GE07161-D APPLY LUBRICANT Figure 11. Fisher GX Balanced Trim (DN 150 [NPS 6]) Figure 12. Fisher GX Unbalanced Port-Guided Trim (DN 40 to 150 [NPS 1-1/2 to 6]) GE03755_8 Figure 13.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Figure 14. Fisher GX Control Valve with Typical Soft Seat Trim Construction (Port Sizes of 36mm - 136mm) Figure 16. Fisher GX Graphite ULF Packing DN15 through DN100 (NPS 1/2 through 4) 2 43 44 42 43 3 W9023-1 GE11961_C Figure 15. Fisher GX PTFE Packing DN15 through DN150 (NPS 1/2 through 6) Figure 17.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 18.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Figure 19.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 20.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Figure 21.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 22.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Figure 23.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 24. Cryogenic Extension Bonnet APPLY LUBRICANT GE23746-A Figure 25.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Figure 26. Bellows Nut Removal and Installation Tool C HEX C HEX D D B F B F A A E E G H 8 mm 6 mm DN80 and 100 (NPS 3 and 4) DN15, 20, 25, 40, and 50 (NPS 1/2, 3/4, 1, 1-1/2, and 2) GF00536_3 Table 13. Bellows Nut Removal and Installation Tool Dimensions Valve Size A B C DN NPS 15, 20, 25, 40, 50 1/2, 3/4, 1, 1-1/2, 2 125 25 36 80, 100 3, 4 135 25 1.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 27.
GX Valve and Actuator August 2011 Figure 28.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Figure 29. Repair Nameplate (Spaces Provided for Recording Trim Maintenance Data) TRIM MATERIAL FLOW CHARACTERISTIC DATE OF MAINTENANCE PORT DIAMETER GE11233-B ACTUATOR ACTION FLOW CAPACITY Parts Ordering Each valve is assigned a serial number which can be found on the valve or on the nameplate (figure 2 and key 35, not shown). The nameplate will normally be fitted to the actuator.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Parts Kits Valve Size Stem Diameter PTFE packing (Contains keys 32 and 33) DN 25, 40, and 50 (NPS 1, 1-1/2, and 2) 10 mm RGXPACKX012 DN 80 and 100 (NPS 3 and 4) 14 mm RGXPACKX022 DN 150 (NPS 6) 19 mm RGXPACKX072 Graphite ULF packing (Contains keys 42, 43, and 44) RGXPACKX052 RGXPACKX042 RGXPACKX082 PACKING KITS Actuator Size 225 750 1200 Actuator (Contains keys 10, 19, 109, and 20) RGX225X0022 RGX750X0032 RGX1200X042 Nitril
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Parts List Note For part numbers not shown, contact your Emerson Process Management sales office.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, LCC, WCC/1.0619 and CF3M/1.4409 Valve Body Material) VALVE SIZE PORT SIZE mm TRAVEL PLUG STYLE mm VALVE PLUG MATERIAL STEM MATERIAL SEAT RING MATERIAL CF3M Micro-Flow Flat S31603 4.8 20 Unbalanced S31603/ CoCr-A Seat R31233 N06022 DN15 (NPS 1/2) Unbalanced (Standard) 9.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, LCC, WCC/1.0619 and CF3M/1.4409 Valve Body Material) VALVE SIZE PORT SIZE mm TRAVEL PLUG STYLE mm VALVE PLUG MATERIAL STEM MATERIAL SEAT RING MATERIAL CF3M Micro-Flow Flat S31603 4.8 20 Unbalanced S31603/ CoCr-A Seat R31233 N06022 Unbalanced (Standard) 9.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, CD3MN Valve Body Material) VALVE SIZE PORT SIZE mm 4.8 DN25 (NPS 1) 9.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, CD3MN Valve Body Material) VALVE SIZE PORT SIZE mm 36 DN80 (NPS 3) 46 70 TRAVEL mm 20 20 40 20 46 70 PLUG STYLE 20 40 90 52 SEAT RING MATERIAL CD3MN S31803 CD3MN CD3MN S31803 CD3MN/ PTFE Seat CD3MN S31803 CD3MN CD3MN S31803 CD3MN/ PTFE Seat CD3MN S31803 CD3MN CD3MN S31803 S31803 S31803 Unbalanced Unbalanced Balanced VALVE PLUG/STEM PART NUMBER
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, CF3 Valve Body Material) VALVE SIZE PORT SIZE mm 4.8 DN25 (NPS 1) 9.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, CF3 Valve Body Material) VALVE SIZE PORT SIZE mm 36 DN80 (NPS 3) 46 TRAVEL PLUG STYLE mm 20 20 40 46 70 20 40 90 54 CF3 S31803 CF3 CF3 S31803 CF3/ PTFE Seat CF3 S31803 CF3 CF3 S31803 CF3/ PTFE Seat CF3 S31803 CF3 CF3 S31803 CF3/ PTFE Seat S30403 S31803 CF3 CF3 S31803 CF3 CF3 S31803 CF3/ PTFE Seat CF3 S31803 CF3 CF3 S31803 CF3/ PTFE Seat
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, CN7M and CW2M Valve Body Material) VALVE SIZE PORT SIZE mm 4.8 DN25 (NPS 1) 9.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Plain Bonnet, CN7M and CW2M Valve Body Material) VALVE SIZE PORT SIZE mm 36 DN80 (NPS 3) 46 TRAVEL PLUG STYLE mm 20 20 40 46 70 20 40 90 56 CW2M N06022 CW2M CW2M N06022 CW2M/ PTFE Seat CW2M N06022 CW2M CW2M N06022 CW2M/ PTFE Seat CW2M N06022 CW2M CW2M N06022 CW2M/ PTFE Seat N06022 N06022 CW2M CW2M N06022 CW2M CW2M N06022 CW2M/ PTFE Seat CW2M N06022 CW2M
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Extension Bonnet, LCC, WCC/1.0619 and CF3M/1.4409 Valve Body Material) VALVE SIZE PORT SIZE mm TRAVEL PLUG STYLE mm VALVE PLUG MATERIAL STEM MATERIAL SEAT RING MATERIAL CF3M 4.8 20 Unbalanced R31233 S31603/ CoCr-A Seat 9.5 20 Unbalanced (Reduced Capacity) 20 Unbalanced Unbalanced (Standard) 9.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Extension Bonnet, LCC, WCC/1.0619 and CF3M/1.4409 Valve Body Material) VALVE SIZE PORT SIZE mm TRAVEL PLUG STYLE mm VALVE PLUG MATERIAL STEM MATERIAL SEAT RING MATERIAL CF3M 4.8 20 Unbalanced R31233 DN25 (NPS 1) 9.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Extension Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Bellows Bonnet, LCC, WCC/1.0619 and CF3M/1.4409 Valve Body Material) VALVE SIZE PORT SIZE TRAVEL mm mm PLUG STYLE VALVE PLUG MATERIAL STEM MATERIAL SEAT RING MATERIAL CF3M TRIM STYLE Micro-Flow Flat S31603 4.8 20 Unbalanced S31603/ CoCr-A Seat R31233 N06022 DN15 (NPS 1/2) Unbalanced (Standard) 9.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Bellows Bonnet, LCC, WCC/1.0619 and CF3M/1.4409 Valve Body Material) VALVE SIZE PORT SIZE mm TRAVEL PLUG STYLE mm VALVE PLUG MATERIAL STEM MATERIAL SEAT RING MATERIAL CF3M Micro-Flow Flat S31603 4.8 20 Unbalanced S31603/ CoCr-A Seat R31233 N06022 Unbalanced (Standard) 9.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Bellows Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Bellows Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Bellows Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Bellows Bonnet, LCC, WCC/1.0619 and CF3M/1.
Instruction Manual GX Valve and Actuator August 2011 D103175X012 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Bellows Bonnet, CW2M Valve Body Material) VALVE SIZE PORT SIZE mm 4.8 DN25 (NPS 1) 9.
Instruction Manual GX Valve and Actuator D103175X012 August 2011 Key 3 Valve Plug/Stem and Key 2 Seat Ring (Bellows Bonnet, CW2M Valve Body Material) VALVE SIZE PORT SIZE mm 36 DN80 (NPS 3) 46 70 46 TRAVEL PLUG STYLE mm 20 20 20 20 DN100 (NPS 4) 20 STEM MATERIAL SEAT RING MATERIAL CW2M N06022 CW2M CW2M N06022 CW2M/ PTFE Seat CW2M N06022 CW2M CW2M N06022 CW2M/ PTFE Seat N06022 N06022 CW2M CW2M N06022 CW2M CW2M N06022 CW2M/ PTFE Seat N06022 N06022 CW2M Unbalanced
GX Valve and Actuator August 2011 Instruction Manual D103175X012 Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher, FIELDVUE, Cavitrol, and Whisper Trim are marks owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co.