Bosch Multi Zone Ductless Air Conditioner / Heat Pump Climate 5000 Series Installation Manual
| Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Data subject to change Installation Manual 05.2019 | Bosch Thermotechnology Corp.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 3 Table of Contents 1 Key to Symbols and Safety Instructions 4 1.1 Key to Symbols 1.2 Safety 4 4 2 Components 6 3 Installation Summary 7 4 Installation Diagram 8 5 Specifications 9 6 Outdoor unit installation 10 7 Refrigerant Piping Connection 14 7.1 Connection Instructions – Refrigerant Piping 14 8 Wiring 17 8.1 Outdoor unit wiring 8.2 Wiring Diagrams 17 18 9 Air Evacuation 21 9.
| Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual 1 Key to Symbols and Safety Instructions 1.2 Safety 1.1 Key to Symbols Please read safety precautions before installation Incorrect installation due to ignoring instructions can cause serious damage or injury. Warnings WARNING: Warnings in this document are identified by a warning triangle printed against a grey background.
Installation Manual WARNING: This product can expose you to chemicals including Lead and Lead components, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www. P65Warnings.ca.gov. Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 5 NOTICE: PROPERTY DAMAGE Install condensate drainage piping according to the instructions in this manual.
| Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual 2 Components The air conditioning / heat pump system installation requires the following components. Use all of the installation parts and components to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or equipment failure. Name Quanity Drain joint 1 Seal ring 1 Liquid side Connecting pipe assembly Φ6.35 (1/4 in) Φ9.52 (3/8 in) Φ9.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 7 3 Installation Summary 1 2 3 L Install the outdoor unit (Page 10) Connect the refrigerant pipes (Page 14) 5 N Connect the wires (Page 17) 4 MC Perform a test run (Page 23) MC Evacuate the refrigeration system (Page 21) Figure 1 Bosch Thermotechnology Corp. | 05.
| Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual 4 Installation Diagram More than 4.7in More than 4.7in 2 More than 4.7in More than 5.9in 1 3 More than 4.7in Air Filter Air Filter Air Filter Air Filter 4 More than 23.6in 5 6 More than 4.7in Two-Zone More than 11.8in Three-Zone More than 11.8in Four-Zone Five-Zone in n re Mo tha .7 78 More than 23.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 9 5 Specifications Number of units that can be used together Connected units Compressor stop/start frequency Power source voltage 2-5 units Stop time 3 min or more Voltage fluctuation within ±10% of rated voltage Voltage drop during start within ±15% of rated voltage Interval unbalance within ±3% of rated voltage Table 3 2 Zone System 3 Zone System 4 Zone System 5 Zone System BMS500-AAM018-1CSX
1 0 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump 6 Outdoor unit installation Step 1: Select installation location The outdoor unit should be installed in the location that meets the following requirements: Place the outdoor unit as close to the indoor unit as possible. Ensure that there is enough room for installation and maintenance. The air inlet and outlet must not be obstructed or exposed to strong wind.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 11 Split type outdoor unit mounting dimensions Series installation Mounting Dimensions mm (in.) Outdoor Unit Dimensions mm (in.) WxHxD Distance A Distance B 845x702x363 (33.27x27.6x14.3) 540 (21.26) 350 (13.8) BMS500-AAM027-1CSXRA, BMS500-AAM027-1CSXHB, 946x810x410 BMS500-AAM036-1CSXRA, (37.24x31.9x16.14) BMS500-AAM036-1CSXHB 673 (26.5) 403 (15.87) BMS500-AAM036-1CSXHB, BMS500-AAM048-1CSXRA 634 (24.
1 2 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual Drain joint installation Drilling a hole in the wall Heat pump units require a drain joint. Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit. Note that there are two different types of drain joints depending on the type of outdoor unit.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 13 Connecting a 24k Btuh Indoor Unit A 24K Btuh indoor unit can only be connected to an A system connection point. If there are two 24K Btuh indoor units, they can be connected with the A and B connection points. (See Fig. 11) Connective pipe sizes Indoor unit capacity (Btu/h) 9k Liquid (in / mm) Gas (in / mm) 1/4" / Φ6.35 3/8" / Φ9.52 12k / 18k 1/4" / Φ6.35 1/2" / Φ12.7 24k 3/8" / Φ9.52 5/8" / Φ15.
1 4 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual 7 Refrigerant Piping Connection NOTICE: Be extra careful not to damage, kink, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit. WARNING: All field piping must be completed by a licensed technician and must comply with the local and national regulations.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 15 4. Remove tape from ends of pipe when ready to perform flaring work. Step 4: Connect pipes 5. Clamp flaring block on the end of the pipe. The end of the pipe must extend beyond the edge of the flare form in accordance with the dimensions shown in the Table 9. Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit.
1 6 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below. DO NOT bend the tubing more than 90° or more than 3 times. Radius 4 in (10 cm) or more Figure 18 6. After connecting the copper pipes to the indoor unit, wrap the power cable, signal cable and the piping together with binding tape. DO NOT intertwine signal cable with other wires.
Installation Manual 8 Wiring Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 17 8.1 Outdoor unit wiring WARNING: WARNING: ELECTRICAL HAZARD Be sure to disconnect the power supply before working on the unit. All electrical wiring must be done according to local and national regulations. Electrical wiring must be done by a qualified technician. Improper connections may cause electrical malfunction, injury and fire.
1 8 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual 8.2 Wiring Diagrams WARNING: ELECTRICAL HAZARD Connect the connective cables to the terminals, as identified, with their matching numbers on the terminal block of the indoor and outdoor units. For example, in the US models shown in the following diagram, Terminal L1(A) of the outdoor unit must connect with terminal L1 on the indoor unit.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 19 Two-Zone system Three-Zone system Magnetic ring (not supplied, optional part) (Used to hitch to the connective cable of indoor and outdoor units after installation.) Figure 21 Bosch Thermotechnology Corp. | 05.
2 0 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual Four-Zone system Five-Zone system Magnetic ring (not supplied, optional part) (Used to hitch to the connective cable of indoor and outdoor units after installation.) Figure 22 Data subject to change 05.2019 | Bosch Thermotechnology Corp.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 21 9 Air Evacuation 7. Wait for approximately 10 to 15 minutes, then check that there has been no change in system pressure. It is recommended to use a micron gauge; check to make sure the system is still below 500 microns. 8. If there is a change in system pressure, refer to Gas Leak Check section for information on how to check for leaks.
2 2 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual 9.3 Adding Refrigerant CAUTION: CONTAINS REFRIGERANT Refrigerant charging must be performed after wiring, vacuuming, and the leak testing. DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system. Doing so can damage the unit or impact its functionality. Charging with unsuitable substances may cause explosions or accidents.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 23 10 Electrical and Gas Leak Checks 10.2 Gas Leak Checks 10.1 Electrical Safety Checks There are two different methods to check for gas leaks. After installation, confirm that all electrical wiring is installed in accordance with local and national codes / regulations, and according to the Installation Manual. All testing must be performed by a licensed electrician.
2 4 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual 11 Test Run 11.1 Before Test Run A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test: Indoor and outdoor units are properly installed. Piping and wiring are properly connected. No obstacles near the inlet and outlet of the unit that might cause poor performance or product malfunction.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 25 12 Automatic Wiring/Piping Correction Function Climate 5000 models now feature automatic correction of wiring/piping errors. Press the "check switch" on the outdoor unit PCB board for 5 seconds until the LED displays "CE”, indicating that this function is working.
2 6 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump 13 Features and Operation 13.1 Protection of the Air Conditioner Compressor protection The compressor cannot restart for 3 minutes after it stops. Anti-cold air The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in one of the following three situations and the set temperature has not been reached.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 27 14 Troubleshooting WARNING: PROPERTY DAMAGE / PERSONAL INJURY If ANY of the following conditions occurs, turn off unit immediately! If a problem persists, contact a local dealer or your nearest customer service center. Provide them with a detailed description of the unit malfunction as well as your model number.
2 8 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Installation Manual 14.2 Error Codes CAUTION: SYSTEM FAILURE If below error codes appear, please turn off the system and contact an Authorized Service Provider.
Installation Manual Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump | 29 15 Disposal Guidelines Components Many parts in the Air Conditioner can be fully recycled in the end of the product life. Contact your city authorities for information about the disposal of recyclable products.
3 0 | Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump Data subject to change Installation Manual 05.2019 | Bosch Thermotechnology Corp.
Installation Manual Bosch Thermotechnology Corp. | 05.
United States and Canada Bosch Thermotechnology Corp. 65 Grove Street Watertown, MA 02472 Tel: 866-642-3198 Fax: 603-965-7581 www.boschheatingandcooling.com BTC 769003106 A / 05.