Specifications

49
2.2 Steam Heater and Steam Spray Type Humidifier
2.2.1 Specifications
Applicable Model
Heater capacity (kW)
Heater specification
Heat source
Humidifier capacity (kg/hr.)
Heat source
Steam
Heater
Steam
Spray Type
Humidifier
USP3H
15.7
1 rowF.P.2.0mm
1.6
USP5H
22.0
1 rowF.P.2.5mm
2.6
USP8H
31.4
3.7
USP10H
41.9
4.7
USP15H
62.8
6.8
USP20H
83.7
8.4
1 rowF.P.3.5mm
0.4 MPa steam
0.0035 MPa steam
2.2.2 Mounting Procedure and Parts Illustrations
Mounting Work Procedure
USP3H
USP5H
USP8H
USP10H
1. Mounting Work Procedure
1. Remove the suction grille, front plate (upper) and rear plate.
2. Remove the rubber bush from the side plate.
3. Align the center of the steam heater with that of the casing, and drill holes on site.
4. To mount the steam spray type humidifier, with the cap and socket mounted to its spray nozzle, fix the
steam spray type humidifier securely to the steam heater.
5. Mount the steam heater thus assembled to the evaporator.
6. Wrap the pieces of asbestos round the joints for steam heater and steam spray nozzle at the portion
100 mm from the joint flange, and fix them tightly by the brass wire. (This measure is to prevent the
steam piping from coming in contact with the casing.)
7. Screw each of the joints into the heater inlet/outlet pipe and spray inlet pipe.
8. Place the suction grille, front plate (upper) and rear plate back in position.
2. Cautions on Mounting Work
¡ The mounting work illustration in the following page shows the right-hand setup of the steam heater.
For the left-hand setup of it, remove the heater upper and lower frames, give the heater 180° turn, re-fit
the frames and fix them securely.
¡ Replace the steam spray nozzle socket with the steam spray nozzle cap and vice versa.
¡ When the steam heater and the steam spray type humidifier are unused for a long period of time, drain
the water inside piping without fail.